Power factor correction multiplier table
Multiply your kW by the number where the present power factor row meets the target column to get the kVAR of capacitors.
| Present PF | To 0.90 | To 0.95 | To 0.98 | To 1.00 |
|---|---|---|---|---|
| 0.60 | 0.849 | 1.005 | 1.130 | 1.333 |
| 0.65 | 0.685 | 0.840 | 0.966 | 1.169 |
| 0.70 | 0.536 | 0.692 | 0.817 | 1.020 |
| 0.75 | 0.398 | 0.553 | 0.679 | 0.882 |
| 0.80 | 0.266 | 0.421 | 0.547 | 0.750 |
| 0.85 | 0.135 | 0.291 | 0.417 | 0.620 |
| 0.90 | 0.000 | 0.156 | 0.281 | 0.484 |
Free to cite with a link to this page. Multiplier = tan(arccos present PF) minus tan(arccos target PF), computed.
How much transformer capacity it frees
A 500 kW load at different power factors needs this much kVA from the transformer. Correcting to 0.95 gives back the difference, so an existing pad mount can often carry more real load before it needs replacing.
| Present PF | kVA drawn | kVA at 0.95 | kVA freed | kVAR to add |
|---|---|---|---|---|
| 0.70 | 714 | 526 | 188 | 346 |
| 0.75 | 667 | 526 | 140 | 277 |
| 0.80 | 625 | 526 | 99 | 211 |
| 0.85 | 588 | 526 | 62 | 146 |
| 0.90 | 556 | 526 | 29 | 78 |
Computed for a 500 kW load. Compare the kVA drawn with the nameplate on the sizes in the transformer sizing calculator.
Fixed banks, switched banks and harmonics
A fixed bank suits a steady load such as a motor that runs all day. A switched bank follows a changing load so the plant does not overcorrect. Where variable frequency drives, rectifiers or arc loads create harmonics, a capacitor can resonate with the system inductance, so detuned reactors or a filter are common. Overcorrecting into a leading power factor can also raise voltage at light load.
Related tools. The kVA to kW calculator converts using power factor, the kVA to amps calculator gives full load current, and the glossary defines the terms. For a bigger transformer, request a quote.
Common questions
How do you calculate power factor
Divide real power in kW by apparent power in kVA. A load of 400 kW and 500 kVA has a power factor of 0.8. From amps, power factor is kW x 1000 / (1.732 x volts x amps) on a three phase system.
How many kVAR do I need to correct power factor
Multiply kW by the difference between tan(arccos present PF) and tan(arccos target PF). Going from 0.78 to 0.95 on 200 kW takes 200 x (0.802 minus 0.329) = 94.6 kVAR, so you would pick the next standard bank size.
What is a good power factor
Close to 1 is best. Many utilities bill a penalty or a demand charge below a threshold, so check your own tariff for the number. The calculator lets you test any target.
Does correcting power factor reduce a transformer load
Yes. A transformer carries kVA, and capacitors at the load cut the reactive part, so kVA falls toward kW. That frees capacity without a bigger unit, as the table below shows.
Is kVA the same as kW
Only at a power factor of 1. kW equals kVA times power factor. Use the kVA to kW calculator for the conversion.
What are the risks of adding capacitors
Capacitors can resonate with the system at a harmonic frequency when there are drives or other nonlinear loads. A harmonic study or detuned reactors may be needed before adding fixed banks.
Sources
- The correction formula, kVAR = kW x (tan(arccos PF1) minus tan(arccos PF2)), is the power triangle result. Sources that give it include the Eaton power factor correction guide for the plant engineer and the Eskom power factor sizing guide.
- Every multiplier and kVA value on this page is computed from that formula.
- Utility penalty thresholds vary by tariff and are not listed here. Read your own rate schedule.