Line to neutral voltage calculator

Divide line to line voltage by 1.732 to get line to neutral, or multiply line to neutral by 1.732 to get line to line. Enter either one below, in volts or kV.

Updated November 18, 2026

Line to line480 V, 0.48 kV
Line to neutral277.1281 V, 0.2771 kV

Balanced three phase wye system. Line to neutral equals line to line divided by 1.732, and line to line equals line to neutral times 1.732. A delta system has no neutral, so the line to neutral value only applies if the source is wye or has a grounded point.

Put this calculator on your site

Free for contractors, electricians, schools and trade sites. Paste this code into any page.

Line to neutral and line to line voltage table

Line to line, VLine to neutral, VWritten asWhere it shows up
208120.1208Y/120Commercial 208Y/120 panels
380219.4380Y/219Three phase 380 V systems
400230.9400Y/231Three phase 400 V systems
415239.6415Y/240Three phase 415 V systems
480277.1480Y/277Standard US industrial and commercial 480Y/277
600346.4600Y/346Canadian industrial 600Y/347
2,4001,3862400Y/1386Older medium voltage motor distribution
4,1602,4024160Y/2402Medium voltage motors and older plants
12,4707,20012470Y/7200Common utility primary
13,2007,62113200Y/7621Utility primary
13,8007,96713800Y/7967Utility and plant primary
24,94014,39924940Y/14399Utility primary
34,50019,91934500Y/19919Utility primary and subtransmission

Free to cite with a link to this page. Each line to neutral value is the line to line value divided by the square root of 3, computed here, then rounded in the written form the way utilities and nameplates round it. The Y marks a wye connection with a neutral.

The formula

  • Line to neutral equals line to line divided by 1.732.
  • Line to line equals line to neutral times 1.732.
  • Phase to phase is another name for line to line. Phase to ground is line to neutral on a grounded wye system.

Worked example. A 480Y/277 service has 480 V between any two phases. Each phase to neutral is 480 / 1.732 = 277 V, which is why 277 V lighting circuits run off a 480 V system. Step it down with a 480 to 208Y/120 transformer and the line to neutral becomes 208 / 1.732 = 120 V, the voltage on the receptacles. See the 480 to 208 volt transformer page for the sizes.

The current side of the same math is in the three phase transformer formulas and the kVA to amps calculator, which use line to line voltage and the same 1.732 factor.

kV to volts

One kilovolt is 1,000 volts. The table converts common system voltages.

Line to line, kVLine to line, VLine to neutral, kVLine to neutral, V
0.2082080.120120
0.484800.277277
0.66000.346346
2.42,4001.3861,386
4.164,1602.4022,402
12.4712,4707.2007,200
13.813,8007.9677,967
24.9424,94014.39914,399
34.534,50019.91919,919

Free to cite with a link to this page. Values are computed from the line to line voltage divided by 1.732 and are for a balanced wye system.

Wye compared with delta

The 1.732 relationship holds for a wye connection, where each winding sits between a phase and the neutral point. In a delta the windings sit between phases, so the winding voltage equals the line voltage and there is no neutral point. A pad mounted transformer with a wye secondary gives a neutral for single phase loads. A delta secondary does not, unless a tap is added. The delta wye transformer diagram shows how each winding is wired, and the three phase transformer wiring diagram covers the other common pairings.

High leg and corner grounded delta

A 240 V four wire delta with a center tapped winding gives 120 V from the tap to two of the phases. The third phase, called the high leg or wild leg, reads 240 x 0.866 = 208 V to the tap, computed from the same square root relationship. NEC 110.15 requires the high leg to be marked orange, so single phase 120 V loads must never be connected to it. A corner grounded delta bonds one phase to ground, so that phase reads 0 V to ground and the other two read the full line voltage. In both cases the simple line to line divided by 1.732 rule does not apply, which is worth checking before measuring or sizing a transformer for an older building.

Common questions

How do you calculate line to neutral voltage

Divide the line to line voltage by the square root of 3, which is 1.732. A 480 V system gives 480 / 1.732 = 277 V line to neutral. A 208 V system gives 120 V.

How do you convert line to neutral to line to line voltage

Multiply the line to neutral voltage by 1.732. 120 V line to neutral gives 208 V line to line, and 277 V gives 480 V.

What is phase to ground voltage

On a solidly grounded wye system the neutral is bonded to ground, so phase to ground voltage equals line to neutral voltage. A 480Y/277 system reads about 277 V from any phase to ground.

What is 12470 line to ground

12,470 / 1.732 = 7,200 V. That is why a common utility primary is written 12470Y/7200.

How do you convert kV to volts

Multiply by 1,000. 12.47 kV is 12,470 V, and 34.5 kV is 34,500 V. To go from volts to kV, divide by 1,000.

Does a delta system have a line to neutral voltage

A plain delta has no neutral, so there is nothing to measure from. If a delta secondary has a center tap on one winding, as in a 240 V high leg delta, the readings from the tap are 120 V to two phases and about 208 V to the high leg phase. A corner grounded delta reads full line voltage from each ungrounded phase to ground on two phases and zero on the grounded phase.

Why is line to neutral on a 208 volt system 120 volts

208 / 1.732 = 120. The three phase voltages are 120 degrees apart, and the vector difference between any two is 1.732 times one phase voltage.

Need a transformer for one of these voltages. Try the transformer sizing calculator, browse the transformer diagrams, or request a quote with the kVA and voltage.

Sources

  • Every voltage on this page is computed from the balanced three phase relationship, line to line equals the square root of 3 times line to neutral.
  • The written forms such as 480Y/277 and 12470Y/7200 follow the way North American nameplates and utilities state wye systems.
  • The high leg delta values are computed from a 240 V line to line system and a center tapped winding. The orange marking rule is NEC 110.15.