Home / Charts / Commercial electrical service sizes, amps, kVA and transformer

Commercial electrical service sizes, amps, kVA and transformer

Commercial services come in standard steps of 200, 400, 600, 800, 1200, 1600, 2000, 3000 and 4000 amps. An 800 amp service at 480Y/277 V is 665 kVA and is fed by a 750 kVA transformer. The same 800 amps at 208Y/120 V is only 288 kVA, fed by a 300 kVA unit. Every size is in the chart below with the kVA at both voltages, the transformer for the full rating and the type of equipment it takes. Enter any service in the calculator for the exact figure.

Service capacity665 kVA
Transformer for the full rating750 kVA
Ground fault protectionnot at this size

kVA equals amps times volts times 1.732, divided by 1000. The transformer shown carries the full service rating. The utility sizes its own transformer on the calculated load, which is often smaller, so treat this as the upper bound.

Service size chart, 100 to 4000 amps

kVA is the full capacity of the service, amps times volts times 1.732 divided by 1000. The transformer column is the smallest standard three phase pad mounted rating that can carry the full service rating. Above 2500 kVA a site usually moves to a unit substation or to several services.

ServicekVA at 208Y/120Transformer at 208 VkVA at 480Y/277Transformer at 480 VEquipment
100 A3645 kVA83112.5 kVAPanelboard
200 A7275 kVA166225 kVAPanelboard
400 A144150 kVA333500 kVAPanelboard
600 A216225 kVA499500 kVAPanelboard or switchboard
800 A288300 kVA665750 kVAPanelboard or switchboard
1,000 A360500 kVA8311000 kVAPanelboard or switchboard
1,200 A432500 kVA9981000 kVAPanelboard or switchboard
1,600 A576750 kVA1,3301500 kVASwitchboard or switchgear
2,000 A721750 kVA1,6632000 kVASwitchboard or switchgear
2,500 A9011000 kVA2,0782500 kVASwitchboard or switchgear
3,000 A1,0811500 kVA2,4942500 kVASwitchboard or switchgear
4,000 A1,4411500 kVA3,326over 2500 kVA, unit substationSwitchboard or switchgear

Free to cite with a link to this page. kVA is computed. The equipment column follows the panelboard and switchboard ranges published by Tech Energy America. Panelboards top out at 1200 A.

What each transformer size can feed

Read the other way, a transformer rating sets the largest service it can carry at full load. A 500 kVA transformer delivers 601 A at 480 V, which matches a 600 A service, and 1,388 A at 208 V.

TransformerFull load amps at 208Y/120Full load amps at 480Y/277
112.5 kVA312 A135 A
150 kVA416 A180 A
225 kVA625 A271 A
300 kVA833 A361 A
500 kVA1,388 A601 A
750 kVA2,082 A902 A
1000 kVA2,776 A1,203 A
1500 kVA4,164 A1,804 A
2000 kVA5,551 A2,406 A
2500 kVA6,939 A3,007 A

Free to cite with a link to this page. Full load amps equal kVA times 1000 divided by volts times 1.732.

208 or 480 volts

The same amps carry 2.3 times as much power at 480 V as at 208 V. A 1200 A service is 432 kVA at 208Y/120 and 998 kVA at 480Y/277. 208Y/120 suits a building whose load is mostly 120 V lighting and receptacles. 480Y/277 suits large motor and HVAC loads, with lighting at 277 V and dry type transformers inside the building stepping down to 208Y/120 for receptacles.

Going to 480 V shrinks the service gear and the feeders for the same load. A 2000 A load at 208 V becomes about 867 A at 480 V.

How many amps per square foot

The 2020 NEC cut the general lighting load for most occupancies. Office buildings dropped from 3.5 to 1.3 VA per square foot. The 2023 NEC renumbered the table as 220.42(A). Lighting is only part of a commercial load, and receptacles, HVAC, kitchen equipment and motors are added on top, so the totals below are a floor for the lighting part, not a service size.

EC&M worked a 300,000 square foot office building on 480Y/277 V. At the old 3.5 VA its lighting needed about 1,260 A of service. At 1.3 VA it needs about 469 A.

OccupancyLighting VA per sq ft10,000 sq ft at 480 V50,000 sq ft at 480 V100,000 sq ft at 480 V
Office1.313 kVA, 16 A65 kVA, 78 A130 kVA, 156 A
Retail1.919 kVA, 23 A95 kVA, 114 A190 kVA, 229 A
Warehouse0.252 kVA, 3 A12 kVA, 15 A25 kVA, 30 A

Lighting load only, computed from the 2020 NEC Table 220.12 unit loads as published by EC&M and exam prep references. Check the edition your jurisdiction enforces.

Ground fault protection at 1000 amps and up

NEC 230.95 requires ground fault protection of equipment on a solidly grounded wye service of more than 150 V to ground where the service disconnect is rated 1000 A or more. In practice that means every 480Y/277 V service of 1000 A or more. A 208Y/120 V service is not covered because it is only 120 V to ground.

The maximum setting is 1200 A, the maximum time delay is one second at 3000 A of ground fault current, and the system has to be performance tested when it is first installed. Budget for the test and the relay when you price a 1200 A or larger 480 V service.

Panelboard, switchboard or switchgear

Lead times differ by an order of magnitude. Tech Energy America lists a 400 A Eaton PRL panelboard at 1 to 2 weeks from its stock and 5 to 7 weeks from the factory, an 800 to 1600 A switchboard at 10 to 14 weeks, and 1600 to 4000 A switchgear at 16 to 26 weeks.

  • Panelboards (UL 67) are wall mounted, front access and carry up to 1200 A. Most tenant services from 100 to 400 A are panelboards with a main breaker
  • Switchboards (UL 891) are free standing and typically run from 800 to 4000 A. Most service entrances of 800 A and up are switchboards
  • Switchgear (UL 1558) is used where the fault current or the size calls for it. Tech Energy America lists low voltage switchgear from 1600 to 4000 A

Who owns the transformer

On many services the utility owns and sizes the pad mounted transformer and the customer owns everything from the meter on. Primary metered customers buy their own transformer, and then the service size, the transformer rating and the lead time are all the customer's problem. If that is you, the chart above gives the starting rating and the pad mounted transformer pages give amps, dimensions and weights for each one.

Common questions

What are the standard commercial electrical service sizes

100, 200, 400, 600, 800, 1000, 1200, 1600, 2000, 2500, 3000 and 4000 amps, the bus and main breaker ratings that switchboard makers build to. Most small commercial buildings have 200 to 800 A, larger buildings 1200 to 4000 A.

What size transformer do I need for an 800 amp service

At 480Y/277 V an 800 A service is 665 kVA, so a 750 kVA transformer carries it at full rating. At 208Y/120 V it is 288 kVA, so a 300 kVA transformer. The utility may install a smaller one sized on the calculated load.

What size transformer for a 1200 amp service

1000 kVA at 480Y/277 V, since 1200 A is 998 kVA. At 208Y/120 V it is 432 kVA, which takes a 500 kVA transformer.

How many kVA is a 400 amp 3 phase service

144 kVA at 208Y/120 V and 333 kVA at 480Y/277 V.

When is ground fault protection required on a service

Under NEC 230.95, on a solidly grounded wye service of more than 150 V to ground with a service disconnect rated 1000 A or more. That covers 480Y/277 V services of 1000 A and up and excludes 208Y/120 V.

How many amps per square foot for a commercial building

For the lighting part, the 2020 NEC uses 1.3 VA per square foot for offices, 1.9 for retail and 0.25 for warehouses. At 480Y/277 V, 10,000 square feet of office lighting is about 16 A. Receptacles, HVAC and equipment are added on top and usually dominate.

Can a panelboard be a 1200 amp service

Yes, panelboards are made up to 1200 A, but above about 800 A most service entrances are switchboards, which take larger mains and more metering and distribution sections.

Related pages

Sources

Free to cite with a link to this page. Always check the edition of the code your inspector enforces.