Apparent power, real power and current are three views of the same load once voltage and power factor are fixed. All three are shown together.

Real power270.0 kW
Reactive power130.8 kVAR
Full load current361 A

kW equals kVA times power factor. Reactive power is the part that does no work but still heats the conductors, which is why transformers are rated in kVA rather than kW. Power factor of 0.9 is a reasonable default for a mixed commercial load, but use the real figure if you have it.

Typical power factors

Power factorTypical of300 kVA gives
1.0Resistive heating, incandescent lighting300 kW
0.95Modern LED lighting, corrected commercial load285 kW
0.9Typical mixed commercial building270 kW
0.85Light industrial with motors255 kW
0.8Motor heavy industrial, uncorrected240 kW

Free to cite with a link to this page. The spread between 0.8 and 0.95 on the same 300 kVA transformer is 45 kW of real power, which is frequently a whole transformer size in a sizing exercise.

Common questions

What does kVA mean on a transformer

Kilovolt amperes, which is apparent power. It is voltage times current with no allowance for power factor. Transformers are rated in kVA because heating depends on current regardless of whether that current is doing useful work, and heating is what limits the machine.

How do you convert kVA to kW

Multiply kVA by the power factor. A 300 kVA transformer at a power factor of 0.9 delivers 270 kW of real power. To go the other way, divide kW by the power factor.

Why are transformers rated in kVA and not kW

Because the transformer does not know what the load is doing with the current. Reactive current heats the windings exactly as much as real current does, so the limit is total current, which is apparent power. Rating in kW would mean the same transformer had a different rating for every load connected to it.

What is a typical power factor

Around 0.9 for a mixed commercial building, 0.85 or lower for motor heavy industrial, and close to 1.0 for resistive loads such as heating. Use the measured figure where you have one, because the difference between 0.8 and 0.95 is a whole transformer size.

Sizing a transformer from a service rating instead. Use the sizing calculator, or the kVA to amps calculator for current.