Home / Ratings / 75 kVA / 75 kVA 12470 to 480Y/277 pad mounted transformer
75 kVA 12470 to 480Y/277 pad mounted transformer
A 75 kVA three phase pad mounted transformer with a 12470GrdY/7200 primary and a 480Y/277 secondary draws 3.5 amps on the primary and 90.2 amps on the secondary at full load. It measures about 52 x 50 x 55 inches and weighs about 1,750 lb. Updated 19 November 2026.
Updated November 21, 2026
Specifications
| Primary voltage | 12470GrdY/7200, grounded wye, 15 kV class |
|---|---|
| Secondary voltage | 480Y/277, four wire |
| BIL | 95 kV listed for this primary in a published design standard |
| Typical impedance | 4.0 percent. Published ranges for this size run wider, so use the nameplate |
| Dimensions | About 52 x 50 x 55 in, width by depth by height |
| Weight | About 1,750 lb including fluid |
| Feed | Loop or radial, see below |
Full load and fault current
| Side | Line voltage | Full load amps |
|---|---|---|
| Primary | 12,470 V | 3.5 A |
| Secondary | 480 V | 90.2 A |
| Secondary fault, infinite bus | 480 V | 2,255 A |
Computed here. The fault figure is full load amps divided by 4.0 percent impedance and is a ceiling, since the utility source adds impedance.
Tap settings at a 12470 primary
Two taps above and two below nominal at 2.5 percent steps, full capacity, are standard on this site's ratings. This table shows the primary voltage each tap sets and the secondary a 12470 volt supply then delivers.
| Tap | Primary tap voltage | Secondary at 12,470 V in |
|---|---|---|
| +5% | 13,094 V | 457 V |
| +2.5% | 12,782 V | 468 V |
| 0% | 12,470 V | 480 V |
| -2.5% | 12,158 V | 492 V |
| -5% | 11,847 V | 505 V |
Details on how taps work.
Loop or radial feed
At 12470 volts a 75 kVA unit on a residential or commercial lateral is usually fed either in a loop, with six primary bushings so the line passes through, or radial with three. Which the utility wants decides the order. See loop feed versus radial feed and dead front versus live front.
Same rating, other voltages
The secondary current changes with the voltage. For the 208Y/120 secondary, use the kVA to amps calculator. For an indoor 480 volt unit see the 75 kVA dry type transformer. The general rating page is 75 kVA pad mounted transformer. The voltage pair is covered on 12470 to 480 volt transformers, and all voltages are listed.
Lead times, from stock or from a factory, are tracked in the transformer lead time guide. For a quote on this exact configuration, send us your spec or call 786 220 2801.
Common questions
How many amps is a 75 kVA 12470 to 480Y/277 transformer
3.5 amps on the 12470 volt primary and 90.2 amps on the 480 volt secondary at full load, from kVA times 1000 divided by 1.732 times the line to line voltage.
What does 12470GrdY/7200 mean
The primary is a grounded wye connection. 12470 volts is the line to line voltage and 7200 volts is line to neutral, which is 12470 divided by 1.732.
What BIL does a 12470GrdY/7200 primary use
A university design standard for three phase pad mounted units lists 12470GrdY/7200 at 95 kV BIL. Confirm against the serving utility specification.
What is the fault current at the 480 volt terminals
About 2,255 amps on an infinite bus with 4.0 percent impedance, which is 90.2 amps divided by 4.0 percent. A real system with source impedance sees less.
Can a 12470 unit run on a 13200 system
Only through taps. Full capacity taps of plus and minus 2.5 and 5 percent reach 13,094 volts on the high tap, so a 13200 system needs a unit specified for it. Order the primary that matches the utility.
Who sizes the primary fuse
The serving utility or the manufacturer coordinates it. Specifications seen in public bids ask the manufacturer to coordinate a partial range current limiting fuse with a Bay O Net fuse. No generic sizing is given here.
Sources
- Southern Methodist University three phase pad mounted distribution transformer design standard, 95 kV BIL for 12470GrdY/7200.
- Columbus, Ohio three phase pad mounted transformer specification, fusing coordination wording.
- Surplus and dealer listings for 75 kVA 12470GY/7200 to 480Y/277 units confirm the configuration is a common one.
- Amps, taps and fault current are computed here from kVA, voltage and the impedance on this site's 75 kVA rating page.