Home / Charts / Copper bus bar ampacity chart, by bar size and temperature rise
Copper bus bar ampacity chart, by bar size and temperature rise
A rectangular copper bus bar carries more current as it gets wider, thicker or is allowed to run hotter. The chart below gives the published ampacity of 68 standard sizes at 30, 50 and 65 C temperature rise, from 100 amps for a 1/16 by 1/2 inch bar to 7,500 amps for a 3/4 by 12 inch bar. To use it, find the amps you need in the column for your allowed rise, then read the bar size on that row. The values assume a bar run horizontally on edge, indoors at 40 C ambient.
Updated November 16, 2026
Thin bars, 1/16 to 3/16 inch thick
Thin bars suit control cabinets, small panels and short jumpers. Pick the column for the temperature rise your equipment allows. The 30 C column is the most conservative, and the 65 C column gives the highest current for the same bar.
| Bar size | Area sq in | Weight lb per ft | 30 C rise, amps | 50 C rise, amps | 65 C rise, amps | Amps per sq in at 50 C |
|---|---|---|---|---|---|---|
| 1/16 by 1/2 in | 0.031 | 0.12 | 103 | 136 | 157 | 4,359 |
| 1/16 by 3/4 in | 0.047 | 0.18 | 145 | 193 | 225 | 4,115 |
| 1/16 by 1 in | 0.062 | 0.24 | 187 | 250 | 285 | 4,000 |
| 1/16 by 1 1/2 in | 0.094 | 0.36 | 270 | 355 | 410 | 3,785 |
| 1/16 by 2 in | 0.125 | 0.48 | 345 | 460 | 530 | 3,680 |
| 1/8 by 1/2 in | 0.062 | 0.24 | 153 | 205 | 235 | 3,280 |
| 1/8 by 3/4 in | 0.094 | 0.36 | 215 | 285 | 325 | 3,038 |
| 1/8 by 1 in | 0.125 | 0.48 | 270 | 360 | 415 | 2,880 |
| 1/8 by 1 1/2 in | 0.188 | 0.73 | 385 | 510 | 590 | 2,713 |
| 1/8 by 2 in | 0.250 | 0.97 | 495 | 660 | 760 | 2,640 |
| 1/8 by 2 1/2 in | 0.312 | 1.21 | 600 | 800 | 920 | 2,564 |
| 1/8 by 3 in | 0.375 | 1.45 | 710 | 940 | 1,100 | 2,507 |
| 1/8 by 3 1/2 in | 0.438 | 1.69 | 810 | 1,100 | 1,250 | 2,511 |
| 1/8 by 4 in | 0.500 | 1.93 | 910 | 1,200 | 1,400 | 2,400 |
| 3/16 by 1/2 in | 0.094 | 0.36 | 195 | 260 | 300 | 2,772 |
| 3/16 by 3/4 in | 0.141 | 0.55 | 270 | 360 | 415 | 2,553 |
| 3/16 by 1 in | 0.188 | 0.73 | 340 | 455 | 520 | 2,420 |
| 3/16 by 1 1/2 in | 0.281 | 1.09 | 480 | 630 | 730 | 2,242 |
| 3/16 by 2 in | 0.375 | 1.45 | 610 | 810 | 940 | 2,160 |
| 3/16 by 2 1/2 in | 0.469 | 1.81 | 740 | 980 | 1,150 | 2,090 |
| 3/16 by 3 in | 0.562 | 2.17 | 870 | 1,150 | 1,350 | 2,046 |
| 3/16 by 3 1/2 in | 0.656 | 2.53 | 990 | 1,300 | 1,500 | 1,982 |
| 3/16 by 4 in | 0.750 | 2.90 | 1,100 | 1,450 | 1,700 | 1,933 |
Source values from the Copper Development Association, Table 1, copper busbar No. 110, 60 Hz, indoors at 40 C ambient, horizontal run on edge, no outside magnetic influence. Amps per square inch is computed here.
Quarter inch bars, the common switchgear size
A 1/4 inch bar in widths of 2 to 12 inches covers most switchboard and motor control center horizontal buses from about 700 to 4,900 amps.
| Bar size | Area sq in | Weight lb per ft | 30 C rise, amps | 50 C rise, amps | 65 C rise, amps | Amps per sq in at 50 C |
|---|---|---|---|---|---|---|
| 1/4 by 1/2 in | 0.125 | 0.48 | 240 | 315 | 360 | 2,520 |
| 1/4 by 3/4 in | 0.188 | 0.73 | 320 | 425 | 490 | 2,261 |
| 1/4 by 1 in | 0.250 | 0.97 | 400 | 530 | 620 | 2,120 |
| 1/4 by 1 1/2 in | 0.375 | 1.45 | 560 | 740 | 860 | 1,973 |
| 1/4 by 2 in | 0.500 | 1.93 | 710 | 940 | 1,100 | 1,880 |
| 1/4 by 2 1/2 in | 0.625 | 2.41 | 850 | 1,150 | 1,300 | 1,840 |
| 1/4 by 3 in | 0.750 | 2.90 | 990 | 1,300 | 1,550 | 1,733 |
| 1/4 by 3 1/2 in | 0.875 | 3.38 | 1,150 | 1,500 | 1,750 | 1,714 |
| 1/4 by 4 in | 1.000 | 3.86 | 1,250 | 1,700 | 1,950 | 1,700 |
| 1/4 by 5 in | 1.250 | 4.83 | 1,500 | 2,000 | 2,350 | 1,600 |
| 1/4 by 6 in | 1.500 | 5.80 | 1,750 | 2,350 | 2,700 | 1,567 |
| 1/4 by 8 in | 2.000 | 7.73 | 2,250 | 3,000 | 3,450 | 1,500 |
| 1/4 by 10 in | 2.500 | 9.66 | 2,700 | 3,600 | 4,200 | 1,440 |
| 1/4 by 12 in | 3.000 | 11.60 | 3,150 | 4,200 | 4,900 | 1,400 |
Source values from the Copper Development Association, Table 1, copper busbar No. 110, 60 Hz, indoors at 40 C ambient, horizontal run on edge, no outside magnetic influence. Amps per square inch is computed here.
Thick bars, 3/8 to 3/4 inch thick
Thick bars carry the largest currents in one piece, up to 7,500 amps at a 65 C rise. Notice that amps per square inch falls as the bar grows, because a thick bar has less surface for each square inch of copper to shed heat.
| Bar size | Area sq in | Weight lb per ft | 30 C rise, amps | 50 C rise, amps | 65 C rise, amps | Amps per sq in at 50 C |
|---|---|---|---|---|---|---|
| 3/8 by 3/4 in | 0.281 | 1.09 | 415 | 550 | 630 | 1,957 |
| 3/8 by 1 in | 0.375 | 1.45 | 510 | 680 | 790 | 1,813 |
| 3/8 by 1 1/2 in | 0.562 | 2.17 | 710 | 940 | 1,100 | 1,673 |
| 3/8 by 2 in | 0.750 | 2.90 | 880 | 1,150 | 1,350 | 1,533 |
| 3/8 by 2 1/2 in | 0.938 | 3.62 | 1,050 | 1,400 | 1,600 | 1,493 |
| 3/8 by 3 in | 1.120 | 4.35 | 1,200 | 1,600 | 1,850 | 1,429 |
| 3/8 by 3 1/2 in | 1.310 | 5.06 | 1,350 | 1,800 | 2,100 | 1,374 |
| 3/8 by 4 in | 1.500 | 5.80 | 1,500 | 2,000 | 2,350 | 1,333 |
| 3/8 by 5 in | 1.880 | 7.26 | 1,800 | 2,400 | 2,800 | 1,277 |
| 3/8 by 6 in | 2.250 | 8.69 | 2,100 | 2,800 | 3,250 | 1,244 |
| 3/8 by 8 in | 3.000 | 11.60 | 2,650 | 3,550 | 4,100 | 1,183 |
| 3/8 by 10 in | 3.750 | 14.50 | 3,200 | 4,300 | 4,900 | 1,147 |
| 3/8 by 12 in | 4.500 | 17.40 | 3,700 | 5,000 | 5,800 | 1,111 |
| 1/2 by 1 in | 0.500 | 1.93 | 620 | 820 | 940 | 1,640 |
| 1/2 by 1 1/2 in | 0.750 | 2.90 | 830 | 1,100 | 1,250 | 1,467 |
| 1/2 by 2 in | 1.000 | 3.86 | 1,000 | 1,350 | 1,550 | 1,350 |
| 1/2 by 2 1/2 in | 1.250 | 4.83 | 1,200 | 1,600 | 1,850 | 1,280 |
| 1/2 by 3 in | 1.500 | 5.80 | 1,400 | 1,850 | 2,150 | 1,233 |
| 1/2 by 3 1/2 in | 1.750 | 6.76 | 1,550 | 2,100 | 2,400 | 1,200 |
| 1/2 by 4 in | 2.000 | 7.73 | 1,700 | 2,300 | 2,650 | 1,150 |
| 1/2 by 5 in | 2.500 | 9.66 | 2,050 | 2,750 | 3,150 | 1,100 |
| 1/2 by 6 in | 3.000 | 11.60 | 2,400 | 3,150 | 3,650 | 1,050 |
| 1/2 by 8 in | 4.000 | 15.50 | 3,000 | 4,000 | 4,600 | 1,000 |
| 1/2 by 10 in | 5.000 | 19.30 | 3,600 | 4,800 | 5,500 | 960 |
| 1/2 by 12 in | 6.000 | 23.20 | 4,200 | 5,600 | 6,400 | 933 |
| 3/4 by 4 in | 3.000 | 11.60 | 2,050 | 2,750 | 3,150 | 917 |
| 3/4 by 5 in | 3.750 | 14.50 | 2,400 | 3,250 | 3,750 | 867 |
| 3/4 by 6 in | 4.500 | 17.40 | 2,800 | 3,750 | 4,300 | 833 |
| 3/4 by 8 in | 6.000 | 23.20 | 3,500 | 4,700 | 5,400 | 783 |
| 3/4 by 10 in | 7.500 | 29.00 | 4,200 | 5,600 | 6,500 | 747 |
| 3/4 by 12 in | 9.000 | 34.80 | 4,900 | 6,500 | 7,500 | 722 |
Source values from the Copper Development Association, Table 1, copper busbar No. 110, 60 Hz, indoors at 40 C ambient, horizontal run on edge, no outside magnetic influence. Amps per square inch is computed here.
What temperature rise and ambient mean
The three columns are the allowed rise of the bar above the surrounding air. A 30 C rise in a 40 C ambient means a bar at 70 C, a 50 C rise means 90 C and a 65 C rise means 105 C. Those are the three operating temperatures the Copper Development Association table lists skin effect ratios for. Lower rise runs cooler, protects joints and insulation, and leaves room for a hot enclosure. Higher rise gets more current out of the same copper.
The table is built on a surface emissivity of 0.4, which the Copper Development Association says was seen on bars exposed for 60 days in an industrial environment. A painted or bright new bar will behave differently, so check the emissivity table at the Copper Development Association before relying on a different finish.
Worked example, a bar for a 1000 kVA transformer at 480 volts
A 1000 kVA three phase transformer at 480 volts delivers 1,203 amps at full load (1000 times 1000 divided by 480 times the square root of 3). The bar must carry at least that. At a 50 C rise, a 1/4 by 2 inch bar is only good for 940 amps and a 1/4 by 3 inch bar for 1,300 amps, so 1/4 by 3 inch copper is the smallest bar in the table that clears 1,203 amps. At a 30 C rise you move up to 1/4 by 4 inch, which carries 1,250 amps. Run it through the kVA to amps calculator for any other size or voltage.
How the chart is used with a pad mount transformer
The bus chart sits on the secondary side. The transformer nameplate gives the secondary full load amps, the bar in the switchgear or the transformer secondary compartment must carry at least that continuously, and the main breaker is selected to match. Primary side current is much smaller, which is why the primary bushings and cable look so different from the secondary bus.
Common questions
How many amps will a 1/4 by 2 inch copper bus bar carry
The Copper Development Association table gives 710 amps at a 30 C rise, 940 amps at a 50 C rise and 1,100 amps at a 65 C rise for a 1/4 by 2 inch bar run on edge indoors at 40 C ambient.
What size copper bus bar is needed for 1000 amps
At a 50 C rise a 1/4 by 2 1/2 inch bar carries 1,150 amps and a 3/8 by 2 inch bar carries 1,150 amps. At a 30 C rise a 1/4 by 3 1/2 inch bar carries 1,150 amps. Always pick from the column for the rise you can accept.
What does temperature rise mean for a bus bar
It is how many degrees Celsius the bar runs above the surrounding air. The chart columns are 30, 50 and 65 C rise, which in a 40 C ambient means a bar at 70, 90 or 105 C.
Does a bus bar carry the same current flat as on edge
No. The table values are for a bar mounted horizontally on edge. Mounting position and bars run close together change how well it sheds heat, so use the manufacturer data for other layouts.
Why does amps per square inch drop on bigger bars
Heat leaves through the surface. Surface grows more slowly than cross section as a bar gets thicker, so a big bar carries less current per square inch of copper than a thin one.
Related pages
Sources
- Copper Development Association, Table 1 ampacities of copper No. 110 busbars
- Copper Development Association, Table 3 quick busbar selector
- Copper Development Association, Table 4 effect of emissivity
Free to cite with a link to this page. Always check the edition of the code your inspector enforces.