Padmount Supply

Home / Products / Data center power / Three phase UPS by kVA, 10 to 1500 kVA, kW table, sizing and pricing

Three phase UPS by kVA, 10 to 1500 kVA, kW table, sizing and pricing

A UPS is sold in kVA but your load is in kW, and the gap between them is the output power factor. A 500 kVA UPS is 450 kW at 0.9 and 500 kW at unity. This page gives the full kVA to kW table, real examples of each rating style, how to size with headroom and redundancy, and the little pricing the public record shows. We quote UPS systems delivered.

Updated November 21, 2026

Request a UPS quoteOr call 786 220 2801.

kVA to kW table for three phase UPS

Output power factor decides the kW. Delta lists its DPS line from 100 to 500 kVA at 0.9, with the DPS 500K at 500 kVA and 450 kW. Delta lists its NT 100K at 100 kVA and 80 kW, a 0.8 rating. ABB lists its SG series at 0.9 from 10 to 500 kVA. Modular UPS are often rated at unity, and the APC Symmetra PX 100 kW is rated so kVA equals kW. Always read kW from the nameplate, not the kVA.

UPS ratingkW at 0.8kW at 0.9kW at unity
10 kVA8 kW9 kW10 kW
20 kVA16 kW18 kW20 kW
30 kVA24 kW27 kW30 kW
50 kVA40 kW45 kW50 kW
60 kVA48 kW54 kW60 kW
80 kVA64 kW72 kW80 kW
100 kVA80 kW90 kW100 kW
120 kVA96 kW108 kW120 kW
150 kVA120 kW135 kW150 kW
160 kVA128 kW144 kW160 kW
200 kVA160 kW180 kW200 kW
250 kVA200 kW225 kW250 kW
300 kVA240 kW270 kW300 kW
400 kVA320 kW360 kW400 kW
500 kVA400 kW450 kW500 kW
750 kVA600 kW675 kW750 kW
1000 kVA800 kW900 kW1000 kW
1200 kVA960 kW1080 kW1200 kW
1500 kVA1200 kW1350 kW1500 kW

Computed as kVA times power factor. Real products come in other sizes, so use the table to compare, not to pick a model.

How to size a UPS

Add up the load in kW, add growth, then divide by the power factor of the UPS you are considering. A forum answer from Schneider Electric support gives the example that a 160 kW load needs a UPS rated around 200 kVA. Our arithmetic gives 160 divided by 0.9, or about 178 kVA, so the next common size up is 200 kVA, which leaves about 11 percent headroom at 0.9.

Redundancy changes the count. N plus 1 adds one spare module to the number needed for the load, and 2N doubles the whole system. A modular UPS makes N plus 1 easier because you add a power module rather than a whole cabinet.

Published prices

Three phase UPS pricing is mostly quote based. Across the vendor pages we read, we found no published price for a 100 kVA or 500 kVA system. The one concrete figure is a CDW listing for a three phase 30 kVA data center tower UPS at $17,588.99, marked down from $27,650. That is one retail listing, not a market benchmark, and it does not scale to larger sizes. Prices depend on batteries, runtime, redundancy, service and installation.

Lead time

We found no published lead time for three phase UPS. We state the lead time on every quote.

Brands you will see

Three phase UPS ranges named by the sources we read include Schneider Electric Galaxy and Symmetra, Delta Ultron and DPS, ABB SG series and Mitsubishi 9900CX. Send the model you are comparing and we quote the same or a match.

What to send for a quote

  • Load in kW and the power factor of the load
  • Required runtime and battery type
  • Input and output voltage
  • Redundancy, N, N plus 1 or 2N
  • Brand or model you are comparing
  • Room or cabinet limits and bypass needs
  • Delivery ZIP code and the date you need it on site
Request a UPS quoteOr call 786 220 2801.

Common questions

How many kW is a 500 kVA UPS

At 0.9 power factor it is 450 kW. At unity it is 500 kW. At 0.8 it is 400 kW. Check the nameplate.

How many kW is a 100 kVA UPS

At 0.9 it is 90 kW, at 0.8 it is 80 kW and at unity it is 100 kW.

How much does a 500 kVA UPS cost

We found no public price for a 500 kVA system. UPS pricing is quote based and depends on batteries, redundancy and service.

What size UPS do I need for a 160 kW load

About 178 kVA at 0.9 power factor, so a 200 kVA UPS is the next common size, before growth and redundancy.

Related pages

Sources

Market figures are public asking prices and published industry figures, dated where the source gives a date. They are not our prices. A quote from us is a delivered price for a specific unit.

CallGet a quote