5 kVA transformer

Control or small dry type. Not a pad mounted transformer.

We supply liquid filled pad mounted distribution transformers. For a building service you need a distribution transformer. Pad mounted units start at 25 kVA. See three phase ratings and single phase ratings.

Full load current

ConfigurationFull load current
480 V single phase10 A
240 V single phase21 A
120 V single phase42 A

Nameplate full load current, computed from the standard formula. Free to cite with a link to this page. Any other rating, use the kVA to amps calculator.

What this rating is

A 5 kVA transformer is nearly always single phase, used for control power or a small dedicated circuit. 480 to 120 volts is the most common configuration, feeding contactor coils, instrumentation and a service receptacle inside a panel.

At 480 to 120 volts this delivers about 42 amps on the secondary. Size it on inrush rather than running load, because contactor coils draw several times their holding current when they pick up.

Common questions

How many amps is a 5 kVA transformer

About 10 amps at 480 V single phase. About 21 amps at 240 V single phase. About 42 amps at 120 V single phase. Three phase current is kVA times 1000 divided by the voltage times the square root of three. Single phase leaves out the square root of three, which is why the single phase figures are much higher.

What is a 5 kVA transformer used for

A 5 kVA transformer is nearly always single phase, used for control power or a small dedicated circuit. 480 to 120 volts is the most common configuration, feeding contactor coils, instrumentation and a service receptacle inside a panel.

Is a 5 kVA transformer pad mounted

No, it is a control or small dry type unit rather than a liquid filled pad mounted transformer. For a building service you need a distribution transformer. Pad mounted units start at 25 kVA.

Nearest pad mounted ratings