10 MVA transformer, amps, price benchmarks and lead time

A 10 MVA transformer is 10,000 kVA, the size where a large pad mounted unit, a unit substation transformer and a small substation power transformer overlap. This page gives the full load amps, public price benchmarks and lead times, and what we need to quote one.

Updated November 18, 2026

10 MVA full load amps by voltage

Full load current for a three phase transformer is MVA times 1,000,000 divided by the square root of 3 times the line voltage. The figures below are computed that way for each winding voltage.

Winding voltageFull load amps at 10 MVA
4.16 kV1,388
12.47 kV463
13.8 kV418
24.94 kV231
34.5 kV167
69 kV84
115 kV50
138 kV42

Computed, rounded to the nearest amp. 10 MVA is 10,000 kVA and 10,000 kVA is the same unit.

Price benchmarks

Power transformer prices are quoted per unit and move with steel, copper and the order book. These are published benchmarks, not our prices.

Benchmark for 10 MVAFigurePublished by
Mid 2019 price for 1 to 25 MVA units at $30,000 to $40,000 per MVA$300,000 to $400,000Electrical Trader, multiplied by 10
That range raised by the 91.4 percent producer price index move from January 2020 to July 2026$574,000 to $766,000Computed from Electrical Trader and NextMSC
Overseas factory price quoted ex works on a manufacturer blog$70,000 to $120,000Manufacturer blog, excludes freight, tariff, US testing and delivery

An index of producer prices is not a quote. The overseas figure excludes ocean freight, the Section 232 tariff, US standard testing and delivery.

Lead time

Electrical Trader reports medium power transformers, 10 to 50 MVA, at 52 to 78 weeks. Wood Mackenzie put the average for all power transformers at 128 weeks in the second quarter of 2025, which is why 10 MVA buyers also look at surplus and reconditioned units, see the used power transformers page.

Choices that change the price and size

Two 10 MVA transformers can differ a lot. The nameplate items below are the ones that change cost and footprint.

  • Voltage class, for example 34.5 kV to 13.8 kV or 69 kV to 13.8 kV.
  • Cooling, self cooled ONAN alone, or a stacked rating with fans, for example 10/12.5 MVA. Check which MVA the percent impedance is stated on.
  • Tap changer, de energized taps or an on load tap changer.
  • Percent impedance, which sets the fault current downstream and matters if the unit must parallel another one.
  • Pad mounted or substation style, and the oil type.

Weight and dimensions

We did not find a public source we trust for one weight per 10 MVA transformer, because it moves with voltage class, impedance, cooling and maker. For a sense of scale, one published catalog sheet for an 8 to 10 MVA, 13.8 kV delta to 6.9 kV wye power transformer lists an outline of 4,300 mm long, 3,700 mm wide and 4,000 mm high, and says exact values are supplied on order confirmation. Ask for the outline drawing with any quote, it gives shipping weight, oil volume and pad size.

What to send for a quote

  • Primary and secondary voltage and winding connection
  • Cooling and stacked rating if you need one
  • Percent impedance and any paralleling requirement
  • Tap changer type and range
  • New, surplus, used or reconditioned
  • Site ZIP code and the date you need it energized

Common questions

How many amps does a 10 MVA transformer draw

At full load it is about 167 amps at 34.5 kV, 418 amps at 13.8 kV and 84 amps at 69 kV, computed from MVA times 1,000,000 divided by the square root of 3 times the line voltage.

Is a 10 MVA transformer the same as 10,000 kVA

Yes. One MVA is 1,000 kVA, so 10 MVA is 10,000 kVA.

How much does a 10 MVA transformer cost

Electrical Trader gave $30,000 to $40,000 per MVA for 1 to 25 MVA units in mid 2019, which is $300,000 to $400,000 for 10 MVA, and the producer price index for power and distribution transformers has risen 91.4 percent since January 2020. Real quotes depend on voltage, impedance, cooling and delivery.

How long is the lead time for a 10 MVA transformer

Electrical Trader reports 52 to 78 weeks for medium power units from 10 to 50 MVA. Surplus and reconditioned units can ship sooner.