Home / Tools / Phase converter sizing calculator and chart
Phase converter sizing calculator and chart
A phase converter is sized from the largest motor it has to start, not from the total of everything on the panel. Pick the largest three phase motor and the type of load, and get the rotary converter rating, the next standard size, what a static converter will really deliver and the single phase amps to wire for. The chart below covers 1 to 50 HP.
Updated November 17, 2026
| Rotary converter, minimum rating | 20 HP (10 HP times 2) |
|---|---|
| Next standard rotary size | 20 HP, standard duty list price about $2,663 |
| Static converter | A 10 HP rated unit. The motor will deliver only about 6.7 HP, two thirds of nameplate. One motor, light loads only. |
| Digital converter | Sized by load HP. Makers name models by an equivalent HP that can be twice the load, so a 10 HP load can mean a 20 equivalent model name. |
| Single phase supply, motor at table amps | About 46.5 A at 240 V for the largest motor. The converter nameplate is the number to wire to. |
| Conductors and breaker, 125 percent | About 58.1 A. Article 455 sizes both from the nameplate single phase input amps. |
Multipliers of 1.5, 2 and 2.5 are converter maker rules of thumb, see the sources. Rotary list prices are the Phoenix Phase Converters NL series, February 2026, and exclude freight and installation. The supply amps ignore converter losses, so the nameplate is always higher. Standard rotary sizes in the list are 3, 5, 7.5, 10, 15, 20, 30, 40, 50, 75, 100 HP.
Rotary phase converter sizing chart, 1 to 50 HP
For each motor size, the minimum rotary converter at the three maker multipliers, the next standard size and the single phase input amps at 240 V. Motor amps are the NEC table values at 230 V. Prices are the published list price of the next standard Phoenix NL series size, February 2026.
| Largest motor | Motor amps, 230 V | Supply amps, 240 V | Rotary at 1.5 times | Rotary at 2 times | Rotary at 2.5 times | Standard size at 2 times, list price |
|---|---|---|---|---|---|---|
| 1 HP | 4.2 | 7.0 | 1.5 HP | 2 HP | 2.5 HP | 3 HP, $749 |
| 1-1/2 HP | 6 | 10.0 | 2.3 HP | 3 HP | 3.8 HP | 3 HP, $749 |
| 2 HP | 6.8 | 11.3 | 3 HP | 4 HP | 5 HP | 5 HP, $985 |
| 3 HP | 9.6 | 15.9 | 4.5 HP | 6 HP | 7.5 HP | 7.5 HP, $1,590 |
| 5 HP | 15.2 | 25.2 | 7.5 HP | 10 HP | 12.5 HP | 10 HP, $1,955 |
| 7-1/2 HP | 22 | 36.5 | 11.3 HP | 15 HP | 18.8 HP | 15 HP, $2,543 |
| 10 HP | 28 | 46.5 | 15 HP | 20 HP | 25 HP | 20 HP, $2,663 |
| 15 HP | 42 | 69.7 | 22.5 HP | 30 HP | 37.5 HP | 30 HP, $4,480 |
| 20 HP | 54 | 89.6 | 30 HP | 40 HP | 50 HP | 40 HP, $4,820 |
| 25 HP | 68 | 112.9 | 37.5 HP | 50 HP | 62.5 HP | 50 HP, $6,785 |
| 30 HP | 80 | 132.8 | 45 HP | 60 HP | 75 HP | 75 HP, $10,715 |
| 40 HP | 104 | 172.6 | 60 HP | 80 HP | 100 HP | 100 HP, $13,034 |
| 50 HP | 130 | 215.8 | 75 HP | 100 HP | 125 HP | 100 HP, $13,034 |
Free to cite with a link to this page. Multipliers are maker rules of thumb, not code. The converter nameplate and the maker sizing chart decide the final size.
The three multipliers and when each applies
Starting current is five to ten times running current, and a rotary converter has to deliver it from an idler motor. Phase-A-Matic cites that range and asks for a rotary unit 50 percent larger than the motor when the load starts hard. Phoenix says to double the largest motor and to go to 2.5 times for compressors and HVAC. The 1.5 times column is the easy load case, the 2 times column is the common shop case and the 2.5 times column is the hard start case. When several machines run at once, the converter also has to be at least as large as their running horsepower together, which the calculator checks.
Static converters are sized the other way
A static converter is a start device. It gets the motor spinning on a capacitor start circuit and then drops out, so the motor runs on two legs. Phase-A-Matic says the motor then develops about two thirds of its nameplate horsepower, and Phoenix says a static converter cuts output by one third to one half. So a 10 HP motor on a static converter delivers about 6.7 HP. Buy a static unit rated for the motor, never larger, because Phoenix warns that an oversized static unit can excite the motor so that it does not start. Static converters run one motor at a time and are for easy loads. The rotary versus static page has the full list of what each can run, see rotary vs static phase converter.
Supply wire and breaker for the converter
NEC Article 455 sizes the single phase feed from the converter nameplate. For variable loads the conductors are at least 125 percent of the nameplate single phase input amps and the breaker is no more than 125 percent of that figure. As a check, the 10 HP motor in the chart draws 28 A on 230 V three phase, which is about 46.5 A single phase at 240 V before converter losses, so a 10 HP rotary converter needs a feeder and breaker well above 46.5 A. American Rotary lists a 40 A minimum breaker for its ADX 10 and 60 A for its AD 20, which are the nameplate figures for those units. Use the nameplate, then look up the wire in the wire size by amps chart. Motor amps for every size are in the motor full load amps chart.
When a converter is the wrong answer
One or two machines under about 20 HP is converter territory. A shop with a building full of three phase equipment, or a three phase line within a few hundred feet, may do better with utility three phase and a transformer. A 480 volt machine on a 240 volt converter also needs a step up transformer, see the 240 to 480 volt transformer page and the phase converter guide for the cost comparison. A single motor that needs speed control can use a variable frequency drive instead, see what is a VFD.
Related
Three phase power calculator, HP to kVA calculator, kVA to amps calculator and the single phase vs three phase transformer comparison. For a pad mounted transformer that brings true three phase to the site, request a quote.
Common questions
How do you size a rotary phase converter
Start with the largest motor. Phoenix Phase Converters says to double its horsepower and to use 2.5 times for compressors and HVAC. Phase-A-Matic says 50 percent larger for machines with high starting current. American Rotary rates its units to start a load of half the running rating, which is the same as doubling. Then check that the converter is at least as large as all the motors that run together.
What size phase converter do I need for a 10 HP motor
For a general shop motor, double it, so a 20 HP rotary converter. An easy starting load can use 15 HP and a compressor 25 HP, which rounds up to the 30 HP size. A static converter rated for 10 HP would run the motor at about two thirds of its nameplate, near 6.7 HP.
Can a rotary phase converter be too big
A larger rotary converter starts hard loads more easily but its idler motor burns power whenever it runs. American Rotary lists 0.3 kW of idle draw for its 10 HP unit and 0.6 kW for its 20 HP unit. A static converter that is too large can over excite the motor, and Phoenix says that may stop it starting.
How many amps does a phase converter draw on single phase
The converter nameplate gives the input amps. As a check, a 10 HP motor at the NEC table figure of 28 A on 230 V three phase is about 11.2 kVA, which is roughly 46.5 A at 240 V single phase before converter losses. NEC Article 455 sets the conductors and the breaker at 125 percent of the nameplate figure.
Do I size a phase converter by HP or by amps
Both matter. Horsepower and load type set the idler size, because starting current is the hard part. Amps set the single phase supply wire and breaker. Phoenix also notes that amps alone are not a good way to size a converter.
What is the difference between 10 HP and 20 HP in a digital converter name
Some makers name digital converters by an equivalent HP that is twice the load they carry. The Phase Technologies Phase Perfect labelled 20 carries a 10 HP load, so compare it with a 10 HP rotary converter and not a 20 HP one.
Sources
- Phoenix Phase Converters, How Much Does a Phase Converter Cost, NL series list prices and sizing guidance, 20 February 2026, https://phoenixphaseconverters.com/blogs/news/how-much-does-a-phase-converter-cost-complete-pricing-guide
- Phoenix Phase Converters, Static vs Rotary Phase Converter Sizing Tips, https://phoenixphaseconverters.com/blogs/news/static-vs-rotary-phase-converters-sizing-tips-applications
- Phoenix Phase Converters, rotary converter sizing page, double the largest motor and 2.5 times for compressors and HVAC (seen in search results)
- Phase-A-Matic, sizing guidelines for static converters and rotary converter technical notes, 50 percent larger for high inrush loads (seen in search results)
- VoltFlow, How Much Does It Cost to Get Three Phase Power, 2026, American Rotary start rating and idle draw, Phase Technologies equivalent HP naming and NEC 455 sizing, https://www.voltflow.net/blog/cost-to-get-three-phase-power-2026
- NEC Table 430.250 three phase motor full load amps at 230 V, the same values as the motor full load amps chart on this site. Supply amps are computed as 1.732 times 230 V times table amps divided by 240 V.