Switchgear vs Switchboard vs Panelboard, Differences in Ratings, Access and Standards

All three hold breakers on a bus, and the three names get swapped constantly. They are different products with different UL standards, sizes and fault ratings. A panelboard hangs on a wall and is reached from the front. A switchboard is a floor mounted assembly. Switchgear is the heaviest of the three, built with draw out breakers in separate compartments. Load centers are covered too, since a load center is the residential form of a panelboard.

Updated November 16, 2026

PanelboardSwitchboardSwitchgear
UL standardUL 67UL 891UL 1558 for low voltage metal enclosed switchgear
Typical voltageUp to 600 V, higher ratings exist. Load centers are made for up to 240 V and normally rated to 225 ANormally up to 600 VUp to 38 kV
Current ratingUp to 1200 A. Load centers normally 225 A, one maker offers up to 600 ASeldom used under 1200 A, up to 5000 AUp to 6000 A
MountingWall, in a cabinet. Recessed units need 2x6 studsFloor mounted, usually starting at 18 inches deepFloor mounted lineup, the largest of the three
BreakersPlug in or bolt on in small sizes, bolt on only in large sizesBolt on or draw outNormally draw out, each in its own compartment
AccessFront only, dead frontFront, and often rear and sideFront and rear
Short circuit withstandRated for 3 cyclesRated for 3 cycles, higher fault currents than panelboardsRated for up to 30 cycles
Where it sitsBranch circuits and tenant panelsMain service and large feedersCritical and industrial mains, outdoor service gear
Factory lead time, one 2026 Arizona fabricator3 to 7 weeks, same week from stock10 to 18 weeks for 800 to 2000 A16 to 26 weeks, 20 to 36 weeks for 5 kV class

Which you actually need

Pick by amperage and fault current first. Under about 1200 A and a modest available fault current, a panelboard is almost always the right and cheapest answer. Between 1200 A and 5000 A at 600 V or less, a switchboard is the normal main service. Choose switchgear when the system needs draw out breakers so a breaker can be serviced without shutting down the main, when fault current is high, or when the voltage is above 600 V. In all three cases the secondary of the pad mounted transformer lands on one of these, so size the transformer and the gear together, and check the gear short circuit rating against the transformer kVA and impedance.

Panelboards, switchboards and switchgear are all defined in Article 100 of the NEC. The Code does not limit any of them to a voltage or current range. The ranges above are what manufacturers such as ABB, Eaton and Schneider Electric actually build, so a specific product can fall outside them.

Main service gear is often mounted outside the building. A section of the gear can hold the utility current transformers and meter, so no separate CT enclosure is needed. Panelboards are then used downstream wherever possible to save wall and floor space.

Medium voltage switchgear above 1000 V follows different standards than the low voltage gear in the table. Read our guide on what switchgear is for the voltage classes, metal clad and metal enclosed construction, and arc resistant designs.