NEMA plug and receptacle chart

A NEMA plug name has three parts. A series number sets the voltage and wiring, a second number sets the amps, and a final R or P says receptacle or plug. A 14-50R is a 125/250 volt, 50 amp, four wire receptacle. An L6-30P is a 250 volt, 30 amp locking plug. The charts below list every series, the amp ratings made in each, the continuous load limit and where each one shows up. Each common configuration links to its own guide.

Updated November 17, 2026

How to read a NEMA name

An optional L means locking, the numbers before the hyphen encode the poles, wires, voltage and phase, the numbers after the hyphen give the amp rating, and R or P marks the receptacle or plug. In the standard ANSI/NEMA WD 6, the blades are named G for ground, W for the grounded neutral and X, Y and Z for the hot conductors.

A connector with a ground has more wires than poles, so the 5-15 is two pole, three wire. NEMA also has special families outside the pattern, the ML midget locking, TT for travel trailers, SS for ship to shore and FSL for military and aircraft.

Which series fits which voltage and wiring

This is the part of the name that matters most, because a plug cannot be inserted into the wrong voltage class by design. The table is the NEMA class matrix. Grounded versions are listed under grounded, and non grounded versions are obsolete in new work, except the 1-15 in old buildings and the 10-30 and 10-50 for old dryers and ranges.

WiringSupply voltageNon grounding seriesGrounding series
Hot and neutral120 V15
Hot and neutral277 V37
Hot and hot208 or 240 V26
Hot and hot480 Vnone8
Hot, hot and neutral120/240 or 120/208 V1014
Three hot208 or 240 V1115

Straight blade chart, amp ratings made in each series

Ratings are from the NEMA receptacle chart. The continuous column is 80 percent of the rating, the NEC limit for a load running three hours or more, which the chart shows in brackets.

SeriesVoltagePoles and wiresRatings made, ampsCommonly used
1125 V2 pole, 2 wire, no ground15, 20, 301-15 only, in pre 1960s buildings
5125 V2 pole, 3 wire grounding15, 20, 30, 505-15 and 5-20 are the standard outlets
6250 V2 pole, 3 wire grounding15, 20, 30, 506-20 and 6-50, A C, welders, EV
7277 V2 pole, 3 wire grounding15, 20, 30, 50Commercial lighting
10125/250 V3 pole, 3 wire, no ground20, 30, 50Old dryers and ranges, 10-30 and 10-50
113 phase 250 V3 pole, 3 wire, no ground15, 20, 30, 50Rare
14125/250 V3 pole, 4 wire grounding15, 20, 30, 50, 6014-30 dryers, 14-50 ranges, RVs and EV
153 phase 250 V3 pole, 4 wire grounding15, 20, 30, 50, 60Three phase equipment
183 phase 120/208Y4 pole, 4 wire, no ground15, 20, 30, 50, 60Obsolete, limited availability

Continuous load by amp rating

The same 80 percent rule applies to every device, and power depends on the voltage. The table is computed. For a three phase device multiply by 1.732.

RatingContinuous ampskW at 120 VkW at 240 VCopper wire at 60 CBreaker
15 A12 A1.442.8814 AWG15 A
20 A16 A1.923.8412 AWG20 A
30 A24 A2.885.7610 AWG30 A
50 A40 A4.809.606 AWG50 A
60 A48 A5.7611.526 AWG60 A

Continuous amps are 80 percent of the rating. Wire is the NEC Table 310.16 60 degree C copper column, with 6 AWG used at 50 and 60 amps as the sources recommend. Voltage drop and ambient correction can require a larger wire.

Locking chart, L5 to L22

Locking series follow the same class numbers. Ratings and uses are from the NEMA list and the sources named below.

SeriesVoltagePoles and wiresAmps named in sourcesWhere it is found
L5125 V2 pole, 3 wire15, 30Marinas, RV shore power
L6250 V2 pole, 3 wire20, 30L6-20 server PDUs, L6-30 welders
L7277 V2 pole, 3 wiresee maker catalogIndustrial lighting
L14125/250 V3 pole, 4 wire30Backup generators, audio racks
L153 phase 250 V3 pole, 4 wire30Three phase equipment
L163 phase 480 V3 pole, 4 wiresee maker catalogThree phase equipment
L213 phase 120/208Y4 pole, 5 wire20, 30Live event power
L223 phase 277/480Y4 pole, 5 wire20, 30Three phase wye loads

See the locking plug guide for detail. Amp ratings listed are only those the sources name, other sizes exist in most series.

Which receptacle takes which plug

A 5-20R takes both a 5-15P and a 5-20P because of its T shaped neutral slot, and the same is true of the 6-20R taking 6-15P and 6-20P plugs. Nothing else is cross compatible. A locking plug does not fit a straight blade receptacle even at the same rating, and the 14-30 and 14-50 neutral blades are different shapes so they do not mate.

Three phase and 208 vs 240 volt equipment

The series number tells you whether a device is meant for 208 or 240 volts. NEMA 6 and 14 devices are rated 250 volts and work on 208 or 240, which means the same receptacle works on a three phase wye building and a split phase house, but the power at 208 volts is about 13 percent lower. Three phase 208 volt devices with a neutral use L21, and the 480Y/277 volt equivalent is L22. The transformer behind the service sets the voltage, see the transformer voltage pages.

Not the same as NEMA enclosure ratings

NEMA also rates enclosures with numbers such as 1, 3R and 4X. That is a separate standard for dust and water protection, not a plug configuration. See the NEMA enclosure ratings chart for those.

Common questions

What does NEMA stand for

National Electrical Manufacturers Association. It writes the standard ANSI/NEMA WD 6 that defines the plug and receptacle shapes.

What does the L in a NEMA plug name mean

Locking. L devices have curved blades that twist and lock into the receptacle.

What is the most common NEMA plug

The 5-15P, a 125 volt, 15 amp, two pole, three wire grounding plug, and the 5-15R receptacle in the wall.

What NEMA plug is used for a 30 amp 240 volt dryer

A 14-30. Older dryers use the 10-30, which has no ground and is now deprecated.

What NEMA plug is used for a 50 amp range or EV charger

A 14-50 for the four wire version with a neutral, or a 6-50 for 240 volt only equipment such as welders and EV chargers.

What does R and P mean on a NEMA name

R is the receptacle, the outlet. P is the plug.

Which NEMA plugs are three phase

The 11, 15 and 18 straight blade series, and locking L15, L16, L17, L18, L21 and L22.

Related pages

Sources

Free to cite with a link to this page. Always check the edition of the code your inspector enforces.

More charts

Wire ampacity chart from NEC Table 310.16
NEC Table 310.16 ampacities for copper and aluminum at 60, 75 and 90°C from 14 AWG to 2000 kcmil, with the terminal rule, small conductor limits and derating factors.
NEMA enclosure ratings chart
What NEMA Types 1, 3R, 4, 4X, 12 and the rest protect against, side by side, with the IP codes three published charts give for each and why they disagree.
Motor full load amps chart
Three phase motor full load amps from 1/2 to 500 HP at 115, 200, 208, 230, 460, 575 and 2300 V from NEC Table 430.250, single phase from 430.248, with wire, breaker and kVA by HP.
What size wire for every amp rating, 15 to 4000 amps
Wire size by amps from 15 to 400 A in copper and aluminum, the dwelling service sizes under NEC 310.12, and parallel sets for 400 to 4000 A services, with a calculator.
Primary distribution voltages, 4.16 kV to 34.5 kV
Every standard US primary voltage from 2.4 kV to 69 kV with its phase to ground value, wye or delta, insulation class and BIL, and what 12470Y/7200 on a nameplate means.
Commercial electrical service sizes, amps, kVA and transformer
Standard commercial service sizes from 100 to 4000 amps at 208Y/120 and 480Y/277 volts, the kVA each one carries, the transformer that feeds it, and when ground fault protection applies.
Breaker size chart, every standard breaker rating and its wire size
Every standard breaker size in NEC 240.6(A) from 10 to 6000 amps, the matching copper and aluminum wire size at 60 and 75°C, the 125 percent continuous load rule and common appliance circuits.
Transformer fuse size chart, primary full load amps by kVA and voltage
Primary full load amps for 25 to 2500 kVA three phase transformers at 4.16 to 34.5 kV, the NEC 450.3(B) 125 and 250 percent limits worked out at 480 V, and how pad mount fuses are chosen.
Copper bus bar ampacity chart, by bar size and temperature rise
Ampacity of 68 standard rectangular copper bus bar sizes from 1/16 by 1/2 inch to 3/4 by 12 inch at 30, 50 and 65 C rise, with area, weight and how to pick a bar for a transformer secondary.
Electrical service size chart, how many kW is a 200 amp service
kVA and kW for 60 to 1200 amp electrical services on single phase 240 volt and three phase 208, 240 and 480 volt systems, with 80 percent loading columns and the formula behind every figure.
Grounding electrode conductor size chart from NEC Table 250.66
NEC Table 250.66 grounding electrode conductor sizes in copper and aluminum, the 6 AWG rod rule and 4 AWG concrete encased rule, and the ground wire size for 100, 200, 400, 600, 800 and 1200 amp services.
How many acres does 1 MW of solar need
A utility scale solar farm needs about 5 to 10 acres per MWac. Fixed tilt averages 7.6 acres and single axis tracking 8.7 acres, with a table from 1 to 500 MW, panel counts and step up transformers.
Generator kVA to kW and amps chart
Generator kVA to kW and full load amps for 10 to 3,000 kVA at 120/240, 208, 240, 480, 600, 2,400 and 4,160 volts, computed at 0.8 power factor, with kW to kVA at other power factors.
Service wire size chart
Service entrance wire size for 100, 125, 150, 200, 225, 320, 400 and larger services in copper and aluminum, with the NEC 310.12 dwelling rule, parallel sets to 2000 amps, ground wire and the transformer behind the service.
AWG wire gauge chart with diameter, mm2, kcmil and resistance
American wire gauge chart from 4/0 to 40 AWG with diameter in inches and mm, area in mm2 and kcmil, and copper resistance, plus a kcmil to mm2 table from 250 to 2000 kcmil.
CallGet a quote