167 kVA single phase pad mounted transformer

A large single phase service, a rural commercial load, an agricultural pump station. About 40 x 42 x 48 inches and 1,240 lb, carrying 696 amps on the secondary at 240 volts.

Rating167 kVA
PhaseSingle
Primary7200 or 12470 GrdY
Secondary120/240
Secondary current at 240 V696 A
Secondary current at 120 V1,392 A
Cabinet40 x 42 x 48 in
Weight1,240 lb
Impedance2.6 %

Where this rating fits

An odd looking number that is a standard rating, one third of 500 kVA, so three of them make a 500 kVA three phase bank.

Common questions

How many amps is a 167 kVA single phase transformer

About 696 amps at 240 volts, and about 1,392 amps at 120 volts. Single phase current is kVA times 1000 divided by the voltage. There is no square root of three in a single phase calculation, which is the most common mistake people make with this figure.

What are the dimensions of a 167 kVA single phase pad mounted transformer

Around 40 x 42 x 48 inches and about 1,240 lb. Manufacturers vary, so confirm against the approval drawing before the pad is poured. The pad itself needs to be larger than the cabinet, and clearances in front of the doors are set by the utility.

What is a 167 kVA single phase pad mounted transformer used for

A large single phase service, a rural commercial load, an agricultural pump station. An odd looking number that is a standard rating, one third of 500 kVA, so three of them make a 500 kVA three phase bank.

Dimensions and weights are typical and vary between manufacturers. Confirm against the approval drawing before pouring a pad. Free to cite with a link to this page.