PCB Transformers, How to Tell If a Transformer Contains PCBs

A PCB transformer is one whose insulating liquid contains 500 ppm or more of polychlorinated biphenyls. Between 50 and 499 ppm it is PCB contaminated, and under 50 ppm it is non PCB. A nameplate can raise suspicion, but only a lab or screening test of the fluid gives the number.

Updated November 18, 2026

The three categories

Federal rules under 40 CFR 761 sort liquid filled transformers by the PCB concentration in the fluid.

CategoryPCB concentrationTypical fluid
PCB transformer500 ppm or moreAskarel or heavily contaminated oil
PCB contaminated50 to 499 ppmMineral oil that picked up PCBs
Non PCBUnder 50 ppmClean mineral oil, ester or retrofilled fluid

Thresholds as stated in the PCB rules at 40 CFR 761. State rules and utility policy can be stricter, so confirm locally.

Why PCBs were used

Askarel was a fire resistant dielectric made from concentrated PCB formulations. It was used in transformers placed indoors and in buildings where mineral oil was a fire concern. Equipment known to hold these fluids is generally treated as PCB equipment.

Trade names to look for

A 1998 Federal Register notice lists names under which PCB containing fluids were sold. The ones most likely to appear on a transformer nameplate are Askarel, Pyranol, Inerteen and Chlorextol. The wider list also includes Asbestol, Clophen, Diaclor, Dykanol, Elemex, Fenclor, Hyvol, Kennechlor, No-Flamol, Phenoclor, Pyralene, Saf-T-Kuhl and Santotherm. If a nameplate shows any of these, treat the unit as suspect until a test says otherwise.

A nameplate does not settle it

AXA XL risk guidance notes that many retrofilled askarel transformers now test below 50 ppm, so the fluid name alone does not set the regulatory category. The reverse also happens. A mineral oil unit can pick up PCBs from contaminated equipment or handling. Under 40 CFR 761.2, mineral oil filled equipment made before July 2, 1979 with no established PCB level is treated as PCB contaminated, not as a full PCB transformer.

What to check on a unit

Read the nameplate for fluid type, gallons and year. Look for a non PCB or PCB label. Ask for any past oil test report, since a dated lab result beats any guess. A unit with no record and a pre 1979 date should be tested before it is moved, sold or scrapped. See the guide on how to read a transformer nameplate for the other fields.

If a test comes back high

A result at 500 ppm or more means the unit and its fluid fall under the PCB transformer rules for use, storage and disposal. 40 CFR 761.30 allows a unit to be reclassified after retrofilling and a period of loaded operation, with a follow up test deciding the new category. Do not drain, move or scrap the unit before you know the category. Disposal steps are in the guide on transformer oil disposal and recycling.

Scrap and resale

A transformer that tests non PCB can be sold or scrapped like any other. A PCB unit cannot go to an ordinary scrapyard. Buyers of used units usually ask for a PCB test report, which is why the test is worth doing before you list a transformer.

Related pages

Common questions

What is a PCB transformer

A transformer whose fluid contains 500 ppm or more PCBs. Units at 50 to 499 ppm are PCB contaminated and units under 50 ppm are non PCB.

How do I know if my transformer has PCBs

Read the nameplate for askarel trade names and the build year, then test the oil. Only a lab or screening test gives the concentration.

Can a mineral oil transformer have PCBs

Yes. Mineral oil units can be contaminated. Mineral oil equipment made before July 2, 1979 with no established level is treated as PCB contaminated.

Does Pyranol or Inerteen on the nameplate mean the unit is still PCB

Not always. Many retrofilled askarel units now test under 50 ppm, so test the fluid.