Padmount Supply

Home / Comparisons / GFCI vs AFCI Breakers and What Each One Does

GFCI vs AFCI Breakers and What Each One Does

A GFCI protects people from shock by tripping when current leaks to ground. An AFCI protects against fires by tripping when it sees the signature of an electrical arc. They detect different faults, so one does not replace the other. A dual function breaker does both in one panel slot.

Updated November 18, 2026

GFCIAFCI
What it protects againstShock from current leaking to groundFire from arcing in wiring or cords
Listed underUL 943UL 1699
What it detectsClass A units trip when current to ground exceeds 4 to 6 mA, nominally 5 mAThe waveform of an arc, not a fixed current level. Combination types see series and parallel arcs
Where the NEC covers itSection 210.8, such as bathrooms, garages, outdoors, crawl spaces, basements and near sinksSection 210.12, covering most living areas of a dwelling including bedrooms, kitchens, laundry and hallways
Breaker or outletEither a breaker or a receptacle can satisfy 210.8Generally at the breaker, with limited outlet branch circuit options

Which you actually need

Use a GFCI where the code lists wet or exposed locations and an AFCI where it lists living areas. Where a location needs both, such as kitchens and laundry areas, a dual function breaker is the practical choice because it meets 210.8 and 210.12 together in one slot. Code edition and local amendments change the exact lists, so read the NEC text for your adopted edition or ask the inspector.

Why they nuisance trip. A GFCI can trip from real leakage in a wet tool, cord or outdoor fixture. An AFCI can trip from arcing in a worn cord or loose connection, and sometimes from motor loads that look like arcs. Unplug everything on the circuit, reset and add devices back one at a time to find the cause.

Breaker compatibility. Use the breaker brand listed for your panel. Check the panel label before you buy.

This page covers branch circuit devices. Feeder and equipment ground fault protection, the kind used on larger services, is a different rule set.

Sources

Working from a specification that uses one of these terms loosely? Send it over and we will tell you which equipment it is actually calling for, before you order the wrong thing. Get a quote or call 786 220 2801.