Formula
Vout = Vin x R2 / (R1 + R2). The current is Vin / (R1 + R2). With a load RL across R2, replace R2 with R2 x RL / (R2 + RL). For two capacitors in series across an AC source, Vout = Vin x C1 / (C1 + C2) with C2 across the output.
Worked examples
| Vin | R1 ohms | R2 ohms | Vout | Current mA |
|---|---|---|---|---|
| 12 | 10,000 | 5,000 | 4.000 | 0.800 |
| 5 | 1,000 | 1,000 | 2.500 | 2.500 |
| 12 | 10,000 | 10,000 | 6.000 | 0.600 |
| 24 | 4,700 | 1,000 | 4.211 | 4.211 |
| 9 | 10,000 | 5,000 | 3.000 | 0.600 |
What a load does, 12 V in, R1 10 kilohm, R2 10 kilohm
| Load ohms | Vout | Drop from the unloaded 6 V |
|---|---|---|
| 1,000,000 | 5.970 | 0.030 |
| 100,000 | 5.714 | 0.286 |
| 20,000 | 4.800 | 1.200 |
| 10,000 | 4.000 | 2.000 |
Capacitive dividers and potential transformers
On a high voltage line a resistor divider would burn power and give no isolation, so utilities use a capacitor stack in a coupling capacitor voltage transformer, with an electromagnetic unit below it to reach the metering level. For lower voltages an ordinary potential transformer does the same job with isolation, and a current transformer handles the current side. For the formula in other forms see the Ohm's law calculator, and size wire runs with the voltage drop calculator.
Need instrument transformers or a metering package with a padmount unit, request a quote.
Common questions
What is the voltage divider formula
Vout equals Vin times R2 divided by the sum of R1 and R2. With 9 V in, 10 kilohm for R1 and 5 kilohm for R2, the output is 3 V.
How does a load change the output
A load across R2 puts a resistance in parallel with it, so the lower leg is smaller and the output drops. Use R2 in parallel with the load in the formula. A divider is only accurate if the load is much larger than R2, often ten times or more.
What is a capacitive voltage divider
Two capacitors in series split an AC voltage in inverse proportion to their capacitance. The ratio of output to input is C1 divided by the sum of C1 and C2, where C2 is the capacitor across the output. It does not pass DC and its ratio does not change with frequency.
How is a voltage divider used in a transformer system
A coupling capacitor voltage transformer uses a stack of capacitors to divide a transmission line voltage down to a few kV, then a small electromagnetic transformer steps that to the 115 V or 120 V metering and relay level. A tuning reactor compensates the phase shift.
Can a voltage divider replace a transformer
Not for power. A divider wastes power as heat, gives no isolation and its output sags with load. A potential transformer isolates the circuit and supplies a burden accurately, which is why metering uses transformers and not resistor dividers.
What resistor values should I pick
Pick values that set the ratio you want, then scale them so divider current is small compared with the load current and the power in each resistor stays within its rating. The calculator shows both.
Sources
- Resistive divider formula Vout equals Vin times R2 over R1 plus R2, Wikipedia voltage divider article and the Analog Devices circuits course page.
- Capacitive divider ratio C1 over C1 plus C2, independent of frequency and blocking DC, Wikipedia voltage divider article.
- Coupling capacitor voltage transformers combine a capacitor divider with an electromagnetic unit and a compensating reactor, Megger article on CCVTs, May 2023.
- Table values on this page are computed from the formulas. The loaded case replaces R2 with R2 in parallel with the load, a direct circuit identity.