Padmount Supply

Home / Tools / Watts to amps calculator

Watts to amps calculator

Amps equal watts divided by volts for DC, watts divided by volts times power factor for single phase, and watts divided by 1.732 times volts times power factor for three phase. Pick the circuit, enter watts and volts, and read amps. It works the other way too.

Updated November 18, 2026

Current6.682 A
Power7,482.5 W

DC is watts divided by volts. Single phase AC divides by volts times power factor. Three phase AC divides by 1.732 times line to line volts times power factor.

The three formulas

CircuitAmps from wattsWatts from amps
DCI = P / VP = I x V
Single phase ACI = P / (V x PF)P = I x V x PF
Three phase ACI = P / (1.732 x V x PF)P = 1.732 x I x V x PF

Worked example, 5 kW at 480 V three phase

A 5,000 W load at 480 V three phase and a power factor of 0.9. The divisor is 1.732 x 480 x 0.9, which is 748.2. 5,000 divided by 748.2 is 6.68 A per line. The same load at power factor 1 draws 6.01 A, so a poor power factor costs 11 percent more current here.

Watts to amps table, single phase

Watts120 V, PF 1240 V, PF 1120 V, PF 0.9240 V, PF 0.9
1000.830.420.930.46
5004.172.084.632.31
1,0008.334.179.264.63
2,00016.678.3318.529.26
5,00041.6720.8346.3023.15
10,00083.3341.6792.5946.30
25,000208.33104.17231.48115.74
50,000416.67208.33462.96231.48
100,000833.33416.67925.93462.96

Watts to amps table, three phase, power factor 0.9

Watts208 V240 V480 V600 V
1000.310.270.130.11
5001.541.340.670.53
1,0003.082.671.341.07
2,0006.175.352.672.14
5,00015.4213.366.685.35
10,00030.8426.7313.3610.69
25,00077.1066.8233.4126.73
50,000154.21133.6566.8253.46
100,000308.41267.29133.65106.92

From amps to a transformer

Current is what a transformer is sized for. Divide watts by power factor to get VA, then read the standard rating and its full load current in the kVA to amps calculator. Going the other way, the kW to amps calculator and the kVA to kW calculator show the power factor link, and the transformer sizing calculator picks the rating. For wire, see the AWG wire gauge chart and the voltage drop calculator. For line to neutral voltages use the line to neutral voltage calculator.

Sizing power for a site, request a quote with your load and voltage, or see pad mounted transformers for sale.

Put this calculator on your site

Free for contractors, electricians, schools and trade sites. Paste this code into any page.

Common questions

How do you convert watts to amps

Divide watts by volts for DC. For single phase AC divide watts by volts times power factor. For three phase AC divide watts by 1.732 times line to line volts times power factor. 1,000 W at 120 V DC is 8.33 A.

How many amps is 1000 watts

At 120 V it is 8.33 A for DC or a resistive load, 9.26 A at a power factor of 0.9. At 240 V it is 4.17 A. At 480 V three phase and a power factor of 0.9 it is 1.34 A per line.

How many amps is 5000 watts

At 240 V single phase and a power factor of 1 it is 20.83 A. At 480 V three phase and a power factor of 0.9 it is 6.68 A per line. At 208 V three phase and 0.9 it is 15.42 A.

Why does power factor matter

Resistive loads such as heaters have a power factor near 1. Motors and other inductive loads run at lower values, commonly quoted as 0.7 to 0.95, so the same watts draw more current. The current is what sizes wire, breakers and transformers.

What voltage do I use for three phase

Use the line to line voltage, 208, 240 or 480 V. Line to neutral voltage such as 120 or 277 V gives the wrong answer with the 1.732 formula. The line to neutral voltage calculator converts between them.

How do I size a transformer from watts

Divide watts by power factor to get VA, then pick the next standard kVA rating. The kVA to amps calculator shows the full load current of the rating you pick on both sides of the transformer.

Sources

  • DC, single phase AC and three phase AC watts to amps formulas, with the 1.732 line to line factor, as given by Inch Calculator, elec.training and wireresult.com.
  • Typical power factor of 1 for resistive loads and about 0.7 to 0.95 for motors, as stated by the same references.
  • Every table value and the worked examples on this page are computed here from those formulas.
CallGet a quote