Shunt Trip Breaker, How It Works and Where It Is Used

A shunt trip is a breaker accessory that opens the breaker when control voltage is applied to a coil. A normal breaker trips on its own from overcurrent. A shunt trip breaker can also be tripped on purpose by a remote signal, such as a fire alarm or an emergency stop.

Updated November 18, 2026

How it works

Control voltage applied across the shunt release terminals sends current through the coil. The coil makes a magnetic field and a plunger trips the breaker mechanism. The breaker still trips on overcurrent in the usual way. The shunt coil adds a second, deliberate way to open it.

Shunt trip against undervoltage release

The two work in opposite ways.

Shunt tripUndervoltage release
Trips whenVoltage is applied to the coilVoltage is lost or drops
Loss of control powerDoes not normally trip the breakerTrips the breaker
Needs power to stay closedNoYes, continuously

Drop out levels for undervoltage releases vary by device. One Eaton leaflet cites 35 to 60 percent of rated voltage, so check the data sheet.

Coil voltage

Sources say shunt trip coils are commonly 120 V AC or 24 V DC. The coil voltage must match the control circuit, and the wrong voltage can damage the coil. Confirm the voltage and trip current on the breaker data sheet and the controller submittal.

Where you see them

Shunt trips are used for emergency power off, fire alarm and suppression interlocks and elevator disconnects. Code rules differ by use and edition. One source says NEC 620.51 covers the elevator disconnecting means and leaves the shunt trip requirement to ASME A17.1 and the local authority. Ask the inspector before you wire one.

Sizing the breaker

The shunt coil does not change the breaker's current rating. Size the breaker from the load current as usual, and use the kVA to amps calculator when the load is fed from a transformer secondary.

Related pages

Common questions

What is a shunt trip breaker

A breaker with a coil that trips it open when control voltage is applied, in addition to its normal overcurrent trip.

What voltage is a shunt trip coil

Common coil voltages are 120 V AC and 24 V DC. Match the coil to the control circuit.

Is a shunt trip the same as an undervoltage release

No. A shunt trip opens when voltage is applied. An undervoltage release opens when voltage is lost.