Substation and Pad Mounted Transformers Compared

Both step distribution voltage down to utilisation voltage. The difference is how they connect and who owns them.

Substation transformerPad mounted transformer
EnclosureOpen frame, or close coupled to switchgearSelf contained locked cabinet
ConnectionBolted throat to primary and secondary gearCable, elbows on the primary
LocationIndoors or in a fenced yardOutdoors at grade, public accessible
OwnershipUsually the customerOften the utility, sometimes the customer
Typical rating750 kVA up to several MVA45 to 2500 kVA
Who specifiesThe electrical engineerThe serving utility standard
Primary connectionBolted bus or cable throatLoad break elbows on dead front bushings
Secondary connectionClose coupled to switchgearCable to a panel or switchboard
WeatherOften indoor or under coverFully outdoor rated as supplied
Maintenance accessRequires an outage and qualified staffFront access, locked, utility serviceable

Which you actually need

If the utility owns the transformer and the service is underground, it is a pad-mount and the utility standard governs everything about it. If you own it and it feeds your own switchgear, a unit substation is often the better answer above about 1000 kVA.

Above roughly 1000 kVA the question usually resolves itself. A unit substation close coupled to your own switchgear removes a set of cable terminations and is easier to protect selectively, so it tends to win on larger customer owned services.

Below that, and wherever the utility owns the transformer, a pad-mount is nearly always what gets installed, because the utility standard says so and the utility standard is not negotiable.

Working from a specification that uses one of these terms loosely? Send it over and we will tell you which equipment it is actually calling for, before you order the wrong thing. Get a quote or call 786 220 2801.