Enter line to line voltage and current with a power factor, or voltage with kVA or kW, or kVA with current. Leave the rest empty.
The formulas
- kVA equals 1.732 x volts x amps / 1000.
- kW equals kVA x power factor.
- kVAR equals the square root of (kVA squared minus kW squared).
- Amps equals kVA x 1000 / (1.732 x volts), or kW x 1000 / (1.732 x volts x power factor).
Apparent power for common currents and voltages
| Line current, A | kVA at 208 V | kVA at 480 V | kVA at 600 V |
|---|---|---|---|
| 10 | 3.6 | 8.3 | 10.4 |
| 25 | 9.0 | 20.8 | 26.0 |
| 50 | 18.0 | 41.6 | 52.0 |
| 100 | 36.0 | 83.1 | 103.9 |
| 200 | 72.1 | 166.3 | 207.8 |
| 400 | 144.1 | 332.6 | 415.7 |
Free to cite with a link to this page. Computed as 1.732 x volts x amps / 1000. Multiply by power factor for kW.
Wye and delta, line and phase values
| Connection | Line voltage | Winding voltage | Line current | Winding current |
|---|---|---|---|---|
| Wye | 1.732 x phase voltage | Line voltage / 1.732 | Equals winding current | Equals line current |
| Delta | Equals winding voltage | Equals line voltage | 1.732 x winding current | Line current / 1.732 |
See the delta wye transformer diagram and the three phase transformers guide. Total power is the same either way, which is why the 1.732 formula uses line values for both. With an unbalanced load, calculate each phase as V line to neutral x I x PF and add the three.
Worked example
A plant draws 150 A at 480 V with a power factor of 0.88. kVA = 1.732 x 480 x 150 / 1000 = 124.7. kW = 124.7 x 0.88 = 109.7. kVAR = square root of (124.7 squared minus 109.7 squared) = 59.3. A 150 kVA transformer carries it, check sizes in the transformer sizing calculator and full load amps in the kVA to amps calculator. More at the three phase transformer formulas, single phase vs three phase, and the power factor calculator. Need a unit, request a quote.
Common questions
What is the three phase power formula
Real power in watts is 1.732 x line voltage x line current x power factor. Apparent power in VA is 1.732 x V x I. Reactive power is the square root of (kVA squared minus kW squared).
Why 1.732
It is the square root of 3. Three voltages 120 degrees apart combine so that the line to line voltage is 1.732 times the line to neutral voltage in a wye system.
How many kW is 100 amps at 480 volts three phase
1.732 x 480 x 100 = 83.1 kVA. At a power factor of 0.85 that is 70.7 kW, and at 1.0 it is 83.1 kW.
How do you find amps from kW on three phase
Divide kW x 1000 by 1.732 x volts x power factor. 100 kW at 480 V and 0.9 power factor is 100,000 / (1.732 x 480 x 0.9) = 133.7 A. The kW to amps calculator does it for any voltage.
Is line current the same as phase current
In a wye connection yes. In a delta connection line current is 1.732 times the winding current, while the winding voltage equals the line voltage.
What is the most common mistake
Using 3 instead of 1.732 or leaving out the power factor. Multiplying volts by amps by 3 overstates the power by about 73 percent.
Sources
- The three phase power equations, apparent power S = 1.732 x V x I, real power P = S x PF, reactive power Q = square root of (S squared minus P squared), are standard and every number here is computed from them.
- The wye and delta line and phase relationships follow from balanced three phase theory.