What Is a Contactor, Contactor vs Relay and NEMA Size Chart
A contactor is an electrically controlled switch built to make and break heavy current. A small control signal energizes a coil, the coil pulls the main contacts closed, and the load, usually a motor, heater or lighting circuit, turns on. A contactor is not a relay, which is rated for lighter loads, and it is not a full motor starter until an overload relay is added. The NEMA size chart and the IEC utilization categories below show how contactors are rated.
Updated November 16, 2026
How a contactor works
Applying the rated control voltage across the coil terminals, marked A1 and A2, pulls an armature in and closes the main power contacts. Removing the voltage lets a return spring open them. The coil voltage must match the control supply and not the load voltage. A three pole contactor marks its power terminals L1, L2 and L3 on the line side and T1, T2 and T3 on the load side. Auxiliary contacts, commonly marked 13 and 14 for normally open and 21 and 22 for normally closed, carry only control current and are used for holding circuits, interlocks and status signals.
Contactor vs relay vs motor starter
A relay switches lower power. Contactors have larger contacts, better contact material, arc suppression and a stronger build so they can switch motor level current repeatedly. A contactor on its own gives switching, not complete overload or short circuit protection. A magnetic motor starter is a contactor plus an overload relay, and the overload contact is wired in series with the coil so a trip drops the contactor out. Short circuit protection comes from the breaker or fuse upstream, which is where the AIC rating matters.
NEMA size chart, amps and horsepower
NEMA sizes group contactors and starters by rated current and power. Pick the size for the motor horsepower at your voltage. Where the table shows a dash, no rating is given at that voltage for that size.
| NEMA size | Max continuous amps | Max HP at 200 V | Max HP at 230 V | Max HP at 460 to 575 V |
|---|---|---|---|---|
| 00 | 9 | 1.5 | 1.5 | 2 |
| 0 | 18 | 3 | 3 | 5 |
| 1 | 27 | 7.5 | 7.5 | 10 |
| 2 | 45 | 10 | 15 | 25 |
| 3 | 90 | 25 | 35 | 50 |
| 4 | 135 | 40 | 50 | 100 |
| 5 | 270 | 75 | 100 | 200 |
| 6 | 540 | 150 | 200 | 400 |
| 7 | 810 | - | 300 | 600 |
| 8 | 1,215 | - | 450 | 900 |
| 9 | 2,250 | - | 800 | 1,600 |
Source values from NEMA ICS 2 as published in the NEMA size table. The 460 to 575 V column is listed as 480 and 575 V in the source.
IEC utilization categories
IEC 60947-4-1 sets utilization categories that say what load and duty a contactor is rated for. The same contactor has a different ampere rating in each category. A contactor listed at 25 amps in AC-1 might be only 9 amps in AC-3, because starting a motor draws 6 to 7 times its running current and wears the contacts faster.
| Category | Typical load | Typical power factor |
|---|---|---|
| AC-1 | Non inductive or slightly inductive loads such as resistance heating | Above 0.95 |
| AC-2 | Slip ring motors, starting and plugging | 0.65 to 0.85 |
| AC-3 | Squirrel cage motors, starting and switching off while running | 0.35 to 0.65 |
| AC-4 | Squirrel cage motors, plugging, jogging and inching | 0.35 to 0.65 |
| AC-22 | Mixed resistive and inductive loads | Not listed |
| AC-23 | Motor or other highly inductive loads | Not listed |
Source values from the IEC 60947-4-1 categories as summarized by the source cited below.
AC-3 versus AC-4
AC-3 switches a motor on at high current and switches it off at running current. AC-4 covers plugging, jogging and inching, where the contactor must make and break at high current again and again, so its rating is much lower. In one worked example from the source, a contactor that handles a 7.5 kW motor in AC-3 handles only a 2.2 kW motor in AC-4. An AC-1 contactor must not be used for motor control, since the high inrush and inductive switching can weld the contacts.
Contactors around transformers and power equipment
Contactors show up wherever motor and heater loads are switched, in motor control centers, on pumps and fans fed from a pad mount transformer secondary, and in control circuits supplied by a small control power transformer. A control transformer steps line voltage down to the coil voltage and its kVA has to cover the coil inrush of every contactor it feeds.
Related pages
Common questions
What is a contactor used for
To switch power to motors, heaters, lighting and other loads using a low power control signal on the coil.
What is the difference between a contactor and a relay
Both are electrically operated switches. A contactor is built for higher current with larger contacts and arc suppression, while a relay is for lighter loads and signals.
What are A1 and A2 on a contactor
The coil terminals. Voltage across A1 and A2 energizes the coil and closes the main contacts.
What NEMA size contactor for a 25 HP motor at 480 volts
NEMA size 2 is rated for up to 25 HP at 480 and 575 volts and 45 amps continuous, per the size table above. Check the motor full load amps and the manufacturer data before you order.
What is the difference between AC-1 and AC-3
AC-1 is for resistive loads at a power factor above 0.95. AC-3 is for squirrel cage motors, which have high inrush on starting, so the same contactor has a lower ampere rating in AC-3.
Sources
- Wikipedia, NEMA size
- Industrial Monitor Direct, IEC contactor utilization categories AC-1 to AC-4
- VIOX Electric, what is a contactor
- Tameson, contactor vs relay
Free to cite with a link to this page. Work out current at any rating with the kVA to amps calculator.