Home / Charts / Transformer fuse size chart, primary full load amps by kVA and voltage
Transformer fuse size chart, primary full load amps by kVA and voltage
A transformer fuse is picked from the primary full load amps, then adjusted for inrush, coordination and the code. The full load amps come first, so the tables below compute them for every common kVA and primary voltage. The NEC limits for transformers rated 1000 volts and under are worked out as well. Utility fuse links and Bay-O-Net cartridge ratings come from the manufacturer application tables for the exact unit, so we do not print a made up link size for each kVA.
Updated November 15, 2026
Primary full load amps, three phase, 25 to 2500 kVA
Full load amps equal kVA times 1000 divided by the square root of 3 times line to line volts. Values are in amps, rounded, for a three phase transformer at the line to line primary voltage shown. Nothing here is a fuse rating. It is the current the fuse must carry all day.
| kVA | 4.16 kV | 12.47 kV | 13.2 kV | 13.8 kV | 24.94 kV | 34.5 kV |
|---|---|---|---|---|---|---|
| 25 | 3.5 | 1.2 | 1.1 | 1.0 | 0.6 | 0.4 |
| 37.5 | 5.2 | 1.7 | 1.6 | 1.6 | 0.9 | 0.6 |
| 45 | 6.2 | 2.1 | 2.0 | 1.9 | 1.0 | 0.8 |
| 50 | 6.9 | 2.3 | 2.2 | 2.1 | 1.2 | 0.8 |
| 75 | 10.4 | 3.5 | 3.3 | 3.1 | 1.7 | 1.3 |
| 100 | 13.9 | 4.6 | 4.4 | 4.2 | 2.3 | 1.7 |
| 112.5 | 15.6 | 5.2 | 4.9 | 4.7 | 2.6 | 1.9 |
| 150 | 20.8 | 6.9 | 6.6 | 6.3 | 3.5 | 2.5 |
| 167 | 23.2 | 7.7 | 7.3 | 7.0 | 3.9 | 2.8 |
| 225 | 31.2 | 10.4 | 9.8 | 9.4 | 5.2 | 3.8 |
| 300 | 41.6 | 13.9 | 13.1 | 12.6 | 6.9 | 5.0 |
| 500 | 69.4 | 23.1 | 21.9 | 20.9 | 11.6 | 8.4 |
| 750 | 104 | 34.7 | 32.8 | 31.4 | 17.4 | 12.6 |
| 1000 | 139 | 46.3 | 43.7 | 41.8 | 23.1 | 16.7 |
| 1500 | 208 | 69.4 | 65.6 | 62.8 | 34.7 | 25.1 |
| 2000 | 278 | 92.6 | 87.5 | 83.7 | 46.3 | 33.5 |
| 2500 | 347 | 116 | 109 | 105 | 57.9 | 41.8 |
Computed from kVA and voltage. Use the kVA to amps calculator for any other voltage.
Single phase full load amps on common line to ground voltages
Single phase pole and pad mount units are fed line to ground, so the amps are kVA divided by the winding voltage in kilovolts. Typical single phase primary ratings on a 4.16Y, 12.47Y, 13.2Y, 24.94Y and 34.5Y system are 2.4, 7.2, 7.62, 14.4 and 19.92 kV line to ground. The 12.47 kV and 24.94 kV systems have 7.2 and 14.4 kV line to ground values, which matches our primary distribution voltages chart.
| kVA | 2.4 kV | 7.2 kV | 7.62 kV | 14.4 kV | 19.92 kV |
|---|---|---|---|---|---|
| 10 | 4.2 | 1.4 | 1.3 | 0.7 | 0.5 |
| 15 | 6.2 | 2.1 | 2.0 | 1.0 | 0.8 |
| 25 | 10.4 | 3.5 | 3.3 | 1.7 | 1.3 |
| 37.5 | 15.6 | 5.2 | 4.9 | 2.6 | 1.9 |
| 50 | 20.8 | 6.9 | 6.6 | 3.5 | 2.5 |
| 75 | 31.2 | 10.4 | 9.8 | 5.2 | 3.8 |
| 100 | 41.7 | 13.9 | 13.1 | 6.9 | 5.0 |
| 167 | 69.6 | 23.2 | 21.9 | 11.6 | 8.4 |
Computed. A 25 kVA unit on 7.2 kV draws only 3.5 amps, which is why small fuse links are used.
Why the fuse is bigger than full load amps
A fuse sized at exactly full load would open on the first energizing, because a transformer draws a brief inrush current many times its rating. A fuse also has to carry the load that follows an outage, when everything starts at once. So the link is chosen above full load and below the point where the transformer is no longer protected. Manufacturer tables, such as Eaton application tables for Bay-O-Net fuses and S and C selection guides, give the actual cartridge or link for each kVA and voltage, and the utility standard decides which one it uses.
NEC 450.3(B) limits for transformers rated 1000 volts or less
For a transformer with a primary of 1000 volts or less, NEC Table 450.3(B) caps the primary protection at 125 percent of primary full load amps when the current is 9 amps or more, and the next standard size up is permitted. For primary current under 9 amps the cap is 167 percent. When the secondary also has protection, set at not more than 125 percent of secondary current, the primary device can go up to 250 percent. Sources disagree on whether the next size up is allowed at 250 percent, so confirm it in the code text.
The table below works this out for a 480 volt three phase primary, which is the usual case for a dry type unit inside a plant.
| kVA | Primary FLA at 480 V | 125 percent | 250 percent with secondary protection |
|---|---|---|---|
| 15 | 18.0 | 22.6 | 45.1 |
| 30 | 36.1 | 45.1 | 90.2 |
| 45 | 54.1 | 67.7 | 135 |
| 75 | 90.2 | 113 | 226 |
| 112.5 | 135 | 169 | 338 |
| 150 | 180 | 226 | 451 |
| 225 | 271 | 338 | 677 |
| 300 | 361 | 451 | 902 |
| 500 | 601 | 752 | 1504 |
| 750 | 902 | 1128 | 2255 |
| 1000 | 1203 | 1504 | 3007 |
Computed from kVA. The code allows the next standard fuse or breaker size above the 125 percent figure. Check the edition adopted where you work.
Transformers with primaries over 1000 volts
Most pad mount transformers have primaries of 4 to 35 kV, so they fall under the separate over 1000 volt table, now Table 450.3(A) in the 2020 and later code. The allowed percentage depends on the impedance of the transformer and on whether the location is supervised by qualified people. We found the published summaries of that table disagree on the exact percentages for supervised locations, so we do not print them here. Read the table in the NEC edition your jurisdiction has adopted. Utility owned transformers follow the utility standard and are not inspected under the NEC at all.
Bay-O-Net and current limiting fuses in a pad mount
Many pad mount transformers carry a Bay-O-Net expulsion fuse in the oil, in series with a partial range current limiting fuse. The expulsion fuse handles ordinary overloads and low current faults, and the current limiting fuse clears high current faults inside the tank. The pairing is picked from the manufacturer coordination table for the unit kVA and voltage, so use the table in the transformer data sheet or ask the maker.
Pole fuse cutouts
On a pole, a fuse cutout holds a replaceable fuse link in a hinged tube. When the link melts the tube drops open, which is why a linesman can see at a glance which transformer has failed. Sizing is by the same logic as above, full load amps first, then the utility standard for the link.
Worked example, 500 kVA at 12.47 kV
From the first table a 500 kVA three phase unit on a 12.47 kV primary draws 23.1 amps. On the 480 volt side of the same unit, full load is 601 amps. Use the primary 23.1 amps to look up the fuse in the manufacturer table, and the secondary 601 amps to pick the main breaker and the conductors.
Common questions
What size fuse for a 500 kVA transformer
Start from the full load amps, 23.1 amps at 12.47 kV or 601 amps at 480 V on a three phase unit. The exact fuse comes from the manufacturer application table or the utility standard, because inrush and coordination decide it.
How do you calculate transformer primary full load amps
Multiply kVA by 1000 and divide by the square root of 3 times the line to line volts for three phase, or divide kVA by the volts in kilovolts for single phase.
What is the NEC rule for transformer fuse size under 1000 volts
Table 450.3(B) allows 125 percent of primary full load amps for currents of 9 amps or more, or 250 percent on the primary when the secondary also has protection set at no more than 125 percent.
What is a Bay-O-Net fuse
An expulsion fuse mounted in the oil of a pad mount transformer, usually backed by a current limiting fuse for high fault currents.
Why does a transformer fuse blow when it is turned on
Inrush current. A transformer draws a brief surge many times its rating on energizing, so the fuse must be sized above full load amps to ride through it.
Related pages
Sources
- EC and M, NEC guidelines for transformer and transformer feeder protection
- Eaton Bussmann, transformer protection
- ExpertCE, transformer overcurrent protection sizing fuses
- EE Power, transformer overcurrent protection
Free to cite with a link to this page. Always check the edition of the code your inspector enforces.