Conduit fill calculator for EMT

Pick an EMT size, add groups of THHN conductors and see the percent fill against the NEC limit of 53, 31 or 40 percent. It also names the smallest EMT that works. The chart below lists the most conductors of each size per EMT trade size.

Updated November 18, 2026

Total conductor area0.0798 sq in
Fill in 1 EMT9.2 percent
Limit for 6 conductors40 percent
ResultPasses
Smallest EMT that passes1/2 inch

Uses THHN, THWN and THWN-2 areas from NEC Chapter 9 Table 5 and EMT areas from Table 4. Count every conductor, including equipment grounding conductors.

Rules in short

  • One conductor 53 percent, two conductors 31 percent, three or more 40 percent of the conduit area.
  • Count every conductor, including the equipment grounding conductor.
  • Use Table 5 conductor areas and Table 4 conduit areas, never the bare copper size.
  • Nipples of 24 inches or less may be filled to 60 percent.
  • Heat and bundling also limit ampacity, see the wire ampacity chart.

EMT areas and fill limits, square inches

EMT trade sizeTotal area53 percent31 percent40 percent
1/20.3040.1610.0940.122
3/40.5330.2820.1650.213
10.8640.4580.2680.346
1-1/41.4960.7930.4640.598
1-1/22.0361.0790.6310.814
23.3561.7791.0401.342
2-1/25.8583.1051.8162.343
38.8464.6882.7423.538
414.7537.8194.5735.901

THHN conductor areas, square inches

SizeArea
14 AWG0.0097
12 AWG0.0133
10 AWG0.0211
8 AWG0.0366
6 AWG0.0507
4 AWG0.0824
3 AWG0.0973
2 AWG0.1158
1 AWG0.1562
1/0 AWG0.1855
2/0 AWG0.2223
3/0 AWG0.2679
4/0 AWG0.3237
250 kcmil0.3970
300 kcmil0.4608
350 kcmil0.5242
400 kcmil0.5863
500 kcmil0.7073

Maximum THHN conductors in EMT, same size wires

Counts are the most conductors of one size that fit at the 40 percent limit. A count of 1 or 2 uses the 53 or 31 percent limit.

Conductor1/23/411-1/41-1/222-1/234
14 AWG1221356183138241364608
12 AWG916254461100176266443
10 AWG51016283863111167279
8 AWG3591622366496161
6 AWG1461116264669116
4 AWG1247916284271
3 AWG1136813243660
2 AWG1125711203050
1 AWG111358152237
1/0 AWG-11347121931
2/0 AWG-11236101526
3/0 AWG-1113581322
4/0 AWG--111471018
250 kcmil--11135814
300 kcmil---1125712
350 kcmil---1114611
400 kcmil---1113610
500 kcmil---111358

Large feeders from a padmount transformer

A 4 inch EMT at 40 percent holds 5.901 square inches, which fits 8 conductors of 500 kcmil. A 3 inch EMT holds 5. Secondary feeders from a pad mount are usually several parallel sets, so confirm the count against the sets, the neutral and the ground before choosing sizes. Size current with the kVA to amps calculator, voltage drop with the voltage drop calculator, and read the pad mounted transformer installation guide and dimensions for the secondary compartment.

Ordering a padmount for a feeder you have already sized, request a quote.

Put this calculator on your site

Free for contractors, electricians, schools and trade sites. Paste this code into any page.

Common questions

What is the conduit fill limit

NEC Chapter 9 Table 1 allows 53 percent of the conduit cross section for one conductor, 31 percent for two and 40 percent for three or more. Equipment grounding conductors count as conductors.

How many wires fit in 3/4 inch EMT

Three or more THHN conductors may fill 40 percent of 0.533 square inches, or 0.213 square inches. That is 16 conductors of 12 AWG (0.0133 each), 21 of 14 AWG and 10 of 10 AWG. Check the chart below for other sizes.

How many wires fit in 1/2 inch EMT

At 40 percent of 0.304 square inches the limit is 0.122 square inches, which holds 12 conductors of 14 AWG, 9 of 12 AWG and 5 of 10 AWG.

How do you calculate conduit fill

Add the area of every conductor from Chapter 9 Table 5, then divide by the conduit area from Table 4. The result must not exceed 40 percent for three or more conductors. The calculator above does the sum and finds the smallest EMT that passes.

Does the 40 percent rule apply to short nipples

No. Chapter 9 allows a 60 percent fill for a conduit or tubing nipple 24 inches or shorter between boxes or enclosures. The 40 percent rule is for ordinary runs.

Can I use this chart for PVC or rigid conduit

Not directly. The internal area differs by conduit type and schedule, so use the area from Table 4 for that type. The method of summing conductor areas and comparing against 40 percent is the same.

Sources

  • EMT internal areas for trade sizes 1/2 to 4 inch from NEC Chapter 9 Table 4, as reproduced by Steel Tube Institute, Conduit Bending, Zing2 and Wire Fill Chart. The 3-1/2 inch size was not confirmed and is left out.
  • THHN, THWN and THWN-2 conductor areas from NEC Chapter 9 Table 5 for 14 AWG to 500 kcmil, as reproduced by Wire Fill Chart, Galco and Conduit Fill Calculator dot com.
  • Fill limits of 53, 31 and 40 percent from NEC Chapter 9 Table 1 as described by Expert CE and NEC Mastery. The 60 percent nipple allowance is Chapter 9 Note 4 as described there.
  • Third party reproductions of NEC tables were used. Verify against the NFPA 70 edition your inspector enforces before you pull wire.