K method at 75 C, K 12.9 for copper and 21.2 for aluminum. It uses resistance only, so it understates drop on large conductors and low power factor loads. Length is one way.
Formula
- Single phase or DC drop equals 2 x K x I x L / CM.
- Three phase drop equals 1.732 x K x I x L / CM.
- K is 12.9 for copper and 21.2 for aluminum, I is amps, L is one way feet and CM is circular mils.
- Percent drop is the drop divided by the supply voltage, times 100.
Example. 40 A at 240 V single phase over 150 ft of 8 AWG copper (16,510 CM) drops 2 x 12.9 x 40 x 150 / 16,510 = 9.4 V, or 3.9 percent, which is over 3 percent, so go to 6 AWG.
Maximum run for a 3 percent drop, copper
| Wire | 120 V single phase, 20 A | 240 V single phase, 40 A | 208 V three phase, 50 A | 480 V three phase, 100 A |
|---|---|---|---|---|
| 14 AWG | 29 ft | 29 ft | 23 ft | 26 ft |
| 12 AWG | 46 ft | 46 ft | 36 ft | 42 ft |
| 10 AWG | 72 ft | 72 ft | 58 ft | 67 ft |
| 8 AWG | 115 ft | 115 ft | 92 ft | 106 ft |
| 6 AWG | 183 ft | 183 ft | 147 ft | 169 ft |
| 4 AWG | 291 ft | 291 ft | 233 ft | 269 ft |
| 2 AWG | 463 ft | 463 ft | 371 ft | 428 ft |
| 1/0 AWG | 737 ft | 737 ft | 590 ft | 681 ft |
| 2/0 AWG | 929 ft | 929 ft | 743 ft | 858 ft |
| 4/0 AWG | 1,476 ft | 1,476 ft | 1,182 ft | 1,364 ft |
| 250 kcmil | 1,744 ft | 1,744 ft | 1,396 ft | 1,611 ft |
| 500 kcmil | 3,488 ft | 3,488 ft | 2,793 ft | 3,222 ft |
Free to cite with a link to this page. One way feet at 3 percent, K 12.9, computed. Check ampacity separately on the wire ampacity chart or the wire size charts.
Maximum run for a 3 percent drop, aluminum
| Wire | 120 V single phase, 20 A | 240 V single phase, 40 A | 208 V three phase, 50 A | 480 V three phase, 100 A |
|---|---|---|---|---|
| 8 AWG | 70 ft | 70 ft | 56 ft | 65 ft |
| 6 AWG | 111 ft | 111 ft | 89 ft | 103 ft |
| 4 AWG | 177 ft | 177 ft | 142 ft | 164 ft |
| 2 AWG | 282 ft | 282 ft | 226 ft | 260 ft |
| 1/0 AWG | 448 ft | 448 ft | 359 ft | 414 ft |
| 2/0 AWG | 565 ft | 565 ft | 452 ft | 522 ft |
| 4/0 AWG | 898 ft | 898 ft | 719 ft | 830 ft |
| 250 kcmil | 1,061 ft | 1,061 ft | 850 ft | 980 ft |
| 500 kcmil | 2,123 ft | 2,123 ft | 1,699 ft | 1,961 ft |
One way feet at 3 percent, K 21.2, computed.
From the transformer to the building
The run from a pad mounted transformer to the service is a feeder like any other, and the secondary is where most of the drop happens because current is high. Keep the transformer close to the service, size the secondary wire for drop and not just ampacity, and ask for taps if the primary voltage runs low. See transformer taps explained and the pad mounted transformer installation guide. Get the full load amps from the kVA to amps calculator, and see the glossary for terms. When you need a unit, request a quote.
Once the wire is chosen, check the raceway with the conduit fill calculator.
Common questions
How do you calculate voltage drop
Single phase is 2 x K x I x L / CM, and three phase replaces the 2 with 1.732. K is 12.9 for copper and 21.2 for aluminum at 75 C, I is amps, L is the one way length in feet and CM is the wire circular mils.
What voltage drop is acceptable
The NEC informational notes suggest no more than 3 percent on a branch circuit or feeder and 5 percent overall. These are recommendations, not mandatory limits, in most cases. Check the code sections and the equipment maker for any place where a drop limit is required.
Is the length one way or round trip
Use one way length. The 2 in the single phase formula already counts the return conductor.
How do I reduce voltage drop
Use a larger wire, shorten the run, raise the voltage, or move the transformer closer to the load. A transformer with taps can also lift the secondary voltage a few percent to offset steady drop, see the transformer taps page.
Does aluminum drop more than copper
Yes. The K value for aluminum is 21.2 against 12.9 for copper, about 64 percent more drop for the same size wire.
Is the K method exact
No. It uses resistance only. On large conductors or low power factor loads reactance matters, and the NEC Chapter 9 Table 9 impedance method is closer.
Sources
- The K method, drop equals 2 x K x I x L / CM for single phase and 1.732 x K x I x L / CM for three phase with K of 12.9 for copper and 21.2 for aluminum at 75 C, is described by IAEI Magazine, EC&M and Mike Holt.
- Circular mil areas are the standard wire sizes from NEC Chapter 9 Table 8.
- The 3 percent and 5 percent figures are NEC informational notes to 210.19(A) and 215.2(A), recommendations rather than mandatory limits.
- Every distance in the tables is computed from the formula.