Home / Guides / PCB Testing of Transformer Oil, Methods, Sampling and Cost
PCB Testing of Transformer Oil, Methods, Sampling and Cost
Transformer oil is tested for PCBs two ways. A laboratory runs gas chromatography under ASTM D4059 and reports a concentration. A field screening kit gives a pass or fail against a set action level in minutes. Use the kit to screen and the lab to confirm.
Updated November 18, 2026
When you need a test
Test before you sell, move, scrap or drain a liquid filled unit whose PCB status is unknown, and before you buy a used one. A pre 1979 mineral oil unit with no record is treated as PCB contaminated until a result says otherwise. The categories and the 50 and 500 ppm lines are in the PCB transformers guide.
Lab method, ASTM D4059
ASTM D4059 is a gas chromatography test method for PCBs in electrical insulating liquids. It also covers the askarel mixtures used as insulating liquids. The method works when the standard PCB mixtures and the PCBs in the sample are closely related, and Aroclors 1242, 1254 and 1260 are named as adequate standards. It may not suit PCBs from other contamination sources. The current version is D4059-00(2018).
Field screening kits
Dexsil sells Clor-N-Oil kits with action levels of 20, 50 and 500 ppm. The maker says each kit has everything needed and runs in under 5 minutes, and that it calibrates on Aroclor 1242 to give conservative results. A sample that turns purple is below the action level of that kit. The kits are for dielectric fluid only and must not be used on motor oil or other lubricants. They are a screen, not a confirmation, so send positive or borderline samples to a lab.
Which kit matches which line
Pick the kit by the decision you need to make.
| Decision | Kit action level | Next step on a fail |
|---|---|---|
| Is it non PCB | 50 ppm | Send to a lab for a number |
| Is it a full PCB transformer | 500 ppm | Treat as PCB until a lab says otherwise |
Kit levels from the Dexsil and Andax product pages. Check the kit instructions for the exact procedure.
Pulling the sample
The sample must come from the unit itself, taken by someone trained to work on energized or de-energized gear safely. Pad mount and pole units have a drain valve or sampling port, and the person pulling it follows the lab's container and volume instructions. A Philippine government testing annex calls sampling the true bottleneck of any PCB inventory, since reaching each unit takes more time than the test. Ask your lab or utility for its sampling protocol before you start.
Cost and turnaround
Kits are cheap compared with lab work. Public listings show a 20 test pack of the Dexsil kit at 230 dollars and a J Harlen 20 pack at 265.95 dollars, roughly 11.50 to 13.30 dollars a test. Prices change, so check the seller. Lab pricing is not published in the sources we found, so we do not quote it. Ask the lab for a per sample price, turnaround and whether they report to the ppm.
Reading the result
Under 50 ppm is non PCB. From 50 to 499 ppm is PCB contaminated. At 500 ppm or more is a PCB transformer. Keep the report with the unit. Buyers, haulers and recyclers all ask for it.
Related pages
Common questions
What method is used to test transformer oil for PCBs
Laboratories use gas chromatography under ASTM D4059. Field kits such as Clor-N-Oil screen against a fixed action level.
How long does a PCB field test take
The maker of the Clor-N-Oil kit says under 5 minutes.
Can I use a field kit for the final answer
Treat it as a screen. Positive or borderline results should be confirmed by a gas chromatography lab.
Can the kit test motor oil
No. The maker says the kits are for dielectric fluid only.