Pad Mounted Transformer Clearance Requirements

Clearance is set by the serving utility and by NESC, and it is a common reason a job fails inspection after everything else is right. The widely used figures are ten feet in front of the doors, three feet at the sides and rear, and ten feet from building openings and combustible walls. Your utility governs, so get their standard in writing early.

The commonly required clearances

DirectionTypical requirement
Front, the door side10 feet clear working space
Sides and rear3 feet
To building openings10 feet from doors, windows and air intakes
To combustible walls10 feet, or a fire barrier
OverheadClear for crane placement and future replacement

These are the figures most utilities use, and they are not a substitute for your serving utility's own standard. Get that standard in writing before the pad location is fixed. Moving a transformer after it is set is expensive and slow.

The one people forget

Vehicle protection. If the unit sits anywhere a truck can reach it, bollards are usually required, and that changes the pad layout. Decide it at design, not at inspection.

Need this checked against a real quote? Send it over and we will tell you what it does and does not include. No charge, and no obligation to buy from us.