Home / Products / Substation transformers / 10 MVA transformer, amps, price benchmarks and lead time
10 MVA transformer, amps, price benchmarks and lead time
A 10 MVA transformer is 10,000 kVA, the size where a large pad mounted unit, a unit substation transformer and a small substation power transformer overlap. This page gives the full load amps, public price benchmarks and lead times, and what we need to quote one.
Updated November 18, 2026
10 MVA full load amps by voltage
Full load current for a three phase transformer is MVA times 1,000,000 divided by the square root of 3 times the line voltage. The figures below are computed that way for each winding voltage.
| Winding voltage | Full load amps at 10 MVA |
|---|---|
| 4.16 kV | 1,388 |
| 12.47 kV | 463 |
| 13.8 kV | 418 |
| 24.94 kV | 231 |
| 34.5 kV | 167 |
| 69 kV | 84 |
| 115 kV | 50 |
| 138 kV | 42 |
Computed, rounded to the nearest amp. 10 MVA is 10,000 kVA and 10,000 kVA is the same unit.
Price benchmarks
Power transformer prices are quoted per unit and move with steel, copper and the order book. These are published benchmarks, not our prices.
| Benchmark for 10 MVA | Figure | Published by |
|---|---|---|
| Mid 2019 price for 1 to 25 MVA units at $30,000 to $40,000 per MVA | $300,000 to $400,000 | Electrical Trader, multiplied by 10 |
| That range raised by the 91.4 percent producer price index move from January 2020 to July 2026 | $574,000 to $766,000 | Computed from Electrical Trader and NextMSC |
| Overseas factory price quoted ex works on a manufacturer blog | $70,000 to $120,000 | Manufacturer blog, excludes freight, tariff, US testing and delivery |
An index of producer prices is not a quote. The overseas figure excludes ocean freight, the Section 232 tariff, US standard testing and delivery.
Lead time
Electrical Trader reports medium power transformers, 10 to 50 MVA, at 52 to 78 weeks. Wood Mackenzie put the average for all power transformers at 128 weeks in the second quarter of 2025, which is why 10 MVA buyers also look at surplus and reconditioned units, see the used power transformers page.
Choices that change the price and size
Two 10 MVA transformers can differ a lot. The nameplate items below are the ones that change cost and footprint.
- Voltage class, for example 34.5 kV to 13.8 kV or 69 kV to 13.8 kV.
- Cooling, self cooled ONAN alone, or a stacked rating with fans, for example 10/12.5 MVA. Check which MVA the percent impedance is stated on.
- Tap changer, de energized taps or an on load tap changer.
- Percent impedance, which sets the fault current downstream and matters if the unit must parallel another one.
- Pad mounted or substation style, and the oil type.
Weight and dimensions
We did not find a public source we trust for one weight per 10 MVA transformer, because it moves with voltage class, impedance, cooling and maker. For a sense of scale, one published catalog sheet for an 8 to 10 MVA, 13.8 kV delta to 6.9 kV wye power transformer lists an outline of 4,300 mm long, 3,700 mm wide and 4,000 mm high, and says exact values are supplied on order confirmation. Ask for the outline drawing with any quote, it gives shipping weight, oil volume and pad size.
What to send for a quote
- Primary and secondary voltage and winding connection
- Cooling and stacked rating if you need one
- Percent impedance and any paralleling requirement
- Tap changer type and range
- New, surplus, used or reconditioned
- Site ZIP code and the date you need it energized
Common questions
How many amps does a 10 MVA transformer draw
At full load it is about 167 amps at 34.5 kV, 418 amps at 13.8 kV and 84 amps at 69 kV, computed from MVA times 1,000,000 divided by the square root of 3 times the line voltage.
Is a 10 MVA transformer the same as 10,000 kVA
Yes. One MVA is 1,000 kVA, so 10 MVA is 10,000 kVA.
How much does a 10 MVA transformer cost
Electrical Trader gave $30,000 to $40,000 per MVA for 1 to 25 MVA units in mid 2019, which is $300,000 to $400,000 for 10 MVA, and the producer price index for power and distribution transformers has risen 91.4 percent since January 2020. Real quotes depend on voltage, impedance, cooling and delivery.
How long is the lead time for a 10 MVA transformer
Electrical Trader reports 52 to 78 weeks for medium power units from 10 to 50 MVA. Surplus and reconditioned units can ship sooner.
Related pages
Sources
- Electrical Trader, power transformers
- NextMSC, US transformer and switchgear prices and lead times 2026
- Wood Mackenzie, tackling supply chain challenges in the electric T and D sector
- HC Transformer, 8 to 10 MVA 13800 6900 V power transformer catalog
Market figures are public asking prices and published industry figures, dated where the source gives a date. They are not our prices. A quote from us is a delivered price for a specific unit.