What Is a Recloser and Why Your Lights Blink Before an Outage

A recloser is a circuit breaker with a control that trips on a fault and then closes again automatically, a preset number of times, to clear temporary faults or isolate a permanent one. That is why your lights blink. The line tripped, the recloser tested it, and either the fault was gone or the recloser locked out. The number of reclose attempts is limited to four by recloser standards.

Updated November 15, 2026

What a recloser does

Many faults on overhead lines are brief, such as a branch touching a wire. A recloser opens to stop the fault current, waits a moment, and closes to see if the fault has cleared. If it has, power returns after a short blink. If not, it repeats up to its set number of operations and then locks out, and stays open until a crew resets it. SEL describes a recloser as a circuit breaker paired with a recloser control.

Why the lights blink, step by step

Each time the recloser opens, everything past it loses power. Each close restores it. So a flicker followed by normal power is one successful reclose, and several blinks and then darkness is a recloser running through its sequence and locking out. A relay manual describes up to four selectable reclosures prior to lockout, and after the last one, if the fault persists, the scheme does not close the breaker again.

Fast and slow curves

Reclosers usually offer two kinds of trip, a nearly instantaneous fast curve and a time delay curve, according to SEL. In a fuse saving scheme the first trips use the fast curve so the recloser clears a temporary fault before the downstream fuse begins to melt. Later trips use the slow curve, which is slower than the fuse clearing time, so on a permanent fault the fuse blows and isolates only its own branch. A trip saving scheme uses the delay curve for every trip.

Recloser compared with a breaker, sectionalizer and fuse

The devices differ by whether they can interrupt fault current and whether they close again.

DeviceInterrupts fault currentRecloses on its own
RecloserYesYes, a set number of times
Substation circuit breakerYesYes, when paired with a reclosing relay
SectionalizerNo, it needs an upstream deviceNo, it counts operations and opens while the line is dead
FuseYes, onceNo, the link must be replaced

Roles from SEL. A sectionalizer isolates a faulted segment after an upstream breaker or recloser has interrupted the fault.

Where reclosers sit

They are found at the substation and out on the line, on poles or on pad mounted bases, protecting a feeder or a branch. A recloser on a branch means only that branch loses power for a permanent fault. Transformers on the line are protected by their own fuses downstream. See our transformer fuse size chart for how those are sized.

What to do when your power keeps blinking

One or two blinks is normal. If it keeps happening, note the times and report it to your utility, which can see recloser operations on the feeder. Never approach a downed or sagging wire. Treat every line as live and call the utility or emergency services.

Related pages

Common questions

What is a recloser in simple terms

A circuit breaker that closes itself again after tripping, a few times, to clear temporary faults before locking out.

Why do my lights flicker and then come back on

A recloser or reclosing breaker tripped on a fault, tested the line, and found it clear.

How many times will a recloser try

Standards limit the attempts to four before it locks out.

What is the difference between a recloser and a fuse

A fuse melts once and must be replaced. A recloser resets itself.

What is the difference between a recloser and a sectionalizer

A sectionalizer cannot interrupt fault current and relies on an upstream recloser or breaker.

Sources