Home / Products / Data center power / Three phase UPS by kVA, 10 to 1500 kVA, kW table, sizing and pricing
Three phase UPS by kVA, 10 to 1500 kVA, kW table, sizing and pricing
A UPS is sold in kVA but your load is in kW, and the gap between them is the output power factor. A 500 kVA UPS is 450 kW at 0.9 and 500 kW at unity. This page gives the full kVA to kW table, real examples of each rating style, how to size with headroom and redundancy, and the little pricing the public record shows. We quote UPS systems delivered.
Updated November 21, 2026
kVA to kW table for three phase UPS
Output power factor decides the kW. Delta lists its DPS line from 100 to 500 kVA at 0.9, with the DPS 500K at 500 kVA and 450 kW. Delta lists its NT 100K at 100 kVA and 80 kW, a 0.8 rating. ABB lists its SG series at 0.9 from 10 to 500 kVA. Modular UPS are often rated at unity, and the APC Symmetra PX 100 kW is rated so kVA equals kW. Always read kW from the nameplate, not the kVA.
| UPS rating | kW at 0.8 | kW at 0.9 | kW at unity |
|---|---|---|---|
| 10 kVA | 8 kW | 9 kW | 10 kW |
| 20 kVA | 16 kW | 18 kW | 20 kW |
| 30 kVA | 24 kW | 27 kW | 30 kW |
| 50 kVA | 40 kW | 45 kW | 50 kW |
| 60 kVA | 48 kW | 54 kW | 60 kW |
| 80 kVA | 64 kW | 72 kW | 80 kW |
| 100 kVA | 80 kW | 90 kW | 100 kW |
| 120 kVA | 96 kW | 108 kW | 120 kW |
| 150 kVA | 120 kW | 135 kW | 150 kW |
| 160 kVA | 128 kW | 144 kW | 160 kW |
| 200 kVA | 160 kW | 180 kW | 200 kW |
| 250 kVA | 200 kW | 225 kW | 250 kW |
| 300 kVA | 240 kW | 270 kW | 300 kW |
| 400 kVA | 320 kW | 360 kW | 400 kW |
| 500 kVA | 400 kW | 450 kW | 500 kW |
| 750 kVA | 600 kW | 675 kW | 750 kW |
| 1000 kVA | 800 kW | 900 kW | 1000 kW |
| 1200 kVA | 960 kW | 1080 kW | 1200 kW |
| 1500 kVA | 1200 kW | 1350 kW | 1500 kW |
Computed as kVA times power factor. Real products come in other sizes, so use the table to compare, not to pick a model.
How to size a UPS
Add up the load in kW, add growth, then divide by the power factor of the UPS you are considering. A forum answer from Schneider Electric support gives the example that a 160 kW load needs a UPS rated around 200 kVA. Our arithmetic gives 160 divided by 0.9, or about 178 kVA, so the next common size up is 200 kVA, which leaves about 11 percent headroom at 0.9.
Redundancy changes the count. N plus 1 adds one spare module to the number needed for the load, and 2N doubles the whole system. A modular UPS makes N plus 1 easier because you add a power module rather than a whole cabinet.
Published prices
Three phase UPS pricing is mostly quote based. Across the vendor pages we read, we found no published price for a 100 kVA or 500 kVA system. The one concrete figure is a CDW listing for a three phase 30 kVA data center tower UPS at $17,588.99, marked down from $27,650. That is one retail listing, not a market benchmark, and it does not scale to larger sizes. Prices depend on batteries, runtime, redundancy, service and installation.
Lead time
We found no published lead time for three phase UPS. We state the lead time on every quote.
Brands you will see
Three phase UPS ranges named by the sources we read include Schneider Electric Galaxy and Symmetra, Delta Ultron and DPS, ABB SG series and Mitsubishi 9900CX. Send the model you are comparing and we quote the same or a match.
What to send for a quote
- Load in kW and the power factor of the load
- Required runtime and battery type
- Input and output voltage
- Redundancy, N, N plus 1 or 2N
- Brand or model you are comparing
- Room or cabinet limits and bypass needs
- Delivery ZIP code and the date you need it on site
Common questions
How many kW is a 500 kVA UPS
At 0.9 power factor it is 450 kW. At unity it is 500 kW. At 0.8 it is 400 kW. Check the nameplate.
How many kW is a 100 kVA UPS
At 0.9 it is 90 kW, at 0.8 it is 80 kW and at unity it is 100 kW.
How much does a 500 kVA UPS cost
We found no public price for a 500 kVA system. UPS pricing is quote based and depends on batteries, redundancy and service.
What size UPS do I need for a 160 kW load
About 178 kVA at 0.9 power factor, so a 200 kVA UPS is the next common size, before growth and redundancy.
Related pages
Sources
- Delta, DPS series 160 to 500 kVA specifications
- Delta, NT series 20 to 500 kVA
- ABB, SG series technical data
- APC, Symmetra PX 100 kW
- Schneider Electric community, UPS power calculation
- CDW, APC Easy UPS 3S 30 kVA listing
Market figures are public asking prices and published industry figures, dated where the source gives a date. They are not our prices. A quote from us is a delivered price for a specific unit.