NEMA Locking Plugs L5, L6, L14 and L21 Twist Lock Chart

NEMA locking plugs start with an L and use curved blades that twist and lock, so they cannot be pulled out by accident. The number after the L gives the voltage and wiring, and the number after the hyphen gives the amps, so an L5-30P is a 125 volt, 30 amp locking plug and an L14-30P is a 125/250 volt, 30 amp, four wire plug. The L21 and L22 series carry three phase power with a neutral and tie to the secondary of the transformer behind the building. This guide gives each series in one table, the uses the sources name and the matching transformer voltage.

Updated November 17, 2026

How locking designations work

A NEMA connector name has an optional L for locking, the class number, a hyphen, the amp rating and R for receptacle or P for plug. The class number encodes the number of poles and wires, the voltage and whether the supply is single or three phase. A device with a ground has more wires than poles. A locking device with the same electrical rating as a straight blade one is not physically compatible with it, so L5-15 does not fit a 5-15 outlet.

Locking connector chart

Ratings and wiring below are from the NEMA connector list, grouped by class. The uses column is what the sources say the class is found on, not a code requirement.

SeriesVoltagePoles and wiresSupply it fitsWhere it is found
L5125 V2 pole, 3 wire grounding120 V single phaseMarinas, RV shore power, L5-30R receptacles
L6250 V2 pole, 3 wire grounding, no neutral208 or 240 VL6-20 in server rack PDUs, L6-30 on welders and machinery
L7277 V2 pole, 3 wire grounding277 V from a 480Y/277 systemCommercial and industrial lighting
L14125/250 V3 pole, 4 wire grounding120/240 V split phaseHousehold backup generators, audio amplifier racks
L15250 V3 pole, 4 wire grounding240 V three phaseThree phase equipment
L16480 V3 pole, 4 wire grounding480 V three phaseThree phase equipment
L17600 V3 pole, 4 wire grounding600 V three phaseThree phase equipment
L21120/208 V4 pole, 5 wire grounding208Y/120 three phase with neutralLive event power distribution, 20 and 30 amp
L22277/480 V4 pole, 5 wire grounding480Y/277 three phase with neutralThree phase wye loads, 20 and 30 amp

Single phase locking plugs, L5, L6 and L14

The L5-30 is the plug on most RV shore power cords on the RV end, and Wikipedia notes RVs are equipped for 120 volt 30 amp or 240 volt 50 amp service. The L6-20 is the common server room choice, and it carries no neutral. The L6-30 is common on welders and manufacturing machinery.The L14 carries both 120 and 240 volts, with a neutral. It is common on household backup generators, and a generator inlet or transfer switch with an L14-30 is the usual setup. The wire for each follows the amp rating, 12 AWG copper for a 20 amp device and 10 AWG copper for a 30 amp device, based on NEC Table 310.16 at 60 degrees C. For the 50 and 60 amp sizes see the NEMA 14-50 guide.

Three phase locking plugs, L15, L16, L21 and L22

L15, L16 and L17 are three phase with no neutral, rated 250, 480 and 600 volts. L21 and L22 add a neutral and a ground, so they run both line to line and line to neutral loads. The L21 for 208Y/120 volt systems and the L22 for 480Y/277 volt systems are the ones that show up on generators, temporary power and portable distribution. The older L18 is a four pole device with no ground and is considered obsolete in favor of L21 at 20 and 30 amps.

Which locking plug matches which transformer secondary

The plug has to match the voltage the transformer delivers, because the voltage class is built into the blade layout. The table pairs the common transformer secondaries with the locking series that fits them.

Transformer secondaryMatching series
120/240 V single phaseL5 for 120 V, L6 for 240 V, L14 for both
208Y/120 V three phaseL21 with neutral, L15 without a neutral, L6 for two phases only
240 V delta three phaseL15
480Y/277 V three phaseL22 with neutral, L16 for 480 V without neutral, L7 for 277 V single phase
600 V three phaseL17

Series voltage ratings from the NEMA connector list. Always confirm that the receptacle is rated for the supply voltage.

Why twist lock for generators and temporary power

Locking plugs stay seated under vibration and cable pull, which is why generators, portable power and stage gear use them. A 50 amp straight blade 5-50 exists, but Wikipedia notes twist locking plugs are generally used for high current. Check the transfer switch and generator labels, as many portable generators ship with an L14-30 or an L5-30 outlet, and match the cord. See the transfer switch and meter collar guide for the whole setup.

Related pages

Common questions

What is an L5-30P

A 30 amp, 125 volt locking plug with two poles and a ground. It is common for RV shore power cords and marina pedestals.

What is the difference between L6-30 and L14-30

The L6-30 is 250 volts, two hots and a ground with no neutral. The L14-30 is 125/250 volts with two hots, a neutral and a ground.

What is an L21-30 used for

A 30 amp, 120/208 volt three phase plug with a neutral and a ground, used for live event power distribution and temporary power on 208Y/120 volt systems.

Does an L14-30 need a neutral

Yes. It is a three pole, four wire device with two hots, a neutral and a ground, which is why it works for generators feeding both 120 and 240 volt loads.

Will an L5-15 plug fit a 5-15 outlet

No. A locking device is not physically compatible with a straight blade one even when the electrical rating is the same.

What is an L6-20 used for

A 20 amp, 250 volt locking plug common in server room power distribution units for servers, backup systems and UPS equipment.

What is the L in NEMA plug names

L means locking, a curved blade twist lock device.