AIC Rating Explained, Breaker Interrupting Rating and Available Fault Current

AIC stands for amps interrupting capacity, the highest fault current a breaker or fuse can safely interrupt. It must be at least as large as the fault current available at that device, and the transformer feeding the equipment is the biggest factor in how large that current is. A larger kVA transformer with a lower impedance produces more fault current. The table below works out the upper limit at the secondary of common pad mount sizes.

Updated November 16, 2026

What AIC means

Interrupting rating, often called AIC, applies to a breaker or fuse. It must be equal to or greater than the available fault current at the line terminals of that device, which is the requirement of NEC 110.9. A breaker with too low a rating can fail violently when it tries to open a fault bigger than it was built for.

AIC rating versus SCCR

SCCR is the short circuit current rating of a whole equipment assembly, for example an industrial control panel. It must also be at least the available fault current where the equipment is installed. Industrial control panels must be marked with their SCCR under NEC 409.110, and UL 508A Supplement SB is an accepted way to work it out. Put simply, AIC is what a device can interrupt and SCCR is what an assembly can withstand. Both must clear the available fault current.

Fault current at the transformer secondary

The utility transformer is usually the main source of fault current at a service. A quick worst case figure assumes an infinite source on the primary and ignores the cable between the transformer and the equipment. It is conservative by design, and the Institute for the Advancement of Electrical Inspection notes that this method is allowed for the NEC 110.24 marking because the code asks for the maximum available fault current. The formula is full load amps divided by the per unit impedance, which is kVA times 1000 divided by 1.732 times volts times the percent impedance divided by 100.

Transformer kVAImpedance percentFault current at 480 V in kAFault current at 208 V in kA
453.51.53.6
754.02.35.2
112.54.23.27.4
1504.54.09.3
2255.05.412.5
3005.07.216.7
5005.510.925.2
7505.7515.736.2
10005.7520.948.3
15006.030.169.4
20006.040.192.5
25006.050.1115.7

Computed from the impedance values used on this site for each pad mount rating, three phase, infinite primary, no cable impedance, no motor contribution. The real value is lower once cable and primary impedance count, and higher if running motors feed the fault. Use the nameplate impedance for a real design.

How to read the table

A 1000 kVA transformer at 480 volts can deliver about 20.9 kA at the secondary terminals. A branch breaker with a 10 kA AIC at that point is not rated for the fault, but one with a 25 kA or 65 kA rating is. At 208 volts the same kVA gives far more current, 48 kA for the 1000 kVA unit, because current rises as voltage falls.

Fully rated versus series rated systems

In a fully rated system every breaker has an AIC at least equal to the available fault current at its own line terminals. In a series rated system, a tested and listed upstream device lets lower rated downstream breakers be applied above their own AIC. NEC 240.86 sets the rules. Only combinations the manufacturer has tested and marked are allowed, the assembly has to carry the series rating marking and a field marking is needed. A series rating cannot be used where motors connected between the upstream and downstream devices have a combined full load current above 1 percent of the lower breaker AIC. For example, with a 10 kA downstream breaker that limit is 100 amps of motor load. The series rating also cannot be claimed above the rating of the upstream device. A 65 kA upstream breaker cannot support a 100 kA series claim.

The NEC 110.24 field marking

Service equipment in other than dwelling units must be marked in the field with the maximum available fault current and the date the calculation was done. When the installation changes in a way that affects the fault current, it has to be verified or recalculated and the marking updated. This requirement is why a transformer replacement often triggers a new fault current calculation at the service.

Why this matters when you buy a transformer

Replacing a pad mount transformer with a larger or lower impedance unit raises the fault current on the secondary. Before you order, compare the new transformer fault current with the AIC of every breaker and the SCCR of every panel it feeds. If the numbers do not clear, the answer is higher rated equipment or a transformer with higher impedance, not a smaller breaker label.

Related pages

Common questions

What does AIC mean on a breaker

Amps interrupting capacity, the maximum fault current the breaker can interrupt without failing. It must be equal to or greater than the available fault current at the breaker, per NEC 110.9.

What is the difference between AIC and SCCR

AIC is the interrupting capability of a breaker or fuse. SCCR is the short circuit withstand rating of an equipment assembly. Both must be at least the available fault current.

How do you calculate available fault current from a transformer

Divide the transformer full load amps by the per unit impedance. For a three phase unit that is kVA times 1000 divided by 1.732 times volts times percent impedance over 100. This is a conservative upper figure that assumes an infinite primary source.

What is a series rated breaker

A downstream breaker applied above its own AIC because a listed upstream device protects it. The combination must be tested, marked and not used where motor contribution is too high.

Does the fault current label have to be on the panel

For service equipment in other than dwelling units, NEC 110.24 requires a field marking with the maximum available fault current and the date it was calculated.