Home / Tools / How many grow lights per circuit
How many grow lights per circuit
A 20 amp, 120 volt circuit carries 1 magnetic 1000 W HPS lights or 3 LED fixtures of about 630 W, because grow lights are a continuous load and a breaker may only be loaded to 80 percent. Move the same circuit to 240 V and it carries twice as many. Pick your light below for amps, lights per circuit and the monthly electricity cost.
Lights that run 3 hours or more are a continuous load, so each circuit is loaded to 80 percent of the breaker. A month is 30 days. Ballast and driver losses are already in the wall watts. Fans, dehumidifiers and air conditioning are extra.
Lights per circuit, by breaker and voltage
Each cell is the number of lights a circuit can carry at 80 percent of the breaker. The usable amps are 12 A on a 15 A breaker, 16 A on a 20 A breaker, 24 A on a 30 A breaker, 32 A on a 40 A breaker, 40 A on a 50 A breaker. 120 and 277 V circuits are single pole, 208 and 240 V circuits are two pole.
1000 W HPS, magnetic ballast, 1128 W at the wall
| Breaker | 120 V | 208 V | 240 V | 277 V |
|---|---|---|---|---|
| Amps per light | 9.70 A | 5.60 A | 4.90 A | 4.20 A |
| 15 A | 1 | 2 | 2 | 2 |
| 20 A | 1 | 2 | 3 | 3 |
| 30 A | 2 | 4 | 4 | 5 |
| 40 A | 3 | 5 | 6 | 7 |
| 50 A | 4 | 7 | 8 | 9 |
315 W CMH fixture, 343 W at the wall
| Breaker | 120 V | 208 V | 240 V | 277 V |
|---|---|---|---|---|
| Amps per light | 2.89 A | 1.60 A | 1.43 A | 1.30 A |
| 15 A | 4 | 7 | 8 | 9 |
| 20 A | 5 | 10 | 11 | 12 |
| 30 A | 8 | 15 | 16 | 18 |
| 40 A | 11 | 20 | 22 | 24 |
| 50 A | 13 | 25 | 27 | 30 |
Gavita Pro 1700e LED, 630 W at the wall
| Breaker | 120 V | 208 V | 240 V | 277 V |
|---|---|---|---|---|
| Amps per light | 5.30 A | 3.03 A * | 2.63 A * | 2.30 A |
| 15 A | 2 | 3 | 4 | 5 |
| 20 A | 3 | 5 | 6 | 6 |
| 30 A | 4 | 7 | 9 | 10 |
| 40 A | 6 | 10 | 12 | 13 |
| 50 A | 7 | 13 | 15 | 17 |
HLG 650R LED, 630 W at the wall
| Breaker | 120 V | 208 V | 240 V | 277 V |
|---|---|---|---|---|
| Amps per light | 5.40 A | 3.03 A * | 2.62 A | 2.27 A * |
| 15 A | 2 | 3 | 4 | 5 |
| 20 A | 2 | 5 | 6 | 7 |
| 30 A | 4 | 7 | 9 | 10 |
| 40 A | 5 | 10 | 12 | 14 |
| 50 A | 7 | 13 | 15 | 17 |
Spider Farmer SF4000 EVO LED, 450 W at the wall
| Breaker | 120 V | 208 V | 240 V | 277 V |
|---|---|---|---|---|
| Amps per light | 3.79 A | 2.16 A * | 1.86 A | 1.62 A * |
| 15 A | 3 | 5 | 6 | 7 |
| 20 A | 4 | 7 | 8 | 9 |
| 30 A | 6 | 11 | 12 | 14 |
| 40 A | 8 | 14 | 17 | 19 |
| 50 A | 10 | 18 | 21 | 24 |
Free to cite with a link to this page. Amps are the line current on the maker sheet for that voltage. A star marks a voltage the sheet does not list, computed as watts divided by volts, which is close for LED drivers with a power factor near 1. Check the sheet for your exact model, and never count the start up current of a magnetic ballast as running load.
Why only 80 percent of the breaker
The National Electrical Code calls a load that runs for 3 hours or more a continuous load, and grow lights on a 12 or 18 hour cycle are exactly that. Sections 210.19 and 210.20 require the branch circuit conductors and the breaker to be rated at no less than the non continuous load plus 125 percent of the continuous load. Dividing 1 by 1.25 gives 0.8, which is where the 80 percent rule of thumb comes from. A 20 A breaker carries 16 A of lights, a 30 A breaker 24 A.
The exception is a breaker and enclosure listed for 100 percent continuous duty, which the breaker label states. A standard branch breaker is not, so plan on 80 percent unless the label says otherwise.
Monthly electricity use and cost
kWh a month is watts times hours a day times 30, divided by 1000. The table is for a room of 8 lights. Put in your own utility rate above, since rates vary widely by state and by tariff.
| 8 lights | Hours a day | kWh a month | $0.10/kWh | $0.15/kWh | $0.20/kWh | $0.30/kWh |
|---|---|---|---|---|---|---|
| 1000 W HPS, magnetic ballast | 18 | 4,873 | $487 | $731 | $975 | $1,462 |
| 1000 W HPS, magnetic ballast | 12 | 3,249 | $325 | $487 | $650 | $975 |
| 315 W CMH fixture | 18 | 1,482 | $148 | $222 | $296 | $445 |
| 315 W CMH fixture | 12 | 988 | $99 | $148 | $198 | $296 |
| Gavita Pro 1700e LED | 18 | 2,722 | $272 | $408 | $544 | $816 |
| Gavita Pro 1700e LED | 12 | 1,814 | $181 | $272 | $363 | $544 |
| HLG 650R LED | 18 | 2,722 | $272 | $408 | $544 | $816 |
| HLG 650R LED | 12 | 1,814 | $181 | $272 | $363 | $544 |
| Spider Farmer SF4000 EVO LED | 18 | 1,944 | $194 | $292 | $389 | $583 |
| Spider Farmer SF4000 EVO LED | 12 | 1,296 | $130 | $194 | $259 | $389 |
Lights only. Air conditioning, dehumidifiers and fans often add as much again, so size the service on the whole room, not the lights.
Moving from 120 V to 240 or 277 V
The three LED fixtures above accept any input from 120 to 277 V. The watts stay the same, so the bill does not change, but the current falls as the voltage rises. A Gavita 1700e draws 5.3 A at 120 V and 2.3 A at 277 V, so a 20 A circuit goes from 3 lights to 6. Fewer circuits means fewer breakers, less copper and a smaller panel. A building with 480Y/277 V service can run lights straight off 277 V, and a 480 to 240 V transformer or a 480 to 120 V transformer feeds anything that cannot. The 220 V versus 240 V guide explains why the same circuit goes by both names.
When the grow outgrows the service
Add up the lights, the cooling and the dehumidifiers in kW. Run the total through the kW to amps calculator and compare it with 80 percent of the main breaker. Forty 630 W LEDs alone are 25.20 kW of continuous load before any air conditioning. A large grow usually ends up on 208 or 480 V three phase with its own transformer. The kVA to amps calculator shows what each transformer size delivers, and the commercial service sizes chart maps every service from 100 to 4000 A to the transformer that feeds it.
Common questions
How many grow lights can I put on a 20 amp circuit
On 120 V a 20 A breaker can carry 16 A of continuous load. That is 1 magnetic 1000 W HPS lights at 9.7 A each, 3 Gavita 1700e LEDs at 5.3 A each, or 5 315 W CMH fixtures at 2.89 A each.
How many 1000 watt lights on a 30 amp 240 volt circuit
4. A 30 A breaker carries 24 A of continuous load, and a magnetic 1000 W HPS ballast draws about 4.9 A at 240 V. For LED fixtures of about 630 W the answer is 9.
How many amps does a 1000 watt HPS light draw
About 9.7 A at 120 V, 5.6 A at 208 V, 4.9 A at 240 V and 4.2 A at 277 V with a magnetic ballast, from the ballast maker sheets. A 1000 W lamp draws more than 1000 W at the wall because the ballast has losses, about 1128 W on the Keystone sheet.
Why can I only use 80 percent of a breaker
Grow lights run for hours at a time, which makes them a continuous load, a load that runs for 3 hours or more. The National Electrical Code requires a breaker rated at no less than 125 percent of a continuous load, which works out to loading a standard breaker to 80 percent of its rating. A breaker listed for 100 percent continuous duty is the exception, so check the breaker label.
Is 240 volts cheaper to run than 120 volts
No. A light uses the same watts, and you pay for kWh, so the bill is the same. What 240 V changes is the current. It halves the amps, so each circuit carries twice as many lights and the wire and panel space go further.
How much electricity does a grow light use a month
Watts times hours a day times 30, divided by 1000. One 630 W LED on 18 hours a day uses 340 kWh a month, and on 12 hours 227 kWh. At $0.15 a kWh that is about $51 and $34.
When does a grow room need a bigger service or a transformer
When the lighting, air conditioning and dehumidifiers add up to more than the service can carry continuously. Larger grows usually move to 208 or 480 V three phase, which brings a utility or customer owned transformer. Add up the total kW and run it through the kW to amps calculator to see where you land.
Sources
- IAEI Magazine, 100 vs 80, choosing the right overcurrent device (NEC 210.20 continuous load rule)
- Fulham, 1000 W HPS ballast specification sheet
- Keystone, HPS-1000A-Q-KIT ballast specification sheet
- EC&M, NEC branch circuit overcurrent protection and continuous loads
- Iluminar, 315 W CMH fixture manual
- Luxx Lighting, 315 W CMH specifications
- Gavita, Pro 1700e LED manual
- Horticulture Lighting Group, 650R manual
- Spider Farmer SF4000 EVO specifications, via Trimleaf
Planning a grow that needs three phase power. Request a transformer quote.