Enter kW, the power factor you have and the power factor you want, and get the capacitor kVAR to add, the kVA you free on the transformer and the capacitor current and microfarads.

Updated November 16, 2026

Capacitors needed94.7 kVAR
Apparent power before256.4 kVA
Apparent power after210.5 kVA
kVA freed45.9 kVA
Capacitor current, three phase113.9 A
Capacitance per phase if delta connected364 uF

Power factor correction multiplier table

Multiply your kW by the number where the present power factor row meets the target column to get the kVAR of capacitors.

Present PFTo 0.90To 0.95To 0.98To 1.00
0.600.8491.0051.1301.333
0.650.6850.8400.9661.169
0.700.5360.6920.8171.020
0.750.3980.5530.6790.882
0.800.2660.4210.5470.750
0.850.1350.2910.4170.620
0.900.0000.1560.2810.484

Free to cite with a link to this page. Multiplier = tan(arccos present PF) minus tan(arccos target PF), computed.

How much transformer capacity it frees

A 500 kW load at different power factors needs this much kVA from the transformer. Correcting to 0.95 gives back the difference, so an existing pad mount can often carry more real load before it needs replacing.

Present PFkVA drawnkVA at 0.95kVA freedkVAR to add
0.70714526188346
0.75667526140277
0.8062552699211
0.8558852662146
0.905565262978

Computed for a 500 kW load. Compare the kVA drawn with the nameplate on the sizes in the transformer sizing calculator.

Fixed banks, switched banks and harmonics

A fixed bank suits a steady load such as a motor that runs all day. A switched bank follows a changing load so the plant does not overcorrect. Where variable frequency drives, rectifiers or arc loads create harmonics, a capacitor can resonate with the system inductance, so detuned reactors or a filter are common. Overcorrecting into a leading power factor can also raise voltage at light load.

Related tools. The kVA to kW calculator converts using power factor, the kVA to amps calculator gives full load current, and the glossary defines the terms. For a bigger transformer, request a quote.

Put this calculator on your site

Free for contractors, electricians, schools and trade sites. Paste this code into any page.

Common questions

How do you calculate power factor

Divide real power in kW by apparent power in kVA. A load of 400 kW and 500 kVA has a power factor of 0.8. From amps, power factor is kW x 1000 / (1.732 x volts x amps) on a three phase system.

How many kVAR do I need to correct power factor

Multiply kW by the difference between tan(arccos present PF) and tan(arccos target PF). Going from 0.78 to 0.95 on 200 kW takes 200 x (0.802 minus 0.329) = 94.6 kVAR, so you would pick the next standard bank size.

What is a good power factor

Close to 1 is best. Many utilities bill a penalty or a demand charge below a threshold, so check your own tariff for the number. The calculator lets you test any target.

Does correcting power factor reduce a transformer load

Yes. A transformer carries kVA, and capacitors at the load cut the reactive part, so kVA falls toward kW. That frees capacity without a bigger unit, as the table below shows.

Is kVA the same as kW

Only at a power factor of 1. kW equals kVA times power factor. Use the kVA to kW calculator for the conversion.

What are the risks of adding capacitors

Capacitors can resonate with the system at a harmonic frequency when there are drives or other nonlinear loads. A harmonic study or detuned reactors may be needed before adding fixed banks.

Sources

  • The correction formula, kVAR = kW x (tan(arccos PF1) minus tan(arccos PF2)), is the power triangle result. Sources that give it include the Eaton power factor correction guide for the plant engineer and the Eskom power factor sizing guide.
  • Every multiplier and kVA value on this page is computed from that formula.
  • Utility penalty thresholds vary by tariff and are not listed here. Read your own rate schedule.