PUE is total facility power divided by IT power. A site drawing 1,500 kW with 1,000 kW of servers has a PUE of 1.50 and pays for 500 kW of overhead. Enter your two readings to get PUE, DCiE and what each 0.1 of PUE costs a year.
Updated November 18, 2026
Formulas
PUE equals total facility power divided by IT equipment power. DCiE equals IT power divided by total facility power. Overhead power equals facility power minus IT power. Annual overhead energy equals IT kW times PUE minus one, times 8,760 hours.
Annual cost of each 0.1 of PUE
This table is computed at $0.07 per kWh, an example rate. Multiply by your own rate divided by 0.07 to adjust.
| IT load kW | kWh per year for 0.1 PUE | Cost per year |
|---|---|---|
| 500 | 438,000 | $30,660 |
| 1,000 | 876,000 | $61,320 |
| 5,000 | 4,380,000 | $306,600 |
| 20,000 | 17,520,000 | $1,226,400 |
Overhead for a 1,000 kW IT load at different PUE
| PUE | Facility kW | Overhead kW | DCiE percent | Overhead cost per year at $0.07 |
|---|---|---|---|---|
| 1.20 | 1,200 | 200 | 83.3 | $122,640 |
| 1.40 | 1,400 | 400 | 71.4 | $245,280 |
| 1.52 | 1,520 | 520 | 65.8 | $318,864 |
| 1.80 | 1,800 | 800 | 55.6 | $490,560 |
| 2.00 | 2,000 | 1,000 | 50.0 | $613,200 |
The 1.52 row is the Uptime Institute industry average. The other rows are examples, not measurements of any site.
Where the overhead comes from
Cooling is the largest piece in most sites. The electrical chain adds losses too, in the utility transformer, UPS, switchgear and distribution transformers. See data center transformers, the UPS sizing calculator and data center power equipment. Convert kW and amps with the kW to amps calculator.
Planning a data center service, request a quote with the kW and voltage.
Common questions
What is PUE in a data center
Power usage effectiveness is total facility power divided by the power used by IT equipment. A PUE of 1.5 means that for every 1 kW of servers the site draws 1.5 kW in total, and the extra 0.5 kW goes to cooling, power conversion and lighting.
How do you calculate PUE
Divide total facility kW by IT equipment kW. A site at 1,500 kW with 1,000 kW of IT load has a PUE of 1.50. The inverse, IT power divided by facility power, is called DCiE and here equals 66.7 percent.
What is the average PUE for data centers
Uptime Institute reports an industry wide annual average of about 1.52 in its 2026 analysis, and describes the global average as relatively stable since 2018, with large differences by region and facility size. Another Uptime summary puts the industry near 1.55 in recent years.
What is a good PUE
Lower is better and 1.0 is the floor. Modern large facilities with efficient cooling run well below the industry average, and smaller or older rooms run above it. Compare against the same region and size, since Uptime finds the average hides large differences.
How much does 0.1 of PUE cost
For a 1,000 kW IT load, each 0.1 of PUE is 876,000 kWh a year, which is $61,320 at $0.07 per kWh. The cost scales directly with IT load and your rate.
Do transformers affect PUE
Yes, a little. Transformer, UPS and switchgear losses sit between the utility and the servers, and they count as facility power and not IT power. Choosing efficient transformers cuts that overhead, though cooling is usually the larger share.
Sources
- Uptime Institute intelligence update of August 2026 on the PUE advantage of larger data centers, industry wide annual average PUE of 1.52.
- Uptime Institute update of October 2025 on PUE trends by region, age and size, global average PUE relatively stable since 2018 with large differences by region and facility size.
- Upsite summary of Uptime Institute survey trends, industry PUE near 1.55 and flat. Figures for Google and other operators were not confirmed in this research and are left out.
- Overhead kWh and cost are computed here as IT kW times PUE minus one times 8,760 hours, at the rate you enter. Rates in the table are examples.