Both parts keep a generator from feeding power back onto the utility line while the grid is down. A breaker interlock is a sliding plate on the main panel that lets either the main breaker or the generator breaker be on, never both. A transfer switch is a separate switch that moves the loads between the utility and the generator, by hand or automatically. The interlock is the cheaper option and the transfer switch is the cleaner one on code.

Updated November 17, 2026

Interlock kitTransfer switch
How it worksA metal plate on the main panel lets only the main breaker or the generator breaker be closed at one time. The generator plugs into an inlet and feeds the panel through its own double pole breaker.A switch with a utility side and a generator side. A manual switch is thrown by hand. An automatic switch senses the outage, starts the generator and transfers the load.
Installed cost, 2026 estimate$400 to $850 for labor and materials, per HomeGuide.$400 to $1,300 for a manual switch and $600 to $2,500 for an automatic switch, installed, per HomeGuide. Unit only, $200 to $800 manual and $400 to $2,000 automatic.
Loads servedThe whole panel, but the owner chooses which breakers to leave on so the load stays inside the generator size.A manual switch with a subpanel serves only the circuits moved to that subpanel. A whole house switch serves the panel.
Automatic startNo. Someone has to start the generator, plug it in and flip the breakers.Only with an automatic transfer switch and a generator with an auto start controller.
Code status under NEC 702Disputed. Electricians in a Mike Holt forum thread say 702.5 calls for listed transfer equipment and that an interlock is not clearly listed as transfer equipment, though it is very common. Some say the inspector can allow it under 90.4. A forum poster reports a draft of the 2026 code would add interlock kits, which could not be confirmed here.Transfer equipment is the thing 702.5 describes. A listed transfer switch is the accepted route.
ListingThe kit must be designed and listed for the brand and model of the panel it goes in. A generic kit on an unlisted panel is the main risk.Listed transfer equipment with a stated amp rating.
Inlet and breaker for a 30 amp generatorA 30 amp 240 volt inlet and a 30 amp double pole breaker carry up to 7,200 watts, about 5,760 watts continuous at 80 percent.The switch is sized to the circuits or the panel it moves, not to the generator inlet.
Inlet and breaker for a 50 amp generatorA 50 amp 240 volt inlet and a 50 amp double pole breaker carry up to 12,000 watts, about 9,600 watts continuous at 80 percent.A 50 amp generator feeds a 50 amp inlet on the switch or subpanel the same way.
Best forA portable generator, an owner who will start it by hand and wants the lowest cost, where the inspector allows it.A standby generator, an owner who wants it to start by itself, or a jurisdiction that requires listed transfer equipment.

Which you actually need

Choose a transfer switch for a standby generator, for automatic start or where the inspector wants listed transfer equipment. Choose an interlock kit only for a portable generator, only with a kit listed for your panel and only where the local inspector accepts it. Either one prevents backfeed, which is a hazard to the line crews working on a dead line. Ask the electrician and the inspector which route is accepted before buying hardware.

How an interlock works. The kit bolts to the panel cover. A slide sits between the main breaker and the generator breaker, so when one is up the other is held down. The generator cord plugs into a power inlet on the outside wall and runs to the generator breaker. With the main breaker off, the panel is isolated from the utility, and the home runs from the generator.

How a transfer switch works. A manual transfer switch is a switch with three positions, utility, off and generator, wired to the panel or a subpanel. An automatic transfer switch senses loss of utility voltage, starts the generator, waits for it to reach voltage and moves the load. When the utility returns it moves back and stops the generator. Large buildings use the same idea at higher ratings, see the transfer switch and switchgear pages.

Sizing the load. The generator size sets how much can run. Add the running watts of what you want to power, and allow for the starting surge of motors. For a larger or permanent set, size from the kVA chart and see the generator pages.

Neutral bonding. Whether the neutral is switched or bonded to ground depends on the generator and the equipment. Follow the generator manual and the inspector, and have an electrician check it, since a wrong neutral connection is dangerous.

Related pages. A meter socket device is a third route, see how a meter collar transfer switch works. Size the set with the generator kVA to kW and amps chart and plan fuel with the generator fuel consumption calculator.