Fill in any two boxes and leave the others empty.
The twelve formulas
Every Ohm's law problem uses one of these. Pick the row for what you want to find and the column for the two values you know.
| To find | From V and I or I and R | From P and one other | From P and R |
|---|---|---|---|
| Voltage V | I x R | P / I | square root of (P x R) |
| Current I | V / R | P / V | square root of (P / R) |
| Resistance R | V / I | V squared / P | P / I squared |
| Power P | V x I | I squared x R | V squared / R |
Worked table, a resistive load on common voltages
| Voltage, V | Resistance, ohms | Current, A | Power, W |
|---|---|---|---|
| 12 | 2 | 6 | 72 |
| 120 | 10 | 12 | 1,440 |
| 120 | 20 | 6 | 720 |
| 208 | 8 | 26 | 5,408 |
| 240 | 30 | 8 | 1,920 |
| 277 | 12 | 23.083 | 6,394.1 |
| 480 | 25 | 19.2 | 9,216 |
Free to cite with a link to this page. Each row is computed, current is V / R and power is V squared / R.
Ohm's law in AC circuits
With coils, motors and transformers the opposition to current is impedance, Z, not just resistance. The law becomes V = I x Z. Real power in watts is then V x I x power factor for single phase, and 1.732 x V x I x power factor for three phase. The three phase power calculator and the power factor calculator do that arithmetic for you.
What a transformer does to resistance and current
An ideal transformer scales voltage by the turns ratio and current by the inverse of it, so power in equals power out. A load on the secondary appears on the primary as its impedance times the turns ratio squared. Turns ratio is the primary voltage divided by the secondary voltage.
| Primary to secondary | Turns ratio | Impedance seen from the primary |
|---|---|---|
| 480 to 208 V | 2.3077 to 1 | 5.3254 times the load impedance |
| 12,470 to 480 V | 25.979 to 1 | 674.92 times the load impedance |
| 12,470 to 208 V | 59.952 to 1 | 3,594.2 times the load impedance |
Computed from the line voltages. Per phase ratios of a delta wye bank differ by the square root of 3, see the formulas page.
For full load amps on the pad mount sizes use the kVA to amps calculator and the three phase transformer formulas. Read the step up and step down transformers guide for why current moves the opposite way to voltage. Ready to buy, request a quote.
Dividing a voltage with two resistors is covered by the voltage divider calculator.
Common questions
What is Ohm's law
Voltage equals current times resistance, V = I x R. One volt pushes one amp through one ohm.
How do you find amps from watts and volts
Divide watts by volts. A 2,400 W heater on 240 V draws 2,400 / 240 = 10 A. For three phase loads divide by 1.732 times the line voltage, and by the power factor if it is not 1.
How do you find resistance from volts and watts
Divide voltage squared by watts. A 120 V, 1,500 W heater has R = 120 x 120 / 1,500 = 9.6 ohms hot.
Does Ohm's law work for AC
Yes for resistive loads. For coils, motors and transformers, replace resistance with impedance Z, which combines resistance and reactance, and remember that real power also depends on power factor.
What is the difference between a watt and a volt amp
A watt is real power. A volt amp is apparent power, voltage times current. They are equal only at a power factor of 1, which is why transformers are rated in kVA. See the kVA to kW calculator.
What does a transformer do to resistance
A load on the secondary looks like a different impedance from the primary. The reflected value is the load impedance times the turns ratio squared.
Sources
- Every value on this page is computed from V = I x R and P = V x I, the standard Ohm's law and power relationships.
- The turns ratio relationship, reflected impedance equals load impedance times the turns ratio squared, is the standard ideal transformer result.
- The three phase factor of 1.732 is the square root of 3, as used throughout the site.