Three phase power calculator

Enter line voltage and line current with a power factor to get kW, kVA and kVAR, or work backward from kVA or kW to amps. Three phase power is 1.732 x volts x amps, times power factor for real power.

Updated November 16, 2026

Enter line to line voltage and current with a power factor, or voltage with kVA or kW, or kVA with current. Leave the rest empty.

Apparent power83.138 kVA
Real power70.668 kW
Reactive power43.796 kVAR
Power factor0.85
Line voltage480 V
Line current100 A

The formulas

  • kVA equals 1.732 x volts x amps / 1000.
  • kW equals kVA x power factor.
  • kVAR equals the square root of (kVA squared minus kW squared).
  • Amps equals kVA x 1000 / (1.732 x volts), or kW x 1000 / (1.732 x volts x power factor).

Apparent power for common currents and voltages

Line current, AkVA at 208 VkVA at 480 VkVA at 600 V
103.68.310.4
259.020.826.0
5018.041.652.0
10036.083.1103.9
20072.1166.3207.8
400144.1332.6415.7

Free to cite with a link to this page. Computed as 1.732 x volts x amps / 1000. Multiply by power factor for kW.

Wye and delta, line and phase values

ConnectionLine voltageWinding voltageLine currentWinding current
Wye1.732 x phase voltageLine voltage / 1.732Equals winding currentEquals line current
DeltaEquals winding voltageEquals line voltage1.732 x winding currentLine current / 1.732

See the delta wye transformer diagram and the three phase transformers guide. Total power is the same either way, which is why the 1.732 formula uses line values for both. With an unbalanced load, calculate each phase as V line to neutral x I x PF and add the three.

Worked example

A plant draws 150 A at 480 V with a power factor of 0.88. kVA = 1.732 x 480 x 150 / 1000 = 124.7. kW = 124.7 x 0.88 = 109.7. kVAR = square root of (124.7 squared minus 109.7 squared) = 59.3. A 150 kVA transformer carries it, check sizes in the transformer sizing calculator and full load amps in the kVA to amps calculator. More at the three phase transformer formulas, single phase vs three phase, and the power factor calculator. Need a unit, request a quote.

Put this calculator on your site

Free for contractors, electricians, schools and trade sites. Paste this code into any page.

Common questions

What is the three phase power formula

Real power in watts is 1.732 x line voltage x line current x power factor. Apparent power in VA is 1.732 x V x I. Reactive power is the square root of (kVA squared minus kW squared).

Why 1.732

It is the square root of 3. Three voltages 120 degrees apart combine so that the line to line voltage is 1.732 times the line to neutral voltage in a wye system.

How many kW is 100 amps at 480 volts three phase

1.732 x 480 x 100 = 83.1 kVA. At a power factor of 0.85 that is 70.7 kW, and at 1.0 it is 83.1 kW.

How do you find amps from kW on three phase

Divide kW x 1000 by 1.732 x volts x power factor. 100 kW at 480 V and 0.9 power factor is 100,000 / (1.732 x 480 x 0.9) = 133.7 A. The kW to amps calculator does it for any voltage.

Is line current the same as phase current

In a wye connection yes. In a delta connection line current is 1.732 times the winding current, while the winding voltage equals the line voltage.

What is the most common mistake

Using 3 instead of 1.732 or leaving out the power factor. Multiplying volts by amps by 3 overstates the power by about 73 percent.

Sources

  • The three phase power equations, apparent power S = 1.732 x V x I, real power P = S x PF, reactive power Q = square root of (S squared minus P squared), are standard and every number here is computed from them.
  • The wye and delta line and phase relationships follow from balanced three phase theory.