kW to amps calculator

A 100 kW three phase load at 480 V draws 142 A at a power factor of 0.85. Enter any kW or amps, voltage, phase and power factor below, or read the answer straight off the charts.

Current142 A
Real power100 kW
Apparent power118 kVA

Three phase amps equal kW times 1000 divided by root 3 times line to line volts times power factor. Single phase drops the root 3. DC drops the power factor too. Transformers are sized on the kVA figure, not the kW figure.

The formulas

SystemkW to ampsAmps to kW
Three phaseA = kW x 1000 / (1.732 x V x PF)kW = A x 1.732 x V x PF / 1000
Single phaseA = kW x 1000 / (V x PF)kW = A x V x PF / 1000
DCA = kW x 1000 / VkW = A x V / 1000

V is line to line voltage on three phase, so 480 on a 480Y/277 system and 208 on a 208Y/120 system. PF is power factor, a number between 0 and 1. The most common mistake is using the single phase formula on a three phase load, which overstates the current by a factor of 1.732.

Amps per kW by voltage

Multiply your kW by the figure in the row for your voltage. At 480 V three phase and unity power factor every kW draws 1.20 A.

SystemPF 1.00PF 0.90PF 0.85PF 0.80
120 V single phase8.33 A9.26 A9.80 A10.42 A
208 V three phase2.78 A3.08 A3.27 A3.47 A
240 V single phase4.17 A4.63 A4.90 A5.21 A
240 V three phase2.41 A2.67 A2.83 A3.01 A
277 V single phase3.61 A4.01 A4.25 A4.51 A
400 V three phase1.44 A1.60 A1.70 A1.80 A
480 V three phase1.20 A1.34 A1.42 A1.50 A
600 V three phase0.96 A1.07 A1.13 A1.20 A

Free to cite with a link to this page. Every figure is computed from the formulas above.

kW to amps chart, three phase

Current per phase at a power factor of 0.85, about what a fully loaded induction motor runs at. The last column is the kVA the load needs and the smallest standard three phase transformer that covers it.

kW208 V240 V480 V600 VkVATransformer
13.3 A2.8 A1.4 A1.1 A1.245 kVA
516.3 A14.2 A7.1 A5.7 A5.945 kVA
7.524.5 A21.2 A10.6 A8.5 A8.845 kVA
1032.7 A28.3 A14.2 A11.3 A11.845 kVA
1549.0 A42.5 A21.2 A17.0 A17.645 kVA
2065.3 A56.6 A28.3 A22.6 A23.545 kVA
2581.6 A70.8 A35.4 A28.3 A29.445 kVA
3098.0 A84.9 A42.5 A34.0 A35.345 kVA
40131 A113 A56.6 A45.3 A47.175 kVA
50163 A142 A70.8 A56.6 A58.875 kVA
60196 A170 A84.9 A67.9 A70.675 kVA
75245 A212 A106 A84.9 A88.2112.5 kVA
100327 A283 A142 A113 A118150 kVA
125408 A354 A177 A142 A147150 kVA
150490 A425 A212 A170 A176225 kVA
200653 A566 A283 A226 A235300 kVA
250816 A708 A354 A283 A294300 kVA
300980 A849 A425 A340 A353500 kVA
4001,306 A1,132 A566 A453 A471500 kVA
5001,633 A1,415 A708 A566 A588750 kVA
6001,959 A1,698 A849 A679 A706750 kVA
7502,449 A2,123 A1,061 A849 A8821000 kVA
8002,612 A2,264 A1,132 A906 A9411000 kVA
10003,266 A2,830 A1,415 A1,132 A1,1761500 kVA
12504,082 A3,538 A1,769 A1,415 A1,4711500 kVA
15004,898 A4,245 A2,123 A1,698 A1,7652000 kVA
20006,531 A5,660 A2,830 A2,264 A2,3532500 kVA
25008,164 A7,075 A3,538 A2,830 A2,941over 2500

Free to cite with a link to this page. For unity power factor loads such as resistive heat, multiply any figure by 0.85. The transformer column is the next standard pad mounted rating and leaves no room for growth, so check it with the sizing calculator.

kW to amps chart, single phase

kW120 V, PF 1.0120 V, PF 0.85240 V, PF 1.0240 V, PF 0.85
18.3 A9.8 A4.2 A4.9 A
1.512.5 A14.7 A6.3 A7.4 A
216.7 A19.6 A8.3 A9.8 A
325.0 A29.4 A12.5 A14.7 A
541.7 A49.0 A20.8 A24.5 A
7.562.5 A73.5 A31.3 A36.8 A
1083.3 A98.0 A41.7 A49.0 A
12100 A118 A50.0 A58.8 A
15125 A147 A62.5 A73.5 A
20167 A196 A83.3 A98.0 A
25208 A245 A104 A123 A
30250 A294 A125 A147 A
40333 A392 A167 A196 A
50417 A490 A208 A245 A

Free to cite with a link to this page.

kW, kVA and why power factor matters

kW is real power, the part that turns a shaft or heats a room. kVA is apparent power, volts times amps, and it is what wires, breakers and transformers actually carry. The two are equal only at a power factor of 1.0. Below that, kVA equals kW divided by power factor, so a 100 kW load at 0.8 needs 125 kVA of transformer. The kVA to kW calculator converts between the two, and the kVA to amps calculator gives current straight from a transformer rating.

LoadTypical power factor
Resistive heating, incandescent lamps1.0
Fluorescent lamps with compensationabout 0.93
Induction motor at full loadabout 0.85
Induction motor at half loadabout 0.73
Induction motor at a quarter loadabout 0.55
Uncorrected industrial plantabout 0.8
Fluorescent lamps without compensationabout 0.5

Typical values from the published sources listed at the end of this page. A lightly loaded motor draws more current per kW than a fully loaded one, so measure where you can.

Picking a transformer from a kW load

Divide the total kW by the power factor to get kVA, then choose the next standard rating up. A 400 kW load at 0.85 is 471 kVA, which points to a 500 kVA pad mounted transformer. The three phase formulas page covers primary current, turns ratio and fault current, and the transformers for sale page lists every standard rating we quote. The commercial service sizes chart maps each service from 100 to 4000 A to its transformer, and the grow light circuit calculator works out lights per breaker and the monthly cost for a grow room. For a motor load, the HP to kVA calculator converts horsepower to the kVA to size from.

Common questions

How do you convert kW to amps in three phase

Multiply kW by 1000 to get watts, then divide by root 3 (1.732), the line to line voltage and the power factor. A 100 kW load at 480 V and a power factor of 0.85 draws 142 A per phase.

How many amps is 100 kW at 480 volts

142 A at a power factor of 0.85, and 120 A at unity power factor, three phase. The lower the power factor the more current the same kW needs.

How many amps is 10 kW three phase

At 208 V and a power factor of 0.85 it is 32.7 A. At 480 V it is 14.2 A. Use the chart above for other voltages.

How many amps is 7.5 kW single phase

At 240 V and unity power factor, such as a resistive heater, it is 31.3 A. At 120 V it is 62.5 A.

How do you convert amps to kW

Reverse the formula. Three phase kW equals amps times root 3 times volts times power factor, divided by 1000. So 200 A at 480 V and a power factor of 0.85 is 141 kW.

Why does power factor change the amps

Real power in kW is only the part of the current that does work. A load with a low power factor draws extra reactive current on top, so it needs more amps for the same kW. Wires, breakers and transformers have to carry the total current, which is why they are sized in amps and kVA.

What power factor should I use

Use the nameplate or a measured figure if you have one. Published guidance puts resistive heating and incandescent lighting at 1.0, an induction motor at about 0.85 at full load falling to about 0.55 at a quarter load, and a typical uncorrected industrial plant at about 0.8.

Sources