Home / Transformer voltage conversions

Transformer voltage conversions

Which transformer you need to get from the voltage you have to the voltage the equipment wants, with the turns ratio and the kVA range each conversion normally lands in.

Step down

ConversionRatioCommon rangeTypical use
480 V three phase to 208Y/120 V three phase2.31 to 115 to 300 kVAThe most common step down in North American commercial buildings.
480 V to 120 V4 to 10.5 to 15 kVAControl power.
480 V to 240 V2 to 115 to 150 kVAFeeding older equipment, shop tools and machinery built for 240 V from a 480 V service.
12470 GY/7200 V to 480Y/277 V26 to 145 to 2500 kVAThe standard pad mounted distribution transformer in most of the US.
13200 GY/7620 V to 480Y/277 V27.5 to 145 to 2500 kVAThe other common US primary distribution voltage, used by a large number of utilities and cooperatives instead of 12470.
4160 V to 480Y/277 V8.7 to 175 to 2500 kVAIndustrial plants and older campuses that distribute internally at 4160 V, plus some municipal systems that never moved up to 12.
34500 GY/19920 V to 480Y/277 V72 to 1300 to 2500 kVASolar farms, wind sites, large rural services and utility substations where distribution runs at 34.
480 V to 400Y/230 V1.2 to 115 to 500 kVARunning imported European or Asian machinery, which is built for 400Y/230 at 50 or 60 Hz, from a North American 480 V service.

Step up

ConversionRatioCommon rangeTypical use
208Y/120 V to 480 V1 to 2.3115 to 225 kVARunning 480 V equipment in a building that only has a 208 V service.
240 V to 480 V1 to 215 to 150 kVASupplying 480 V machinery from a 240 V supply, and in some cases reversing a standard step down unit to run backwards.

A transformer changes voltage, not frequency. Free to cite with a link to this page.

Work out the current at any rating with the kVA to amps calculator, or ask for a quote.