Home / Guides / NEMA 6-20, 6-30 and 6-50 Receptacles Explained
NEMA 6-20, 6-30 and 6-50 Receptacles Explained
NEMA 6 devices are 250 volt, two pole, three wire grounding receptacles with two hot terminals and a ground and no neutral. The 6-15, 6-20, 6-30 and 6-50 differ only in current rating. They are used on 240 volt circuits and also on 208 volt circuits, so the same receptacle shows up on a split phase house and a three phase commercial building. The 6-50 is the one most people search for because it charges an electric vehicle at the same 32 or 40 amp maximum as a 14-50 and is common for welders.
Updated November 17, 2026
The 6 series at a glance
The table gives ratings from the NEMA list and the wire pairing from NEC Table 310.16 copper values in the 60 degree C column, which is the safe choice for NM-B cable. Continuous limits are 80 percent and the power figures are computed at 240 volts.
| Receptacle | Rating | Copper wire | Breaker | Continuous limit | Power at limit, 240 V | Typical use |
|---|---|---|---|---|---|---|
| 6-15 | 15 A, 250 V | 14 AWG | 15 A | 12 A | 2.88 kW | Small 240 V equipment, some window air conditioners |
| 6-20 | 20 A, 250 V | 12 AWG | 20 A | 16 A | 3.84 kW | Large room air conditioners, hotel and commercial equipment |
| 6-30 | 30 A, 250 V | 10 AWG | 30 A | 24 A | 5.76 kW | Welders, shop tools, generators |
| 6-50 | 50 A, 250 V | 6 AWG | 50 A | 40 A | 9.60 kW | Welders, farm equipment, EV charging |
Wire sizes follow NEC Table 310.16 at 60 degrees C and the guidance of Electrical Technology for the 6-15 and 6-50. The 6-20 and 6-30 pairings come from the ampacity table, so confirm with the receptacle label and your inspector.
Why a 6-50 has no neutral
A 6-50 supplies 240 volts only, hot to hot, with a ground. Nothing on the circuit runs at 120 volts, so there is nothing for a neutral to carry. That makes the cable cheaper, a 6/2 with ground instead of 6/3, and it is why a 6-50 cannot run a range or dryer that needs 120 volts for its controls. A 14-50 adds the neutral for those loads. Electrical Technology states that a 6-50R is incompatible with devices that need a 120 volt neutral connection.
Common uses
Wikipedia lists large room air conditioners and commercial kitchen equipment for the non locking 6 series, and notes the occasional home arc welder uses a 6-50. Single phase 6-50 is common on farms for silo unloaders with a 6 gauge flexible cord up to 200 feet. Electrical Technology adds plasma cutters, ovens, heaters and generators. For heavier work the locking L6-30 and direct wiring are more common than the 6-30, see the locking plug guide.
6-50 for EV charging
The 6-50 charges an EV at the same 32 or 40 amp maximum as the 14-50 on a short cord, and the 14-50 neutral is not used by any EV charging today, per Wikipedia. Many chargers and the ChargePoint Home Flex style units list a 6-50 plug option. On 208 volt supplies the power is lower, 40 amps at 208 volts is 8.32 kW instead of 9.6 kW. Wiring is a 2 pole 50 amp breaker, 6 AWG copper and a dedicated circuit. The GFCI question is the same as for the 14-50, so see that guide.
| Current | At 240 V | At 208 V |
|---|---|---|
| 32 A | 7.68 kW | 6.66 kW |
| 40 A | 9.60 kW | 8.32 kW |
Computed as amps times volts.
208 volt or 240 volt
NEMA 6 devices are rated 250 volts maximum and are used on either. The Wikipedia entry notes that the 6-20R or 6-30R in a hotel room is typically fed from two phases of a three phase 208 volt system, while a house uses 240 volt split phase. Equipment on a 6 series plug is designed for the range. The service transformer decides which voltage the building gets, see the 480V to 208V transformer page.
6-50 vs 14-50
Charging speed is identical because EVs do not use the neutral. The 6-50 needs a cheaper 3 conductor cable and a smaller receptacle. The 14-50 is the better choice if the circuit may later feed an RV, a range or a dryer, or if you want the plug that most portable chargers ship with. See the NEMA 14-50 guide.
Related pages
Common questions
What breaker for a NEMA 6-50
A 2 pole 50 amp breaker on a dedicated circuit, wired with 6 AWG copper.
Does a NEMA 6-50 need a neutral
No. It has two hots and a ground only, 250 volts, so a 6/2 with ground cable is used.
What is a NEMA 6-20 used for
240 volt 20 amp loads such as large room air conditioners and commercial equipment, and it is found in hotel rooms on 208 or 240 volts.
What is the difference between 6-20 and 6-30
The 6-20 is rated 20 amps for 12 AWG circuits and the 6-30 is rated 30 amps for 10 AWG circuits. The plugs have different blade shapes and do not interchange.
Can I charge an EV on a 6-50
Yes, at the same 32 or 40 amp maximum as a 14-50 on a short cord.
Can a 6-50 run a welder
Yes. Welders are one of the standard uses, and sources list plasma cutters and arc welders for the 6-50.
Is a 6-50 120 volt
No. It supplies 240 volts, or 208 volts on a three phase supply, and has no 120 volt connection.
Sources
- Wikipedia, NEMA connector
- Electrical Technology, how to wire a NEMA 6-50 receptacle
- Emporia Energy, NEMA 14-50 outlet safety for EV owners
- NEC Table 310.16 values as shown on our wire ampacity chart
Free to cite with a link to this page. Work out current at any rating with the kVA to amps calculator.