Transformer sizing calculator

Enter a service size and voltage and get the kVA it implies, the smallest standard rating that covers it, and the same figures at 80 percent continuous.

Full rated load332.6 kVA
Smallest standard rating500 kVA
At 80 percent continuous266.0 kVA
Standard rating for that300 kVA

kVA equals amps times volts times the square root of three, divided by 1000. A service rating is the breaker size, not the actual load, so sizing straight off it usually oversizes the transformer. Size to measured or calculated demand where you have it, and use this as the upper bound.

Standard ratings, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500 kVA. Specifying a non standard number adds weeks of lead time and costs more than the size above it.

Common service sizes

What each service rating works out to, and the standard transformer rating that covers it. These are full rated figures, not derated to 80 percent.

ServiceAt 208Y/120RatingAt 480Y/277Rating
100 A36 kVA45 kVA83 kVA112.5 kVA
200 A72 kVA75 kVA166 kVA225 kVA
400 A144 kVA150 kVA333 kVA500 kVA
600 A216 kVA225 kVA499 kVA500 kVA
800 A288 kVA300 kVA665 kVA750 kVA
1000 A360 kVA500 kVA831 kVA1000 kVA
1200 A432 kVA500 kVA998 kVA1000 kVA
1600 A576 kVA750 kVA1330 kVA1500 kVA
2000 A721 kVA750 kVA1663 kVA2000 kVA
3000 A1081 kVA1500 kVA2494 kVA2500 kVA
4000 A1441 kVA1500 kVA3326 kVAover 2500

Standard ratings, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500 kVA. Free to cite with a link to this page. Size to real demand where you have it. A service rating is what the building could draw, not what it does.

Common questions

What size transformer is needed for a 200 amp service

At 208Y/120 volts a 200 amp service is about 72 kVA, so the smallest standard rating that covers it is 75 kVA. At 480Y/277 volts it is about 166 kVA, which takes a 225 kVA unit. The voltage matters as much as the amps, so a service described only in amps is not enough information to size a transformer.

What is the 80 percent rule for transformers

It is the continuous load allowance. Overcurrent devices are generally limited to 80 percent of their rating for loads running three hours or more, so a 400 amp service is treated as 320 amps of continuous capacity. Applied to transformer sizing it gives a smaller and usually more realistic number than the full service rating.

How do you calculate transformer kVA from amps

kVA equals amps times volts times the square root of three, divided by 1000, for a three phase system. For single phase leave out the square root of three. A 400 amp service at 480 volts three phase is 400 times 480 times 1.732 divided by 1000, which is about 333 kVA.

What are the standard kVA transformer sizes

For three phase liquid filled pad mounted units in the US, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000 and 2500 kVA. Specifying a number between those means a special build with a longer lead time and a worse price than the standard size above it.

Should I size a transformer to the service rating

It is an upper bound rather than an answer. A service rating is the breaker size, which is what the building could draw, not what it does draw. Sizing straight off it commonly oversizes the transformer, and an oversized unit costs more to buy and carries higher no load loss for its whole life.

Need the current rather than the rating. Use the kVA to amps calculator, or ask for a quote.