A transformer does not care which way power flows through it. Step up and step down describe how it is being used, not usually how it is built.

Step upStep down
What it doesRaises voltage, lowers currentLowers voltage, raises current
Turns ratioSecondary has more turns than primaryPrimary has more turns than secondary
Where usedAt generation, to push power long distancesAt the customer end, to make it usable
On a pad-mountRare, and only on generation or solar sitesThis is the normal case, 12470 down to 480
ReversibleMany units can be reverse fed with careSame unit, fed the other way

Which you actually need

A three phase pad-mounted distribution transformer is a step down unit in almost every installation, taking utility primary at 12470 or 13200 volts down to a usable 480Y/277 or 208Y/120. Reverse feeding a step down unit to step up is possible but it changes the impedance seen by the system and voids some warranties, so check with the manufacturer rather than assuming.