NEMA Locking Plugs L5, L6, L14 and L21 Twist Lock Chart
NEMA locking plugs start with an L and use curved blades that twist and lock, so they cannot be pulled out by accident. The number after the L gives the voltage and wiring, and the number after the hyphen gives the amps, so an L5-30P is a 125 volt, 30 amp locking plug and an L14-30P is a 125/250 volt, 30 amp, four wire plug. The L21 and L22 series carry three phase power with a neutral and tie to the secondary of the transformer behind the building. This guide gives each series in one table, the uses the sources name and the matching transformer voltage.
Updated November 17, 2026
How locking designations work
A NEMA connector name has an optional L for locking, the class number, a hyphen, the amp rating and R for receptacle or P for plug. The class number encodes the number of poles and wires, the voltage and whether the supply is single or three phase. A device with a ground has more wires than poles. A locking device with the same electrical rating as a straight blade one is not physically compatible with it, so L5-15 does not fit a 5-15 outlet.
Locking connector chart
Ratings and wiring below are from the NEMA connector list, grouped by class. The uses column is what the sources say the class is found on, not a code requirement.
| Series | Voltage | Poles and wires | Supply it fits | Where it is found |
|---|---|---|---|---|
| L5 | 125 V | 2 pole, 3 wire grounding | 120 V single phase | Marinas, RV shore power, L5-30R receptacles |
| L6 | 250 V | 2 pole, 3 wire grounding, no neutral | 208 or 240 V | L6-20 in server rack PDUs, L6-30 on welders and machinery |
| L7 | 277 V | 2 pole, 3 wire grounding | 277 V from a 480Y/277 system | Commercial and industrial lighting |
| L14 | 125/250 V | 3 pole, 4 wire grounding | 120/240 V split phase | Household backup generators, audio amplifier racks |
| L15 | 250 V | 3 pole, 4 wire grounding | 240 V three phase | Three phase equipment |
| L16 | 480 V | 3 pole, 4 wire grounding | 480 V three phase | Three phase equipment |
| L17 | 600 V | 3 pole, 4 wire grounding | 600 V three phase | Three phase equipment |
| L21 | 120/208 V | 4 pole, 5 wire grounding | 208Y/120 three phase with neutral | Live event power distribution, 20 and 30 amp |
| L22 | 277/480 V | 4 pole, 5 wire grounding | 480Y/277 three phase with neutral | Three phase wye loads, 20 and 30 amp |
Single phase locking plugs, L5, L6 and L14
The L5-30 is the plug on most RV shore power cords on the RV end, and Wikipedia notes RVs are equipped for 120 volt 30 amp or 240 volt 50 amp service. The L6-20 is the common server room choice, and it carries no neutral. The L6-30 is common on welders and manufacturing machinery.The L14 carries both 120 and 240 volts, with a neutral. It is common on household backup generators, and a generator inlet or transfer switch with an L14-30 is the usual setup. The wire for each follows the amp rating, 12 AWG copper for a 20 amp device and 10 AWG copper for a 30 amp device, based on NEC Table 310.16 at 60 degrees C. For the 50 and 60 amp sizes see the NEMA 14-50 guide.
Three phase locking plugs, L15, L16, L21 and L22
L15, L16 and L17 are three phase with no neutral, rated 250, 480 and 600 volts. L21 and L22 add a neutral and a ground, so they run both line to line and line to neutral loads. The L21 for 208Y/120 volt systems and the L22 for 480Y/277 volt systems are the ones that show up on generators, temporary power and portable distribution. The older L18 is a four pole device with no ground and is considered obsolete in favor of L21 at 20 and 30 amps.
Which locking plug matches which transformer secondary
The plug has to match the voltage the transformer delivers, because the voltage class is built into the blade layout. The table pairs the common transformer secondaries with the locking series that fits them.
| Transformer secondary | Matching series |
|---|---|
| 120/240 V single phase | L5 for 120 V, L6 for 240 V, L14 for both |
| 208Y/120 V three phase | L21 with neutral, L15 without a neutral, L6 for two phases only |
| 240 V delta three phase | L15 |
| 480Y/277 V three phase | L22 with neutral, L16 for 480 V without neutral, L7 for 277 V single phase |
| 600 V three phase | L17 |
Series voltage ratings from the NEMA connector list. Always confirm that the receptacle is rated for the supply voltage.
Why twist lock for generators and temporary power
Locking plugs stay seated under vibration and cable pull, which is why generators, portable power and stage gear use them. A 50 amp straight blade 5-50 exists, but Wikipedia notes twist locking plugs are generally used for high current. Check the transfer switch and generator labels, as many portable generators ship with an L14-30 or an L5-30 outlet, and match the cord. See the transfer switch and meter collar guide for the whole setup.
Related pages
Common questions
What is an L5-30P
A 30 amp, 125 volt locking plug with two poles and a ground. It is common for RV shore power cords and marina pedestals.
What is the difference between L6-30 and L14-30
The L6-30 is 250 volts, two hots and a ground with no neutral. The L14-30 is 125/250 volts with two hots, a neutral and a ground.
What is an L21-30 used for
A 30 amp, 120/208 volt three phase plug with a neutral and a ground, used for live event power distribution and temporary power on 208Y/120 volt systems.
Does an L14-30 need a neutral
Yes. It is a three pole, four wire device with two hots, a neutral and a ground, which is why it works for generators feeding both 120 and 240 volt loads.
Will an L5-15 plug fit a 5-15 outlet
No. A locking device is not physically compatible with a straight blade one even when the electrical rating is the same.
What is an L6-20 used for
A 20 amp, 250 volt locking plug common in server room power distribution units for servers, backup systems and UPS equipment.
What is the L in NEMA plug names
L means locking, a curved blade twist lock device.
Sources
- Wikipedia, NEMA connector
- Signal and Power, NEMA connector guide
- Interpower, NEMA nomenclature guide
- NEC Table 310.16 values as shown on our wire ampacity chart
Free to cite with a link to this page. Work out current at any rating with the kVA to amps calculator.