Voltage drop calculator

Enter the voltage, current, wire size and one way length to get the voltage drop, the voltage at the load, and the longest run that stays under your limit. Three percent is the usual target.

Updated November 18, 2026

Voltage drop9.38 V
Percent of supply3.91 percent
Voltage at the load230.6 V
Longest run at 3 percent115 ft
Smallest wire for this run and limit1 AWG

K method at 75 C, K 12.9 for copper and 21.2 for aluminum. It uses resistance only, so it understates drop on large conductors and low power factor loads. Length is one way.

Formula

  • Single phase or DC drop equals 2 x K x I x L / CM.
  • Three phase drop equals 1.732 x K x I x L / CM.
  • K is 12.9 for copper and 21.2 for aluminum, I is amps, L is one way feet and CM is circular mils.
  • Percent drop is the drop divided by the supply voltage, times 100.

Example. 40 A at 240 V single phase over 150 ft of 8 AWG copper (16,510 CM) drops 2 x 12.9 x 40 x 150 / 16,510 = 9.4 V, or 3.9 percent, which is over 3 percent, so go to 6 AWG.

Maximum run for a 3 percent drop, copper

Wire120 V single phase, 20 A240 V single phase, 40 A208 V three phase, 50 A480 V three phase, 100 A
14 AWG29 ft29 ft23 ft26 ft
12 AWG46 ft46 ft36 ft42 ft
10 AWG72 ft72 ft58 ft67 ft
8 AWG115 ft115 ft92 ft106 ft
6 AWG183 ft183 ft147 ft169 ft
4 AWG291 ft291 ft233 ft269 ft
2 AWG463 ft463 ft371 ft428 ft
1/0 AWG737 ft737 ft590 ft681 ft
2/0 AWG929 ft929 ft743 ft858 ft
4/0 AWG1,476 ft1,476 ft1,182 ft1,364 ft
250 kcmil1,744 ft1,744 ft1,396 ft1,611 ft
500 kcmil3,488 ft3,488 ft2,793 ft3,222 ft

Free to cite with a link to this page. One way feet at 3 percent, K 12.9, computed. Check ampacity separately on the wire ampacity chart or the wire size charts.

Maximum run for a 3 percent drop, aluminum

Wire120 V single phase, 20 A240 V single phase, 40 A208 V three phase, 50 A480 V three phase, 100 A
8 AWG70 ft70 ft56 ft65 ft
6 AWG111 ft111 ft89 ft103 ft
4 AWG177 ft177 ft142 ft164 ft
2 AWG282 ft282 ft226 ft260 ft
1/0 AWG448 ft448 ft359 ft414 ft
2/0 AWG565 ft565 ft452 ft522 ft
4/0 AWG898 ft898 ft719 ft830 ft
250 kcmil1,061 ft1,061 ft850 ft980 ft
500 kcmil2,123 ft2,123 ft1,699 ft1,961 ft

One way feet at 3 percent, K 21.2, computed.

From the transformer to the building

The run from a pad mounted transformer to the service is a feeder like any other, and the secondary is where most of the drop happens because current is high. Keep the transformer close to the service, size the secondary wire for drop and not just ampacity, and ask for taps if the primary voltage runs low. See transformer taps explained and the pad mounted transformer installation guide. Get the full load amps from the kVA to amps calculator, and see the glossary for terms. When you need a unit, request a quote.

Once the wire is chosen, check the raceway with the conduit fill calculator.

Put this calculator on your site

Free for contractors, electricians, schools and trade sites. Paste this code into any page.

Common questions

How do you calculate voltage drop

Single phase is 2 x K x I x L / CM, and three phase replaces the 2 with 1.732. K is 12.9 for copper and 21.2 for aluminum at 75 C, I is amps, L is the one way length in feet and CM is the wire circular mils.

What voltage drop is acceptable

The NEC informational notes suggest no more than 3 percent on a branch circuit or feeder and 5 percent overall. These are recommendations, not mandatory limits, in most cases. Check the code sections and the equipment maker for any place where a drop limit is required.

Is the length one way or round trip

Use one way length. The 2 in the single phase formula already counts the return conductor.

How do I reduce voltage drop

Use a larger wire, shorten the run, raise the voltage, or move the transformer closer to the load. A transformer with taps can also lift the secondary voltage a few percent to offset steady drop, see the transformer taps page.

Does aluminum drop more than copper

Yes. The K value for aluminum is 21.2 against 12.9 for copper, about 64 percent more drop for the same size wire.

Is the K method exact

No. It uses resistance only. On large conductors or low power factor loads reactance matters, and the NEC Chapter 9 Table 9 impedance method is closer.

Sources

  • The K method, drop equals 2 x K x I x L / CM for single phase and 1.732 x K x I x L / CM for three phase with K of 12.9 for copper and 21.2 for aluminum at 75 C, is described by IAEI Magazine, EC&M and Mike Holt.
  • Circular mil areas are the standard wire sizes from NEC Chapter 9 Table 8.
  • The 3 percent and 5 percent figures are NEC informational notes to 210.19(A) and 215.2(A), recommendations rather than mandatory limits.
  • Every distance in the tables is computed from the formula.