Home / Charts / AWG wire gauge chart with diameter, mm2, kcmil and resistance

AWG wire gauge chart with diameter, mm2, kcmil and resistance

AWG is the American wire gauge. A smaller gauge number means a thicker wire, and every 6 gauge steps roughly doubles the diameter. The chart runs from 4/0 to 40 AWG with diameter, area and copper resistance, then a second table converts kcmil sizes from 250 to 2000 into mm2, the sizes used on transformer secondaries and feeders.

Updated November 18, 2026

AWG chart, 4/0 to 40 AWG

Values are computed from the AWG definition for solid round wire. Resistance is for annealed copper at 20 degrees C, using a resistivity of 1.724 x 10 to the minus 8 ohm meter. Other sources use slightly different resistivity, so published resistance values can differ by a few percent. Stranded conductors have a larger overall diameter than the solid equivalent and a little more resistance.

GaugeDiameter inchesDiameter mmArea mm2Area kcmilOhms per 1000 ft
4/0 (0000) AWG0.460011.684107.219211.6000.049
3/0 (000) AWG0.409610.40585.029167.8060.062
2/0 (00) AWG0.36489.26667.431133.0770.078
1/0 (0) AWG0.32498.25153.475105.5350.098
1 AWG0.28937.34842.40883.6930.124
2 AWG0.25766.54433.63166.3710.156
3 AWG0.22945.82726.67052.6350.197
4 AWG0.20435.18921.15141.7410.248
5 AWG0.18194.62116.77333.1020.313
6 AWG0.16204.11513.30226.2510.395
7 AWG0.14433.66510.54920.8180.498
8 AWG0.12853.2648.36616.5100.628
9 AWG0.11442.9066.63413.0930.792
10 AWG0.10192.5885.26110.3830.999
11 AWG0.09072.3054.1728.2341.259
12 AWG0.08082.0533.3096.5301.588
13 AWG0.07201.8282.6245.1782.003
14 AWG0.06411.6282.0814.1072.525
15 AWG0.05711.4501.6503.2573.184
16 AWG0.05081.2911.3092.5834.015
17 AWG0.04531.1501.0382.0485.063
18 AWG0.04031.0240.8231.6246.385
19 AWG0.03590.9120.6531.2888.051
20 AWG0.03200.8120.5181.02210.152
21 AWG0.02850.7230.4100.81012.801
22 AWG0.02530.6440.3260.64216.142
23 AWG0.02260.5730.2580.50920.355
24 AWG0.02010.5110.2050.40425.667
25 AWG0.01790.4550.1620.32032.365
26 AWG0.01590.4050.1290.25440.812
27 AWG0.01420.3610.1020.20251.463
28 AWG0.01260.3210.0810.16064.893
29 AWG0.01130.2860.0640.12781.829
30 AWG0.01000.2550.0510.101103.184
31 AWG0.00890.2270.0400.0797130.113
32 AWG0.00800.2020.0320.0632164.069
33 AWG0.00710.1800.0250.0501206.887
34 AWG0.00630.1600.0200.0398260.880
35 AWG0.00560.1430.0160.0315328.964
36 AWG0.00500.1270.0130.0250414.815
37 AWG0.00450.1130.0100.0198523.073
38 AWG0.00400.1010.00800.0157659.582
39 AWG0.00350.0900.00630.0125831.718
40 AWG0.00310.0800.00500.00991049

Area in kcmil is the diameter in mils squared, divided by 1,000. One kcmil is 0.5067 mm2.

How AWG is defined

The diameter of gauge n in inches is 0.005 times 92 raised to the power of (36 minus n) divided by 39. Gauge 36 is exactly 0.005 inch and gauge 0000 is exactly 0.46 inch, a ratio of 92. Each gauge step changes the diameter by about 12 percent, 3 gauges halve or double the area and 6 gauges halve or double the diameter. The sizes 1/0, 2/0, 3/0 and 4/0 are also written 0, 00, 000 and 0000, and count as gauge numbers 0 to minus 3.

kcmil to mm2, 250 to 2000 kcmil

Above 4/0 AWG, conductors are sold by area in kcmil, thousands of circular mils, which is how the large feeders on a transformer are specified. Convert with mm2 equals kcmil times 0.5067. The equivalent solid diameter is the square root of the circular mils.

SizeArea mm2Equivalent solid diameter inchesEquivalent solid diameter mmCopper ohms per 1000 ft
250 kcmil126.70.50012.700.0415
300 kcmil152.00.54813.910.0346
350 kcmil177.30.59215.030.0296
400 kcmil202.70.63216.060.0259
500 kcmil253.40.70717.960.0207
600 kcmil304.00.77519.670.0173
700 kcmil354.70.83721.250.0148
750 kcmil380.00.86622.000.0138
800 kcmil405.40.89422.720.0130
900 kcmil456.00.94924.100.0115
1000 kcmil506.71.00025.400.0104
1250 kcmil633.41.11828.400.0083
1500 kcmil760.11.22531.110.0069
1750 kcmil886.71.32333.600.0059
2000 kcmil1013.41.41435.920.0052

Real conductors above 4/0 are stranded and their overall diameter is larger than the equivalent solid value shown.

Common sizes at a glance

The sizes most often asked about, for quick reference.

GaugeDiameter mmArea mm2Ohms per 1000 ft
4/0 (0000) AWG11.684107.2190.049
1/0 (0) AWG8.25153.4750.098
1 AWG7.34842.4080.124
2 AWG6.54433.6310.156
4 AWG5.18921.1510.248
6 AWG4.11513.3020.395
8 AWG3.2648.3660.628
10 AWG2.5885.2610.999
12 AWG2.0533.3091.588
14 AWG1.6282.0812.525

From gauge to current and transformer feeders

Gauge sets resistance and voltage drop, but the current a conductor may carry comes from the NEC ampacity table, which depends on insulation temperature rating and conductor material. See the wire ampacity chart for NEC Table 310.16, the wire size by amps chart for a size from a load, the voltage drop calculator for long runs and the conduit fill calculator for the raceway.

For transformers, secondary conductors from a padmount are usually 250 kcmil to 750 kcmil in parallel sets, so the kcmil table above is the one to use. Full load amps for any kVA and voltage are on the kVA to amps calculator.

Common questions

What does AWG mean

AWG stands for American wire gauge, a standard for the diameter of round, solid, nonferrous conductors. A smaller number means a thicker wire.

What is the diameter of 12 AWG wire

12 AWG solid wire is 0.0808 inch or 2.053 mm across and has an area of 3.309 mm2.

How do you convert AWG to mm2

Find the diameter with d in mm equals 0.127 times 92 to the power of (36 minus n) over 39, then area equals pi over 4 times d squared. The chart above lists the result for every gauge. 10 AWG is 5.26 mm2 and 4 AWG is 21.2 mm2.

What is kcmil

A kcmil is one thousand circular mils, a unit of area for conductors larger than 4/0 AWG. It is also written MCM. 1 kcmil is 0.5067 mm2, so 500 kcmil is 253.4 mm2.

What is the size after 4/0 AWG

250 kcmil is the next standard size above 4/0 AWG, which itself is 211.6 kcmil.

Does the gauge number tell me how much current a wire carries

No. Gauge sets the size only. Ampacity depends on the insulation temperature rating, the number of conductors in a raceway, ambient temperature and the terminals. Use NEC Table 310.16 and the wire ampacity chart.

Related pages

Sources

Free to cite with a link to this page. Always check the edition of the code your inspector enforces.

More charts

Wire ampacity chart from NEC Table 310.16
NEC Table 310.16 ampacities for copper and aluminum at 60, 75 and 90°C from 14 AWG to 2000 kcmil, with the terminal rule, small conductor limits and derating factors.
NEMA enclosure ratings chart
What NEMA Types 1, 3R, 4, 4X, 12 and the rest protect against, side by side, with the IP codes three published charts give for each and why they disagree.
Motor full load amps chart
Three phase motor full load amps from 1/2 to 500 HP at 115, 200, 208, 230, 460, 575 and 2300 V from NEC Table 430.250, single phase from 430.248, with wire, breaker and kVA by HP.
What size wire for every amp rating, 15 to 4000 amps
Wire size by amps from 15 to 400 A in copper and aluminum, the dwelling service sizes under NEC 310.12, and parallel sets for 400 to 4000 A services, with a calculator.
Primary distribution voltages, 4.16 kV to 34.5 kV
Every standard US primary voltage from 2.4 kV to 69 kV with its phase to ground value, wye or delta, insulation class and BIL, and what 12470Y/7200 on a nameplate means.
Commercial electrical service sizes, amps, kVA and transformer
Standard commercial service sizes from 100 to 4000 amps at 208Y/120 and 480Y/277 volts, the kVA each one carries, the transformer that feeds it, and when ground fault protection applies.
Breaker size chart, every standard breaker rating and its wire size
Every standard breaker size in NEC 240.6(A) from 10 to 6000 amps, the matching copper and aluminum wire size at 60 and 75°C, the 125 percent continuous load rule and common appliance circuits.
Transformer fuse size chart, primary full load amps by kVA and voltage
Primary full load amps for 25 to 2500 kVA three phase transformers at 4.16 to 34.5 kV, the NEC 450.3(B) 125 and 250 percent limits worked out at 480 V, and how pad mount fuses are chosen.
Copper bus bar ampacity chart, by bar size and temperature rise
Ampacity of 68 standard rectangular copper bus bar sizes from 1/16 by 1/2 inch to 3/4 by 12 inch at 30, 50 and 65 C rise, with area, weight and how to pick a bar for a transformer secondary.
Electrical service size chart, how many kW is a 200 amp service
kVA and kW for 60 to 1200 amp electrical services on single phase 240 volt and three phase 208, 240 and 480 volt systems, with 80 percent loading columns and the formula behind every figure.
Grounding electrode conductor size chart from NEC Table 250.66
NEC Table 250.66 grounding electrode conductor sizes in copper and aluminum, the 6 AWG rod rule and 4 AWG concrete encased rule, and the ground wire size for 100, 200, 400, 600, 800 and 1200 amp services.
How many acres does 1 MW of solar need
A utility scale solar farm needs about 5 to 10 acres per MWac. Fixed tilt averages 7.6 acres and single axis tracking 8.7 acres, with a table from 1 to 500 MW, panel counts and step up transformers.
Generator kVA to kW and amps chart
Generator kVA to kW and full load amps for 10 to 3,000 kVA at 120/240, 208, 240, 480, 600, 2,400 and 4,160 volts, computed at 0.8 power factor, with kW to kVA at other power factors.
Service wire size chart
Service entrance wire size for 100, 125, 150, 200, 225, 320, 400 and larger services in copper and aluminum, with the NEC 310.12 dwelling rule, parallel sets to 2000 amps, ground wire and the transformer behind the service.
NEMA plug and receptacle chart
NEMA plug chart for every straight blade and locking configuration, with voltage, poles, wires, amp ratings, the 80 percent continuous limit, how to read a name like 14-50R and L6-30P and which series fits 120, 208, 240 and 480 volts.
CallGet a quote