Home / Guides / NEMA 5-15 and 5-20 Plugs and Receptacles Explained
NEMA 5-15 and 5-20 Plugs and Receptacles Explained
A NEMA 5-15 is the standard 125 volt, 15 amp outlet. A NEMA 5-20 is the 125 volt, 20 amp version, and its T shaped neutral slot takes both 15 amp and 20 amp plugs. A 5-15 outlet takes only 15 amp plugs. The two share the same voltage and the same three wire layout, so the real difference is the circuit behind them. A 15 amp circuit uses 14 AWG copper and a 15 amp breaker, and a 20 amp circuit uses 12 AWG copper and a 20 amp breaker. The sections below cover the fit, the code rule, the continuous load limit and what each means for charging an electric vehicle on a regular outlet.
Updated November 17, 2026
5-15 and 5-20 at a glance
All NEMA 5 devices are grounded, three wire (hot, neutral, ground) and rated 125 volts. The number after the hyphen is the current rating. The table adds the 80 percent continuous figure that the NEC applies to loads that run three hours or more, and the power that figure gives at 120 volts. Those two columns are computed here, the rest is from the NEMA configuration list.
| Configuration | Rating | Poles and wires | Continuous limit at 80 percent | Power at that limit, 120 V | Where it is found |
|---|---|---|---|---|---|
| 5-15 | 15 A, 125 V | 2 pole, 3 wire grounding | 12 A | 1.44 kW | Standard household outlet and plug |
| 5-20 | 20 A, 125 V | 2 pole, 3 wire grounding | 16 A | 1.92 kW | Kitchens, garages, shops, commercial buildings |
| 5-30 | 30 A, 125 V | 2 pole, 3 wire grounding | 24 A | 2.88 kW | Uncommon, twist lock plugs are used instead |
| 5-50 | 50 A, 125 V | 2 pole, 3 wire grounding | 40 A | 4.80 kW | Uncommon, twist lock plugs are used instead |
The 80 percent figures follow the NEC continuous load rule as described by Electrical Technology. Power is amps times 120 volts.
How to tell a 5-15 from a 5-20 and which plug fits which outlet
The 5-20P plug has its neutral blade turned 90 degrees, so it sits sideways. The 5-20R receptacle has a T shaped neutral slot, which lets it accept a 5-15 plug (straight blades) and a 5-20 plug (one sideways blade). Wikipedia notes that an alternative 5-20R with a plain rectangular slot exists and takes only 5-20 plugs.The 5-15R has straight slots only, so a 5-20 plug will not go in. That is the point. A 20 amp appliance cannot be plugged into a 15 amp outlet by accident. The 5-30 and 5-50 are physically larger with 1 inch between the power blades, and the 5-30 has an L shaped neutral blade.
| Plug | Fits 5-15R | Fits 5-20R |
|---|---|---|
| 5-15P | Yes | Yes |
| 5-20P | No | Yes |
| 5-30P | No | No |
| 5-50P | No | No |
The circuit rule for 5-15 and 5-20 receptacles
The sources agree on how NEC 210.21(B) works. A single receptacle on its own circuit must have a rating at least equal to the circuit, so a 20 amp circuit serving one receptacle needs a 5-20R. On a circuit with two or more receptacles, Table 210.21(B)(3) applies. A 20 amp circuit may feed 15 amp or 20 amp receptacles, which is why a house with 20 amp kitchen circuits is full of ordinary 5-15 duplex outlets. A 15 amp circuit may feed only 15 amp receptacles.One consumer guide we read says a 5-20 outlet needs 12 AWG wire and a 20 amp breaker. That is the usual pairing but it is a separate check from the receptacle rule, so the table below shows both. Code editions and local amendments differ, so confirm the rule in the edition your inspector enforces.
| Circuit breaker | Copper wire | Wire ampacity at 60 C | Receptacles allowed |
|---|---|---|---|
| 15 A | 14 AWG | 15 A | 5-15R only |
| 20 A, one receptacle | 12 AWG | 20 A | 5-20R |
| 20 A, two or more receptacles | 12 AWG | 20 A | 5-15R or 5-20R |
| 30 A | 10 AWG | 30 A | 5-30R |
Wire ampacities are NEC Table 310.16, 60 degree C column. Electrical Technology gives 14 AWG copper for 15 amp and 12 AWG copper for 20 amp circuits.
Continuous load limits and Level 1 EV charging
A load that runs three hours or more counts as continuous, and the NEC limits it to 80 percent of the circuit. That makes 12 amps the limit on a 15 amp circuit and 16 amps the limit on a 20 amp circuit, or 1,440 watts and 1,920 watts at 120 volts.Plugging an electric vehicle into a regular outlet is Level 1 charging. At 12 amps and 120 volts it adds 1.44 kW, which is a slow rate. A dedicated 20 amp circuit with a 5-20R allows 16 amps, or 1.92 kW. Faster charging needs 240 volts, see the NEMA 14-50 guide and the NEMA 6-50 guide. Do not share the circuit with other loads while charging.
5-30, 5-50 and the RV plug
The 5-30 and 5-50 exist and are 125 volt devices, but Wikipedia notes they are uncommon because twist locking plugs are generally used for high current. RVs use a different straight blade device, the TT-30, for 30 amp 120 volt campground power, and adapters from TT-30 to 5-15 or 5-20 are sold. For 240 volt power the common choices are the 6-50, 14-30 and 14-50, all covered in the NEMA plug chart.
Where this meets transformers
A 120 volt receptacle is fed from the secondary of a service transformer, usually a 120/240 volt single phase transformer or one leg of a 208Y/120 volt three phase one. The kVA that all those 15 and 20 amp circuits add up to is what sizes the pad mounted transformer behind the building, and the single phase wiring configurations guide shows how the 120 volt and 240 volt legs are made.
Related pages
Common questions
Can I plug a 15 amp plug into a 20 amp outlet
Yes. A 5-20R receptacle has a T shaped neutral slot that accepts both 5-15 and 5-20 plugs.
Can I plug a 20 amp plug into a 15 amp outlet
No. A 5-15R has straight slots only, so the sideways blade of a 5-20 plug will not fit.
Can I put a 15 amp outlet on a 20 amp circuit
Yes when the circuit has two or more receptacles, because Table 210.21(B)(3) allows 15 amp or 20 amp receptacles on a 20 amp circuit. A single receptacle on its own 20 amp circuit must be a 20 amp receptacle.
Can I put a 20 amp outlet on a 15 amp circuit
No. A 15 amp circuit takes 15 amp receptacles only, and the 14 AWG wire is sized for 15 amps.
What wire size for a 5-20 outlet
12 AWG copper on a 20 amp breaker, which has an ampacity of 20 amps at 60 degrees C in NEC Table 310.16.
How much can I run continuously on a 5-15 outlet
12 amps, or 1,440 watts at 120 volts, which is 80 percent of the 15 amp rating.
What does NEMA 5-15P mean
NEMA is the standards body, 5 is the 125 volt grounded two pole class, 15 is the amp rating and P means plug. R means receptacle.
Sources
- Wikipedia, NEMA connector
- Electrical Technology, difference between 15 amp and 20 amp outlets
- Interpower, NEMA nomenclature guide
- NEC Table 310.16 values as shown on our wire ampacity chart
Free to cite with a link to this page. Work out current at any rating with the kVA to amps calculator.