Padmount Supply

Home / Ratings / 750 kVA pad mounted transformer

750 kVA pad mounted transformer

Three phase, liquid-filled, dead front, loop feed. Typically heavy industrial, small data hall.

Rating
750 kVA
Dimensions, in
80 x 72 x 78
Weight
6,600 lb
Impedance
5.75%
Amps at 480 V
902

Full load current

ConfigurationFull load current
480Y/277 three phase, secondary902 A
208Y/120 three phase, secondary2,082 A
12470 GY/7200 three phase, primary34.7 A
13200 GY/7620 three phase, primary32.8 A

Nameplate full load current at 750 kVA, from kVA times 1000 divided by the voltage times the square root of three. Free to cite with a link to this page. Any other rating or voltage, use the kVA to amps calculator.

Standard configuration

Primary12470 GY/7200 or 13200 GY/7620
Secondary480Y/277, also 208Y/120 on smaller ratings
StandardsANSI/IEEE C57.12.34 and C57.12.00
EfficiencyDOE 2016 per 10 CFR Part 431
Temperature rise65 C
FluidMineral oil, FR3 natural ester on request
FrontDead front with separable elbow connectors
FeedLoop feed, six primary bushings. Radial available
TapsTwo above and two below nominal at 2.5 percent, full capacity
ULListed under CCN XPLH, liquid-filled distribution over 600 V

What to check before you order

  • Primary voltage and taps. A unit built at 12470 GY/7200 with a 13200 tap covers both common systems, but only if the taps are full capacity. How taps work
  • Dead front or live front. Most utilities will not accept live front on new work. The difference
  • Loop or radial feed. Loop feed needs six bushings and costs more. Which you need
  • Pad and clearance. At 6,600 lb this needs a proper pad and crane access. Clearance rules
  • Freight. A unit this size ships on a flatbed and often needs a crane at the far end. Freight quoted separately is the single most common surprise on a transformer order.

Who builds this rating

We quote this rating on every route we can buy it, delivered and factory, and we tell you which is which. Send us your spec or call 786 220 2801.

Common questions on this rating

WeightAbout 6,600 lb including fluid
DimensionsRoughly 80 x 72 x 78 in, width by depth by height
Amps at 480Y/277About 902 A full load, 34.7 A on a 12470 primary
Impedance5.75 percent, needed for any coordination study
Lead time40 to 60 weeks new from a US factory, days from stock
PriceWhat drives the number, then get it quoted