Phase Converters Explained, Rotary, Static and Digital, and Why a Transformer Cannot Add a Phase

A phase converter makes three phase power for motors from a single phase supply. A transformer cannot do that. A transformer changes voltage and keeps the number of phases it was given, so one phase in is one phase out. Something has to build the missing legs, and there are four ways to do it, a static converter, a rotary converter, a digital converter and a variable frequency drive. This guide covers how each works, what each costs, the code rules and when it is cheaper to bring in real three phase power from the utility.

Updated November 17, 2026

What a phase converter does and does not do

Many lathes, mills, compressors and CNC machines, new and used, have three phase motors. A shop, farm or garage that only has single phase service cannot run them directly. A phase converter produces a third voltage leg so the motor sees something close to three phase. It does not change the voltage by itself, so a 240 volt converter feeding a 480 volt machine also needs a step up transformer on its output, see the 240 to 480 volt transformer page. And a transformer without a converter cannot work either, since the phases must come from somewhere. A pad mounted transformer fed by a three phase utility line gives true three phase, which is the other route and is covered at the end of this guide.

Static phase converters

A static converter is a start device. A capacitor circuit gets a three phase motor turning, then the converter drops out and the motor runs on single phase across two legs. Phase-A-Matic says the motor then develops about two thirds of its nameplate horsepower. Phoenix Phase Converters says the loss is one third to one half. A static converter runs one motor, costs the least and has no moving parts. Phase-A-Matic says it will not run old open frame motors, pumps, blowers, compressors, heating elements, most hydraulics or battery chargers, while Phoenix lists above ground pumps, bench grinders, saws, drill presses, conveyors and mixers as suitable, so the makers differ on pumps and the motor and load matter. Phoenix also warns that an oversized static converter can excite a motor so it will not start, so buy one rated for the motor.

Rotary phase converters

A rotary converter is an idler motor with a control panel and capacitors. The idler spins on single phase power and generates the third leg, and the three legs together feed a whole three phase panel with several machines. It starts hard loads, because it is sized above the motor. American Rotary rates its units to start a load of half the running rating, so a 10 HP converter starts a 5 HP motor, which is the reason makers say to double the motor horsepower. Voltage balance between legs is 0 to 5 percent for American Rotary and 3 to 5 percent for the Phoenix NL series. The idler uses power whenever the converter is on, 0.3 kW for an American Rotary 10 HP and 0.6 kW for the 20 HP, and it makes noise. NEC 455.21 requires a rotary converter to be running before any equipment on it is energized.

Digital phase converters

A digital or electronic converter builds the third leg with power electronics instead of a spinning idler. Phase Technologies states 98.7 percent efficiency, 80 watts of idle power and voltage balance within 2 percent for its Phase Perfect line, and the Phoenix DualZone line states 1 to 2 percent. That clean power is why digital units are sold for CNC machines and elevators. They cost the most per horsepower. Digital models are named by an equivalent HP that can be twice the load they carry, so a Phase Perfect named 20 carries a 10 HP load.

Variable frequency drives

A VFD rectifies the single phase input to DC and builds three phase output at any frequency. It is wired directly to one motor with no contactor in between, and it gives speed control and soft start that a converter cannot. VoltFlow reports single phase input drives stop at about 3 HP. A drive built for three phase input can run on single phase if derated to one half to one third, so a 7.5 HP motor needs a 15 to 25 HP drive, per Industrial Monitor Direct. Prices run from $190 for a 1/4 HP GS20 to $353 for a 3 to 4 HP Hitachi WJ200. See what a VFD is for how a drive works.

Price by type and size

List prices from converter makers in 2026. They exclude freight, installation and surge protection, and prices differ by maker, so treat them as ranges.

TypeSizeList priceSource
Static1/3 to 3/4 HP up to 8 to 10 HP$299.95 to $599.95Phase-A-Matic at Penn Tool, October 2026, via VoltFlow
Rotary, American Rotary5 HP$599American Rotary, October 2026, via VoltFlow
Rotary, American Rotary10 HP$1,099 to $1,199American Rotary, October 2026, via VoltFlow
Rotary, American Rotary20 HP$1,749American Rotary, October 2026, via VoltFlow
Rotary, American Rotary60 HP$5,599American Rotary, October 2026, via VoltFlow
Rotary, Phoenix NL3 HP to 100 HP$749 to $13,034Phoenix Phase Converters, 20 February 2026
Rotary, Phoenix PL heavy duty3 HP to 100 HP$849 to $14,780Phoenix Phase Converters, 20 February 2026
Digital, Phase Perfect5 load HP$1,625Phase Technologies, October 2026, via VoltFlow
Digital, Phase Perfect10 load HP$3,297Phase Technologies, October 2026, via VoltFlow
Digital, Phase Perfect20 load HP$7,047Phase Technologies, October 2026, via VoltFlow
Digital, Phoenix DualZone15 to 60 HP$5,980 to $14,400Phoenix Phase Converters, 20 February 2026
VFD, single phase in1/4 to 4 HP$190 to $353AutomationDirect and vfds.com, October 2026, via VoltFlow

Phoenix NL rotary converter price by horsepower

The standard duty NL series from Phoenix Phase Converters is the only maker here that publishes a full list, so it is a good guide to how price climbs with size. The price per horsepower falls as the unit gets larger.

RatingList price, February 2026
3 HP$749
5 HP$985
7.5 HP$1,590
10 HP$1,955
15 HP$2,543
20 HP$2,663
30 HP$4,480
40 HP$4,820
50 HP$6,785
75 HP$10,715
100 HP$13,034

How big a converter

Size from the largest motor, not the total. Phoenix says to double the largest motor horsepower and to go to 2.5 times for compressors and HVAC. Phase-A-Matic says to make a rotary converter 50 percent larger when starting current is high, five to ten times running current. The phase converter sizing calculator gives the rating, the next standard size and the single phase supply amps, and the motor full load amps chart gives the table amps for each motor size.

Code rules from NEC Article 455

Article 455 covers phase converters. For variable loads the single phase supply conductors must be at least 125 percent of the converter nameplate single phase input amps (455.6) and the overcurrent device no more than 125 percent of the same figure (455.7). The disconnect must be in sight (455.8). No single phase loads may be connected to the manufactured phase, so lights and outlets go on the two utility legs only (455.9). A rotary converter must be running before the equipment it feeds is energized (455.21). That list is a summary from VoltFlow reviewed against NEC 2023, and your jurisdiction may use another edition.

When utility three phase beats a converter

Utilities charge by the foot for a new three phase line. Green Mountain Power in Vermont charges $15.00 a foot overhead and $21.60 underground on its tariff effective 15 June 2025. Connexus Energy in Minnesota charges a $3,800 service fee with the first 200 feet included and $14.85 a foot after that, effective 1 April 2026, plus a capacity fee of 60 percent of the transformer cost. Pioneer Electric Cooperative lists $9.50 a foot overhead and $15.00 underground. Where three phase already passes the property, Connexus charges $2,120 plus $12.75 a foot for an overhead conversion and $1,500 plus $12.75 a foot underground. The transformer is billed at actual cost.

RouteCost basisSource
Three phase overhead line$15.00 per foot, $500 application feeGreen Mountain Power, June 2025
Three phase underground line$21.60 per foot at 15 kVGreen Mountain Power, June 2025
Three phase extension$3,800 service fee, then $14.85 per foot after 200 feetConnexus Energy, April 2026
Three phase overhead line$9.50 per footPioneer Electric Cooperative, October 2026
Single to three phase conversion, overhead$2,120 plus $12.75 per footConnexus Energy, April 2026
Single to three phase conversion, underground$1,500 plus $12.75 per footConnexus Energy, April 2026

A rule of thumb for the choice

VoltFlow gives a worked 10 HP example. A 1,000 foot overhead extension at $15.00 a foot is about $15,000 before the transformer, against $1,199 for a 10 HP rotary converter, so for one or two machines under 20 HP buy a converter. The utility starts to win when the connected three phase load passes roughly 30 to 40 HP, when a converter would run long hours every day, when the equipment will not accept a manufactured leg or when the line is already at the property. A building full of three phase equipment wants true three phase, a service transformer sized with the transformer sizing calculator and a utility quote in writing before anything is bought. A pad mounted transformer on three phase service is what our pages cover, see the three phase transformers guide and request a quote when the site is ready for it.

Related pages

Common questions

What is a phase converter

A device that makes three phase power for motors and machines from a single phase supply. The four common types are static, rotary, digital and a variable frequency drive for one motor.

How does a rotary phase converter work

An idler motor spins on single phase power and generates the third leg. The control panel and capacitors start it and balance the output, and the three legs feed a three phase panel. American Rotary rates its units to start a load of half the running rating.

Can a transformer convert single phase to three phase

No. A transformer keeps the number of phases it is given. Three phase power needs a phase converter, a VFD or a three phase utility supply. A transformer is used with a converter when the voltage has to change, such as 240 volts to 480 volts.

How much does a phase converter cost

A static converter lists from $299.95 to $599.95 for 1/3 to 10 HP. A rotary converter lists from $599 for 5 HP, $1,099 to $1,199 for 10 HP and $1,749 for 20 HP, and the Phoenix NL series runs $749 for 3 HP to $13,034 for 100 HP. Digital converters list at $1,625 for 5 load HP and $3,297 for 10.

What is the difference between a static and a rotary phase converter

A static converter starts one motor and lets it run on two legs at about two thirds of its horsepower. A rotary converter generates a real third leg with an idler motor and runs several machines at full power. See the rotary vs static phase converter comparison.

Is a VFD better than a phase converter

For one motor, often yes. A drive gives speed control and soft start, and costs $190 to $353 for the small sizes. Single phase input drives stop at about 3 HP, and a larger motor needs a derated drive or a converter.

How much does it cost to get three phase power from the utility

Tariffs range from $9.50 to $21.60 a foot for new line, plus fees and the transformer. A 1,000 foot overhead run comes to between about $9,500 and $15,700 before the transformer, per the tariffs above.

What size phase converter do I need

Double the largest motor horsepower and use 2.5 times for compressors and HVAC. A 10 HP motor on a general load needs a 20 HP rotary converter. Use the phase converter sizing calculator.