What Is a VFD, How a Variable Frequency Drive Works and How to Size One

A VFD, or variable frequency drive, controls the speed of an AC motor by changing the frequency and voltage that reach it. Inside it, a rectifier turns incoming AC into DC, a capacitor bank smooths that DC, and an inverter builds a new AC output at whatever frequency is needed. It is also called a variable speed drive, or VSD. For a fan or pump, running slower saves energy, which is the main reason VFDs are installed.

Updated November 16, 2026

How a VFD works in three stages

The rectifier is built from diodes or thyristors and converts three phase AC into pulsating DC. The DC bus, also called the DC link, is a bank of capacitors that smooths that DC into a steady rail and absorbs energy when a motor slows down. The inverter uses IGBT transistors to chop the DC into high frequency pulses. Varying the width of each pulse, known as pulse width modulation or PWM, builds an output that approximates a sine wave at any frequency from near zero up to the drive maximum. The motor sees an approximation of a sine wave, not a true one.

Volts per hertz control

The simplest control mode keeps the ratio of output voltage to frequency constant. Holding that ratio keeps the magnetic flux in the motor steady, which lets it make torque across the speed range. It needs no speed feedback device and suits variable torque loads such as fans and pumps. Drives that need tight speed or torque control use more advanced modes, which are outside the scope of this guide.

Speed from frequency and poles

Synchronous speed in RPM equals 120 times frequency in hertz divided by the number of poles. A four pole motor on 60 Hz is a 1800 RPM motor. The table is computed from that formula. An induction motor shaft turns slightly slower than these synchronous values.

Motor poles20 Hz30 Hz40 Hz50 Hz60 Hz
2 poles1,2001,8002,4003,0003,600
4 poles6009001,2001,5001,800
6 poles4006008001,0001,200
8 poles300450600750900

Synchronous speed in RPM, 120 x frequency / poles.

Where VFDs are used

The classic uses are variable torque loads such as fans and pumps, and VFDs are widely used on HVAC equipment. Motor control centers, the line ups that hold motor starters and controls, are where drives are often installed, and our MCC buyer page covers that equipment.

Size a VFD from motor current, not horsepower

NEC 430.6(C) covers motors on adjustable voltage, variable torque drive systems. It says to use the maximum operating current marked on the motor or control nameplate to size conductors, switches and branch circuit protection. If no maximum operating current is marked, use 150 percent of the values in Tables 430.249 and 430.250. A drive is therefore chosen by the current it must deliver at the duty of the load, and the horsepower rating is only a starting point.

What a VFD does to the transformer feeding it

Rectifiers and inverters changing AC to DC and back can cause power quality issues such as voltage swells and sags, and capacitive coupling can push ground currents back upstream. A drive isolation transformer breaks that path. It has isolated windings, which make a separately derived system, and an optional electrostatic shield between the high and low voltage windings for added noise attenuation. One maker lists drive isolation units with 150 percent overload for 60 seconds and 200 percent for 30 seconds, and rates them in kVA matched to motor horsepower, for example 11 kVA for 7.5 hp and 63 kVA for 50 hp. A drive isolation transformer is not the same as a K rated unit, which is built for harmonic heating with a 200 percent neutral.

Drives and K rated transformers

K rated transformers are built for non sinusoidal loads with triplen harmonics, with a neutral rated at 200 percent and an electrostatic shield as standard. A drive isolation unit has a 100 percent neutral and is built for the overload and isolation needs of motor drive circuits. Pick on what the supply actually has to handle, and send us the drive nameplates if you are not sure which is needed.

Related pages

Common questions

What does VFD stand for

Variable frequency drive. It is also called a variable speed drive or VSD, and it controls an AC motor by changing frequency and voltage.

How does a VFD change motor speed

Motor speed follows frequency. Synchronous speed equals 120 times the frequency divided by the number of poles, so a 4 pole motor runs near 1800 RPM at 60 Hz and near 900 RPM at 30 Hz.

What are the parts of a VFD

A rectifier that converts AC to DC, a DC bus of capacitors that smooths it, and a PWM inverter that builds the variable frequency AC output.

Do I need a transformer for a VFD

Not always. A drive isolation transformer is used where ground currents or common mode noise from the drive is a problem, because it makes a separately derived system for the drive.

How do you size a VFD

Use motor nameplate current and the duty of the load. NEC 430.6(C) points to the maximum operating current marked on the nameplate, or 150 percent of the table values if none is marked.

What is volts per hertz

A control method that holds the output voltage to frequency ratio constant, which keeps motor flux steady and works well for fans and pumps.

Sources

Free to cite with a link to this page. Work out current at any rating with the kVA to amps calculator.