Home / Charts / AWG wire gauge chart with diameter, mm2, kcmil and resistance
AWG wire gauge chart with diameter, mm2, kcmil and resistance
AWG is the American wire gauge. A smaller gauge number means a thicker wire, and every 6 gauge steps roughly doubles the diameter. The chart runs from 4/0 to 40 AWG with diameter, area and copper resistance, then a second table converts kcmil sizes from 250 to 2000 into mm2, the sizes used on transformer secondaries and feeders.
Updated November 18, 2026
AWG chart, 4/0 to 40 AWG
Values are computed from the AWG definition for solid round wire. Resistance is for annealed copper at 20 degrees C, using a resistivity of 1.724 x 10 to the minus 8 ohm meter. Other sources use slightly different resistivity, so published resistance values can differ by a few percent. Stranded conductors have a larger overall diameter than the solid equivalent and a little more resistance.
| Gauge | Diameter inches | Diameter mm | Area mm2 | Area kcmil | Ohms per 1000 ft |
|---|---|---|---|---|---|
| 4/0 (0000) AWG | 0.4600 | 11.684 | 107.219 | 211.600 | 0.049 |
| 3/0 (000) AWG | 0.4096 | 10.405 | 85.029 | 167.806 | 0.062 |
| 2/0 (00) AWG | 0.3648 | 9.266 | 67.431 | 133.077 | 0.078 |
| 1/0 (0) AWG | 0.3249 | 8.251 | 53.475 | 105.535 | 0.098 |
| 1 AWG | 0.2893 | 7.348 | 42.408 | 83.693 | 0.124 |
| 2 AWG | 0.2576 | 6.544 | 33.631 | 66.371 | 0.156 |
| 3 AWG | 0.2294 | 5.827 | 26.670 | 52.635 | 0.197 |
| 4 AWG | 0.2043 | 5.189 | 21.151 | 41.741 | 0.248 |
| 5 AWG | 0.1819 | 4.621 | 16.773 | 33.102 | 0.313 |
| 6 AWG | 0.1620 | 4.115 | 13.302 | 26.251 | 0.395 |
| 7 AWG | 0.1443 | 3.665 | 10.549 | 20.818 | 0.498 |
| 8 AWG | 0.1285 | 3.264 | 8.366 | 16.510 | 0.628 |
| 9 AWG | 0.1144 | 2.906 | 6.634 | 13.093 | 0.792 |
| 10 AWG | 0.1019 | 2.588 | 5.261 | 10.383 | 0.999 |
| 11 AWG | 0.0907 | 2.305 | 4.172 | 8.234 | 1.259 |
| 12 AWG | 0.0808 | 2.053 | 3.309 | 6.530 | 1.588 |
| 13 AWG | 0.0720 | 1.828 | 2.624 | 5.178 | 2.003 |
| 14 AWG | 0.0641 | 1.628 | 2.081 | 4.107 | 2.525 |
| 15 AWG | 0.0571 | 1.450 | 1.650 | 3.257 | 3.184 |
| 16 AWG | 0.0508 | 1.291 | 1.309 | 2.583 | 4.015 |
| 17 AWG | 0.0453 | 1.150 | 1.038 | 2.048 | 5.063 |
| 18 AWG | 0.0403 | 1.024 | 0.823 | 1.624 | 6.385 |
| 19 AWG | 0.0359 | 0.912 | 0.653 | 1.288 | 8.051 |
| 20 AWG | 0.0320 | 0.812 | 0.518 | 1.022 | 10.152 |
| 21 AWG | 0.0285 | 0.723 | 0.410 | 0.810 | 12.801 |
| 22 AWG | 0.0253 | 0.644 | 0.326 | 0.642 | 16.142 |
| 23 AWG | 0.0226 | 0.573 | 0.258 | 0.509 | 20.355 |
| 24 AWG | 0.0201 | 0.511 | 0.205 | 0.404 | 25.667 |
| 25 AWG | 0.0179 | 0.455 | 0.162 | 0.320 | 32.365 |
| 26 AWG | 0.0159 | 0.405 | 0.129 | 0.254 | 40.812 |
| 27 AWG | 0.0142 | 0.361 | 0.102 | 0.202 | 51.463 |
| 28 AWG | 0.0126 | 0.321 | 0.081 | 0.160 | 64.893 |
| 29 AWG | 0.0113 | 0.286 | 0.064 | 0.127 | 81.829 |
| 30 AWG | 0.0100 | 0.255 | 0.051 | 0.101 | 103.184 |
| 31 AWG | 0.0089 | 0.227 | 0.040 | 0.0797 | 130.113 |
| 32 AWG | 0.0080 | 0.202 | 0.032 | 0.0632 | 164.069 |
| 33 AWG | 0.0071 | 0.180 | 0.025 | 0.0501 | 206.887 |
| 34 AWG | 0.0063 | 0.160 | 0.020 | 0.0398 | 260.880 |
| 35 AWG | 0.0056 | 0.143 | 0.016 | 0.0315 | 328.964 |
| 36 AWG | 0.0050 | 0.127 | 0.013 | 0.0250 | 414.815 |
| 37 AWG | 0.0045 | 0.113 | 0.010 | 0.0198 | 523.073 |
| 38 AWG | 0.0040 | 0.101 | 0.0080 | 0.0157 | 659.582 |
| 39 AWG | 0.0035 | 0.090 | 0.0063 | 0.0125 | 831.718 |
| 40 AWG | 0.0031 | 0.080 | 0.0050 | 0.0099 | 1049 |
Area in kcmil is the diameter in mils squared, divided by 1,000. One kcmil is 0.5067 mm2.
How AWG is defined
The diameter of gauge n in inches is 0.005 times 92 raised to the power of (36 minus n) divided by 39. Gauge 36 is exactly 0.005 inch and gauge 0000 is exactly 0.46 inch, a ratio of 92. Each gauge step changes the diameter by about 12 percent, 3 gauges halve or double the area and 6 gauges halve or double the diameter. The sizes 1/0, 2/0, 3/0 and 4/0 are also written 0, 00, 000 and 0000, and count as gauge numbers 0 to minus 3.
kcmil to mm2, 250 to 2000 kcmil
Above 4/0 AWG, conductors are sold by area in kcmil, thousands of circular mils, which is how the large feeders on a transformer are specified. Convert with mm2 equals kcmil times 0.5067. The equivalent solid diameter is the square root of the circular mils.
| Size | Area mm2 | Equivalent solid diameter inches | Equivalent solid diameter mm | Copper ohms per 1000 ft |
|---|---|---|---|---|
| 250 kcmil | 126.7 | 0.500 | 12.70 | 0.0415 |
| 300 kcmil | 152.0 | 0.548 | 13.91 | 0.0346 |
| 350 kcmil | 177.3 | 0.592 | 15.03 | 0.0296 |
| 400 kcmil | 202.7 | 0.632 | 16.06 | 0.0259 |
| 500 kcmil | 253.4 | 0.707 | 17.96 | 0.0207 |
| 600 kcmil | 304.0 | 0.775 | 19.67 | 0.0173 |
| 700 kcmil | 354.7 | 0.837 | 21.25 | 0.0148 |
| 750 kcmil | 380.0 | 0.866 | 22.00 | 0.0138 |
| 800 kcmil | 405.4 | 0.894 | 22.72 | 0.0130 |
| 900 kcmil | 456.0 | 0.949 | 24.10 | 0.0115 |
| 1000 kcmil | 506.7 | 1.000 | 25.40 | 0.0104 |
| 1250 kcmil | 633.4 | 1.118 | 28.40 | 0.0083 |
| 1500 kcmil | 760.1 | 1.225 | 31.11 | 0.0069 |
| 1750 kcmil | 886.7 | 1.323 | 33.60 | 0.0059 |
| 2000 kcmil | 1013.4 | 1.414 | 35.92 | 0.0052 |
Real conductors above 4/0 are stranded and their overall diameter is larger than the equivalent solid value shown.
Common sizes at a glance
The sizes most often asked about, for quick reference.
| Gauge | Diameter mm | Area mm2 | Ohms per 1000 ft |
|---|---|---|---|
| 4/0 (0000) AWG | 11.684 | 107.219 | 0.049 |
| 1/0 (0) AWG | 8.251 | 53.475 | 0.098 |
| 1 AWG | 7.348 | 42.408 | 0.124 |
| 2 AWG | 6.544 | 33.631 | 0.156 |
| 4 AWG | 5.189 | 21.151 | 0.248 |
| 6 AWG | 4.115 | 13.302 | 0.395 |
| 8 AWG | 3.264 | 8.366 | 0.628 |
| 10 AWG | 2.588 | 5.261 | 0.999 |
| 12 AWG | 2.053 | 3.309 | 1.588 |
| 14 AWG | 1.628 | 2.081 | 2.525 |
From gauge to current and transformer feeders
Gauge sets resistance and voltage drop, but the current a conductor may carry comes from the NEC ampacity table, which depends on insulation temperature rating and conductor material. See the wire ampacity chart for NEC Table 310.16, the wire size by amps chart for a size from a load, the voltage drop calculator for long runs and the conduit fill calculator for the raceway.
For transformers, secondary conductors from a padmount are usually 250 kcmil to 750 kcmil in parallel sets, so the kcmil table above is the one to use. Full load amps for any kVA and voltage are on the kVA to amps calculator.
Common questions
What does AWG mean
AWG stands for American wire gauge, a standard for the diameter of round, solid, nonferrous conductors. A smaller number means a thicker wire.
What is the diameter of 12 AWG wire
12 AWG solid wire is 0.0808 inch or 2.053 mm across and has an area of 3.309 mm2.
How do you convert AWG to mm2
Find the diameter with d in mm equals 0.127 times 92 to the power of (36 minus n) over 39, then area equals pi over 4 times d squared. The chart above lists the result for every gauge. 10 AWG is 5.26 mm2 and 4 AWG is 21.2 mm2.
What is kcmil
A kcmil is one thousand circular mils, a unit of area for conductors larger than 4/0 AWG. It is also written MCM. 1 kcmil is 0.5067 mm2, so 500 kcmil is 253.4 mm2.
What is the size after 4/0 AWG
250 kcmil is the next standard size above 4/0 AWG, which itself is 211.6 kcmil.
Does the gauge number tell me how much current a wire carries
No. Gauge sets the size only. Ampacity depends on the insulation temperature rating, the number of conductors in a raceway, ambient temperature and the terminals. Use NEC Table 310.16 and the wire ampacity chart.
Related pages
Sources
- Wikipedia, American wire gauge, the diameter formula and gauge definitions
- University of California Santa Barbara AWG handout, copper resistance derivation
- Engineering Toolbox, AWG wire gauge and circular mils
- Omni Calculator, wire gauge area formula
Free to cite with a link to this page. Always check the edition of the code your inspector enforces.