Home / Products / Dry type transformers / Single phase dry type transformer, 240x480 to 120/240
Single phase dry type transformer, 240x480 to 120/240
The standard single phase dry type transformer has a 240x480 volt primary and a 120/240 volt secondary, so one unit works from a 480 volt or a 240 volt supply and feeds both 120 and 240 volt loads. A 25 kVA unit draws 52.1 amps at 480 volts and delivers 104.2 amps at 240 volts. In November 2026 public listings put a new 25 kVA unit at about $2,100 to $6,700 and a used one near $315. We quote new, new surplus and reconditioned units delivered.
Updated November 16, 2026
What the 240x480 to 120/240 rating means
The primary has two 240 volt windings. Wired in series they accept 480 volts. Wired in parallel they accept 240 volts. The secondary has two 120 volt windings. Wired in series they give 240 volts, and with the middle tap they give two 120 volt legs. That is why one catalog number covers many jobs, a 480 volt panel feeding lighting and receptacles, or a 240 volt supply feeding a 120 volt control load.
The table shows full load current at every kVA size, computed from kVA times 1000 divided by the voltage.
| kVA | Primary amps at 480 V | Primary amps at 240 V | Secondary amps at 240 V |
|---|---|---|---|
| 3 | 6.2 A | 12.5 A | 12.5 A |
| 5 | 10.4 A | 20.8 A | 20.8 A |
| 10 | 20.8 A | 41.7 A | 41.7 A |
| 15 | 31.2 A | 62.5 A | 62.5 A |
| 25 | 52.1 A | 104.2 A | 104.2 A |
| 37.5 | 78.1 A | 156.2 A | 156.2 A |
| 50 | 104.2 A | 208.3 A | 208.3 A |
| 75 | 156.2 A | 312.5 A | 312.5 A |
| 100 | 208.3 A | 416.7 A | 416.7 A |
| 167 | 347.9 A | 695.8 A | 695.8 A |
Computed. Secondary current at 240 V equals the 240 V primary current because the ratio is one to one. Each 120 V half carries the same current at 120 V when loaded evenly across the center tap.
Public prices for 25 kVA, November 2026
These are asking prices from distributor and surplus listings read in November 2026. They are not our prices. 25 kVA is the most listed size, and the spread shows how much brand, stock position and delivery surcharges move the number.
| Unit | Condition | Price | Seller |
|---|---|---|---|
| Acme T2535183S, 240x480 to 120/240, NEMA 3R, copper | New | $2,123.90, one page shows call the nearest store | Elliott Electric |
| Hammond SG3N0025LE, 240x480 to 120/240 | New | $2,314.09 | Elliott Electric |
| Phoenix Phase Converters 25 kVA 240x480 to 120/240 | New | $2,471, page shows out of stock | Phoenix Phase Converters |
| Acme T2535183S | New | $4,257.01 | Riswll |
| Square D 25S1F, NEMA 3R, 115 C rise | New | $6,705.03 plus a $350 delivery surcharge | Zoro |
| General Electric 9T23B2671 | Used | $315 | Surplus Record listing |
Asking prices from the sources listed below. Freight, taxes and installation are extra.
Lead times
Stock units are the fast route, and Maddox says its in stock dry type units ship in 3 to 5 business days. Several of the listings above show out of stock or call for availability, so ask before you plan around a date. A factory order follows the dry type schedules in the 75 kVA page, 20 to 32 weeks for standard units in 2026.
Catalog numbers you will see
All of these are 25 kVA single phase with a 240x480 primary and a 120/240 secondary, taken from the listings cited on this page. The catalog numbers page lines up the same ratings across brands. Send us any of them and we quote the same rating.
- Acme T2535183S, 25 kVA, NEMA 3R wall mount, copper winding
- Hammond Sentinel G3 SG3N0025LE, 25 kVA, aluminum winding
- Square D EE25S3H and C25S3H, 25 kVA, 240x480 to 120/240
- Square D 25S1F, 25 kVA, NEMA 3R
- General Electric 9T23B2671 and 9T21B9106 on older surplus units
DOE efficiency now and from April 2029
Low voltage dry type transformers sold in the United States must meet DOE efficiency levels. For a single phase 25 kVA unit the level is 98.00 percent under the 2016 rule. For units made in or imported into the United States on or after April 23, 2029 it rises to 98.60 percent, measured at 35 percent load. Units built before the date can still be sold and installed after it.
Single phase or three phase
A single phase unit suits a load that is already single phase, such as a lighting panel, a small shop, a pump or control power. For a building panel with three phase loads use a three phase unit, such as the 45 kVA or 75 kVA 480 to 208Y/120 transformers on this site.
What to send for a quote
- kVA, from 3 to 167
- Primary voltage, 240x480 or other
- Secondary voltage, 120/240 or other
- Indoor NEMA 1 or outdoor NEMA 3R, ventilated or encapsulated
- Aluminum or copper windings
- New, new surplus or reconditioned, quantity and the delivery ZIP code
Common questions
What does 240x480 to 120/240 mean on a transformer
The primary can be wired for 240 or 480 volts and the secondary gives 120 volts on each leg and 240 volts across both, from one single phase unit.
How many amps is a 25 kVA single phase transformer
52.1 A on a 480 V primary, 104.2 A on a 240 V primary and 104.2 A on a 240 V secondary at full load.
How much does a 25 kVA single phase transformer cost
In November 2026 public listings put new units at about $2,100 to $6,700 and a used General Electric unit at $315. Freight is extra.
What changes for single phase transformers in 2029
Units made or imported on or after April 23, 2029 must reach 98.60 percent efficiency at 25 kVA, up from 98.00 percent under the 2016 rule.
Can a single phase dry type transformer go outside
Yes, in a NEMA 3R enclosure such as the Acme T2535183S or the Square D 25S1F. A ventilated NEMA 1 unit is for indoor use only.
Related pages
Sources
- Elliott Electric, Acme T2535183S
- Elliott Electric, Hammond SG3N0025LE
- Phoenix Phase Converters, 25 kVA 240x480 to 120/240
- Riswll, Acme T2535183S
- Zoro, Square D 25S1F 25 kVA NEMA 3R
- Surplus Record, General Electric 9T23B2671 25 kVA
- Surplus Record, Square D C25S3H 25 kVA
- Standard Electric Supply, Square D EE25S3H
- Maddox, Updated DOE 2029 energy efficiency standards for distribution transformers
- Rex Power Magnetics, DOE 2029 dry type transformer efficiency rules
- Maddox, Low voltage dry type transformers
Market figures are public asking prices and published industry figures, dated where the source gives a date. They are not our prices. A quote from us is a delivered price for a specific unit.