Copper bus bar ampacity chart, by bar size and temperature rise

A rectangular copper bus bar carries more current as it gets wider, thicker or is allowed to run hotter. The chart below gives the published ampacity of 68 standard sizes at 30, 50 and 65 C temperature rise, from 100 amps for a 1/16 by 1/2 inch bar to 7,500 amps for a 3/4 by 12 inch bar. To use it, find the amps you need in the column for your allowed rise, then read the bar size on that row. The values assume a bar run horizontally on edge, indoors at 40 C ambient.

Updated November 16, 2026

Thin bars, 1/16 to 3/16 inch thick

Thin bars suit control cabinets, small panels and short jumpers. Pick the column for the temperature rise your equipment allows. The 30 C column is the most conservative, and the 65 C column gives the highest current for the same bar.

Bar sizeArea sq inWeight lb per ft30 C rise, amps50 C rise, amps65 C rise, ampsAmps per sq in at 50 C
1/16 by 1/2 in0.0310.121031361574,359
1/16 by 3/4 in0.0470.181451932254,115
1/16 by 1 in0.0620.241872502854,000
1/16 by 1 1/2 in0.0940.362703554103,785
1/16 by 2 in0.1250.483454605303,680
1/8 by 1/2 in0.0620.241532052353,280
1/8 by 3/4 in0.0940.362152853253,038
1/8 by 1 in0.1250.482703604152,880
1/8 by 1 1/2 in0.1880.733855105902,713
1/8 by 2 in0.2500.974956607602,640
1/8 by 2 1/2 in0.3121.216008009202,564
1/8 by 3 in0.3751.457109401,1002,507
1/8 by 3 1/2 in0.4381.698101,1001,2502,511
1/8 by 4 in0.5001.939101,2001,4002,400
3/16 by 1/2 in0.0940.361952603002,772
3/16 by 3/4 in0.1410.552703604152,553
3/16 by 1 in0.1880.733404555202,420
3/16 by 1 1/2 in0.2811.094806307302,242
3/16 by 2 in0.3751.456108109402,160
3/16 by 2 1/2 in0.4691.817409801,1502,090
3/16 by 3 in0.5622.178701,1501,3502,046
3/16 by 3 1/2 in0.6562.539901,3001,5001,982
3/16 by 4 in0.7502.901,1001,4501,7001,933

Source values from the Copper Development Association, Table 1, copper busbar No. 110, 60 Hz, indoors at 40 C ambient, horizontal run on edge, no outside magnetic influence. Amps per square inch is computed here.

Quarter inch bars, the common switchgear size

A 1/4 inch bar in widths of 2 to 12 inches covers most switchboard and motor control center horizontal buses from about 700 to 4,900 amps.

Bar sizeArea sq inWeight lb per ft30 C rise, amps50 C rise, amps65 C rise, ampsAmps per sq in at 50 C
1/4 by 1/2 in0.1250.482403153602,520
1/4 by 3/4 in0.1880.733204254902,261
1/4 by 1 in0.2500.974005306202,120
1/4 by 1 1/2 in0.3751.455607408601,973
1/4 by 2 in0.5001.937109401,1001,880
1/4 by 2 1/2 in0.6252.418501,1501,3001,840
1/4 by 3 in0.7502.909901,3001,5501,733
1/4 by 3 1/2 in0.8753.381,1501,5001,7501,714
1/4 by 4 in1.0003.861,2501,7001,9501,700
1/4 by 5 in1.2504.831,5002,0002,3501,600
1/4 by 6 in1.5005.801,7502,3502,7001,567
1/4 by 8 in2.0007.732,2503,0003,4501,500
1/4 by 10 in2.5009.662,7003,6004,2001,440
1/4 by 12 in3.00011.603,1504,2004,9001,400

Source values from the Copper Development Association, Table 1, copper busbar No. 110, 60 Hz, indoors at 40 C ambient, horizontal run on edge, no outside magnetic influence. Amps per square inch is computed here.

Thick bars, 3/8 to 3/4 inch thick

Thick bars carry the largest currents in one piece, up to 7,500 amps at a 65 C rise. Notice that amps per square inch falls as the bar grows, because a thick bar has less surface for each square inch of copper to shed heat.

Bar sizeArea sq inWeight lb per ft30 C rise, amps50 C rise, amps65 C rise, ampsAmps per sq in at 50 C
3/8 by 3/4 in0.2811.094155506301,957
3/8 by 1 in0.3751.455106807901,813
3/8 by 1 1/2 in0.5622.177109401,1001,673
3/8 by 2 in0.7502.908801,1501,3501,533
3/8 by 2 1/2 in0.9383.621,0501,4001,6001,493
3/8 by 3 in1.1204.351,2001,6001,8501,429
3/8 by 3 1/2 in1.3105.061,3501,8002,1001,374
3/8 by 4 in1.5005.801,5002,0002,3501,333
3/8 by 5 in1.8807.261,8002,4002,8001,277
3/8 by 6 in2.2508.692,1002,8003,2501,244
3/8 by 8 in3.00011.602,6503,5504,1001,183
3/8 by 10 in3.75014.503,2004,3004,9001,147
3/8 by 12 in4.50017.403,7005,0005,8001,111
1/2 by 1 in0.5001.936208209401,640
1/2 by 1 1/2 in0.7502.908301,1001,2501,467
1/2 by 2 in1.0003.861,0001,3501,5501,350
1/2 by 2 1/2 in1.2504.831,2001,6001,8501,280
1/2 by 3 in1.5005.801,4001,8502,1501,233
1/2 by 3 1/2 in1.7506.761,5502,1002,4001,200
1/2 by 4 in2.0007.731,7002,3002,6501,150
1/2 by 5 in2.5009.662,0502,7503,1501,100
1/2 by 6 in3.00011.602,4003,1503,6501,050
1/2 by 8 in4.00015.503,0004,0004,6001,000
1/2 by 10 in5.00019.303,6004,8005,500960
1/2 by 12 in6.00023.204,2005,6006,400933
3/4 by 4 in3.00011.602,0502,7503,150917
3/4 by 5 in3.75014.502,4003,2503,750867
3/4 by 6 in4.50017.402,8003,7504,300833
3/4 by 8 in6.00023.203,5004,7005,400783
3/4 by 10 in7.50029.004,2005,6006,500747
3/4 by 12 in9.00034.804,9006,5007,500722

Source values from the Copper Development Association, Table 1, copper busbar No. 110, 60 Hz, indoors at 40 C ambient, horizontal run on edge, no outside magnetic influence. Amps per square inch is computed here.

What temperature rise and ambient mean

The three columns are the allowed rise of the bar above the surrounding air. A 30 C rise in a 40 C ambient means a bar at 70 C, a 50 C rise means 90 C and a 65 C rise means 105 C. Those are the three operating temperatures the Copper Development Association table lists skin effect ratios for. Lower rise runs cooler, protects joints and insulation, and leaves room for a hot enclosure. Higher rise gets more current out of the same copper.

The table is built on a surface emissivity of 0.4, which the Copper Development Association says was seen on bars exposed for 60 days in an industrial environment. A painted or bright new bar will behave differently, so check the emissivity table at the Copper Development Association before relying on a different finish.

Worked example, a bar for a 1000 kVA transformer at 480 volts

A 1000 kVA three phase transformer at 480 volts delivers 1,203 amps at full load (1000 times 1000 divided by 480 times the square root of 3). The bar must carry at least that. At a 50 C rise, a 1/4 by 2 inch bar is only good for 940 amps and a 1/4 by 3 inch bar for 1,300 amps, so 1/4 by 3 inch copper is the smallest bar in the table that clears 1,203 amps. At a 30 C rise you move up to 1/4 by 4 inch, which carries 1,250 amps. Run it through the kVA to amps calculator for any other size or voltage.

How the chart is used with a pad mount transformer

The bus chart sits on the secondary side. The transformer nameplate gives the secondary full load amps, the bar in the switchgear or the transformer secondary compartment must carry at least that continuously, and the main breaker is selected to match. Primary side current is much smaller, which is why the primary bushings and cable look so different from the secondary bus.

Common questions

How many amps will a 1/4 by 2 inch copper bus bar carry

The Copper Development Association table gives 710 amps at a 30 C rise, 940 amps at a 50 C rise and 1,100 amps at a 65 C rise for a 1/4 by 2 inch bar run on edge indoors at 40 C ambient.

What size copper bus bar is needed for 1000 amps

At a 50 C rise a 1/4 by 2 1/2 inch bar carries 1,150 amps and a 3/8 by 2 inch bar carries 1,150 amps. At a 30 C rise a 1/4 by 3 1/2 inch bar carries 1,150 amps. Always pick from the column for the rise you can accept.

What does temperature rise mean for a bus bar

It is how many degrees Celsius the bar runs above the surrounding air. The chart columns are 30, 50 and 65 C rise, which in a 40 C ambient means a bar at 70, 90 or 105 C.

Does a bus bar carry the same current flat as on edge

No. The table values are for a bar mounted horizontally on edge. Mounting position and bars run close together change how well it sheds heat, so use the manufacturer data for other layouts.

Why does amps per square inch drop on bigger bars

Heat leaves through the surface. Surface grows more slowly than cross section as a bar gets thicker, so a big bar carries less current per square inch of copper than a thin one.

Related pages

Sources

Free to cite with a link to this page. Always check the edition of the code your inspector enforces.

More charts

Wire ampacity chart from NEC Table 310.16
NEC Table 310.16 ampacities for copper and aluminum at 60, 75 and 90°C from 14 AWG to 2000 kcmil, with the terminal rule, small conductor limits and derating factors.
NEMA enclosure ratings chart
What NEMA Types 1, 3R, 4, 4X, 12 and the rest protect against, side by side, with the IP codes three published charts give for each and why they disagree.
Motor full load amps chart
Three phase motor full load amps from 1/2 to 500 HP at 115, 200, 208, 230, 460, 575 and 2300 V from NEC Table 430.250, single phase from 430.248, with wire, breaker and kVA by HP.
What size wire for every amp rating, 15 to 4000 amps
Wire size by amps from 15 to 400 A in copper and aluminum, the dwelling service sizes under NEC 310.12, and parallel sets for 400 to 4000 A services, with a calculator.
Primary distribution voltages, 4.16 kV to 34.5 kV
Every standard US primary voltage from 2.4 kV to 69 kV with its phase to ground value, wye or delta, insulation class and BIL, and what 12470Y/7200 on a nameplate means.
Commercial electrical service sizes, amps, kVA and transformer
Standard commercial service sizes from 100 to 4000 amps at 208Y/120 and 480Y/277 volts, the kVA each one carries, the transformer that feeds it, and when ground fault protection applies.
Breaker size chart, every standard breaker rating and its wire size
Every standard breaker size in NEC 240.6(A) from 10 to 6000 amps, the matching copper and aluminum wire size at 60 and 75°C, the 125 percent continuous load rule and common appliance circuits.
Transformer fuse size chart, primary full load amps by kVA and voltage
Primary full load amps for 25 to 2500 kVA three phase transformers at 4.16 to 34.5 kV, the NEC 450.3(B) 125 and 250 percent limits worked out at 480 V, and how pad mount fuses are chosen.
Electrical service size chart, how many kW is a 200 amp service
kVA and kW for 60 to 1200 amp electrical services on single phase 240 volt and three phase 208, 240 and 480 volt systems, with 80 percent loading columns and the formula behind every figure.
Grounding electrode conductor size chart from NEC Table 250.66
NEC Table 250.66 grounding electrode conductor sizes in copper and aluminum, the 6 AWG rod rule and 4 AWG concrete encased rule, and the ground wire size for 100, 200, 400, 600, 800 and 1200 amp services.
How many acres does 1 MW of solar need
A utility scale solar farm needs about 5 to 10 acres per MWac. Fixed tilt averages 7.6 acres and single axis tracking 8.7 acres, with a table from 1 to 500 MW, panel counts and step up transformers.
Generator kVA to kW and amps chart
Generator kVA to kW and full load amps for 10 to 3,000 kVA at 120/240, 208, 240, 480, 600, 2,400 and 4,160 volts, computed at 0.8 power factor, with kW to kVA at other power factors.
Service wire size chart
Service entrance wire size for 100, 125, 150, 200, 225, 320, 400 and larger services in copper and aluminum, with the NEC 310.12 dwelling rule, parallel sets to 2000 amps, ground wire and the transformer behind the service.