Bitcoin miner power consumption calculator

One Antminer S21 draws about 3,500 W, which is 14.6 A at 240 V and 84.0 kWh a day. Pick a miner, enter how many you run and your rate, and get amps, kWh, cost and the transformer a farm needs.

Updated November 18, 2026

Amps per miner14.6 A at 240 V
Total load350.0 kW
kWh per day8,400 kWh
kWh per month, 30 days252,000 kWh
Electricity cost per month$15,120
Electricity cost per year$183,960
Hash rate20.00 PH/s
Transformer kVA with headroom461 kVA
Next standard size500 kVA

Amps are watts divided by volts, which treats the miner power supply as near unity power factor. Check the nameplate current before you size breakers, and size each circuit at 125 percent of the continuous load.

Power, amps and efficiency by miner

MinerTH/sWattsJ/THAmps at 208 VAmps at 220 VAmps at 240 VAmps at 277 VkWh per day
Antminer S212003,50017.516.815.914.612.684.0
Antminer S21+2163,56416.517.116.214.912.985.5
Antminer S21 Pro2343,5101516.916.014.612.784.2
Antminer S21 Hydro3355,3601625.824.422.319.4128.6

Monthly electricity cost per S21

Thirty days at 3,500 W is 2,520 kWh per miner. Multiply by your own rate. These four are examples.

Rate per kWhOne S21 per month100 miners per month1,000 miners per month
$0.04$101$10,080$100,800
$0.06$151$15,120$151,200
$0.08$202$20,160$201,600
$0.10$252$25,200$252,000

Transformer size for an S21 farm

The table uses a 0.95 power factor and 25 percent headroom. Both are planning assumptions, change them in the calculator. Cooling load is not included. Compare with standard sizes in the transformer sizing calculator.

MinersLoad kWDesign kVANext standard sizeAmps at 480 V three phase
10354675 kVA90
100350461500 kVA601
5001,7502,3032,500 kVA3,007
1,0003,5004,6055,000 kVA6,014

Related

Sizing a farm service, request a quote with the kW, voltage and site.

Put this calculator on your site

Free for contractors, electricians, schools and trade sites. Paste this code into any page.

Common questions

How much power does a bitcoin miner use

An Antminer S21 is rated at about 3,500 W at the wall for 200 TH/s, which is 17.5 J/TH on the Bitmain specification. Bitmain lists a tolerance of about 5 percent on wall power, so a real unit can draw a little more or less.

How many amps does an Antminer S21 draw

About 14.6 A at 240 V, 16.8 A at 208 V and 12.6 A at 277 V, found by dividing watts by volts. Size the circuit at 125 percent of that continuous current.

How much does it cost to run one S21 for a month

One S21 uses 2,520 kWh in 30 days. At $0.06 per kWh that is about $151, and at $0.10 it is about $252.

What size transformer does a mining farm need

Divide the total kW by the power factor, then add headroom. One hundred S21 miners are 350 kW, which at 0.95 power factor and 25 percent headroom is 461 kVA, so a 500 kVA transformer is the next standard size. Cooling fans, immersion pumps and dry coolers add to the load, so add them in.

How much electricity does the whole bitcoin network use

The Cambridge Digital Mining Industry Report of April 2025 estimated about 138 TWh a year. Cambridge later published a preliminary annualized figure of about 190 TWh for December 2025. Annualized means the rate at that moment continued for a year.

Sources

  • Bitmain support page, S21 specifications, 200 TH/s, 3,500 W at the wall at 25 C and 17.5 J/TH, with the manual noting about 3 percent on hash rate and 5 percent on wall power.
  • Hashrate Index hardware overviews for the S21+ (216 TH/s, 16.5 J/TH, about 3,564 W), the S21 Pro (234 TH/s, 15.0 J/TH, about 3,510 W) and the S21 Hydro (about 5,360 W, 16 J/TH). Hydro hash rate is reported as 335 to 355 TH/s by different sources, so the low figure is used.
  • Cambridge Centre for Alternative Finance, Digital Mining Industry Report, April 2025, about 138 TWh a year, and the preliminary December 2025 annualized estimate of about 190 TWh as reported by trade press.
  • Amps, kWh, cost and kVA on this page are computed here from the wattage and the numbers you enter. Electricity rates in the tables are examples, not quotes.
CallGet a quote