Padmount Supply

Home / Guides / Service Entrance Cable Types SE, SER, SEU, USE and URD Explained

Service Entrance Cable Types SE, SER, SEU, USE and URD Explained

Service entrance cable carries power from the service point to the meter and panel. SE cable is covered by NEC Article 338, and the letter U marks underground use. SER and SEU are above ground cables. USE-2 and URD are the types built to go underground. A common 200 amp aluminum size is 4/0 4/0 2/0.

Updated November 18, 2026

The names

Type SE stands for service entrance and type USE for underground service entrance. Article 338 covers both. SER and SEU share a 600 V rating and a rating up to 90 degrees C. The difference is construction. SER is round and SEU is flat, per the distributor sources below. Several sellers swap the two, so check the jacket marking and UL 854 listing on the reel.

Which type goes where

NEC 338.12 lists uses not permitted. Sources agree that SER and SEU are not for direct burial or underground use, and that USE and USE-2 are listed for underground installation including direct burial.

TypeWhere it is usedUnderground
SEUFlat cable for service entrance above groundNo
SERRound cable for service entrance and feeders above groundNo
USE-2Single conductors for underground services, RHW-2 or XHHW-2 insulation at 90 degrees CYes, including direct burial
URDUnderground distribution cable, multi conductor assembliesYes

From the ECM Code Standards article, the ARH Foundation SER guide and the NPC Electric URD and USE-2 comparison. Verify against the current NEC text.

Utility side and customer side

A service lateral runs underground from the utility transformer to the customer, and USE-2 or URD cable fits that run. Above ground runs to the meter and panel use SE cable. Utility rules vary, so ask the utility which cable it accepts before you order.

The 200 amp size

Distributor sources give 4/0 4/0 2/0 aluminum as the usual size for 200 amp service entrance cable. The label alone does not make a cable right for the job. A 4/0 4/0 2/0 URD product is a separate family built for burial, not above ground service entrance. Listings often show 200 A for SER and 205 A for SEU, but the allowed ampacity depends on termination temperature and conditions.

Temperature limits

Since the 2008 NEC, SE cable used for branch circuits or feeders follows the 60 degree C ampacity rule that applies to NM cable. USE-2 conductors are rated 90 degrees C in wet, damp or dry locations. Terminations rated 75 degrees C limit what you can use. Read NEC 310 and 338.10 for your edition.

Size the cable from the load

Start from the service current. The kVA to amps calculator gives the secondary current from the transformer rating, and the voltage drop calculator checks long runs.

Related pages

Common questions

What is the difference between SER and SEU cable

Both are 600 V service entrance cable rated to 90 degrees C. SER is round and SEU is flat.

Can SER cable be buried

No. SER and SEU are not rated for underground use. USE-2 and URD are the underground types.

What size aluminum service entrance cable is used for 200 amps

4/0 4/0 2/0 aluminum is the common size, but confirm ampacity under NEC 310 for your terminations.

What is URD cable

URD is underground residential distribution cable, built for burial and used for utility distribution and underground laterals.

Sources

Free to cite with a link to this page. Work out current at any rating with the kVA to amps calculator.

More guides

CallGet a quote