Home / Products / Switchgear / Medium voltage switchgear

Medium voltage switchgear

Medium voltage switchgear controls, protects and isolates equipment between 1 kV and about 42 kV. For most buyers that means one of three products, metal clad gear with drawout breakers in a building or e-house, metal enclosed gear that costs less and takes less room, or pad mounted gear that sits outdoors on a slab beside the transformer. Lead times for new gear have run 52 to 80 weeks at 15 kV, so many buyers look at stock, surplus and reconditioned units too. We source all of it from US and overseas makers and quote it delivered to site.

Updated November 17, 2026

Which type of medium voltage switchgear do you need

Pick by where it sits and how it is used. The table sorts the three common products. Ratings are the classes the standards and makers publish, so confirm the exact figures for your project with the maker.

TypeWhere it is usedTypical ratingsMain reason to choose it
Metal cladPlant substations, data center and utility buildings, e-houses4.76 to 38 kV maximum voltage, main bus 1,200 to 4,000 A (IEEE C37.20.2)Drawout breakers in grounded compartments, the most serviceable and the usual choice for main and feeder breakers
Metal enclosedSwitching, fused feeders, smaller plantsLoad interrupter and fused designs, see the Eaton comparisonLower cost and smaller footprint than metal clad
Pad mountedUtility loops, campuses, solar collector feeders, data center yardsS&C PMH and PME gear is offered at 14.4 and 25 kV with 600 A switchesOutdoor, compact, dead front or live front, fits beside a pad mounted transformer

Metal clad ratings from IEEE C37.20.2 as summarized by IEEE. Pad mounted ratings from S&C Electric bulletins. Metal enclosed versus metal clad cost and size from Eaton and IEEE Region 6 comparisons.

Metal clad gear

IEEE C37.20.2 defines metal clad switchgear. The main switching and interrupting device is a removable drawout breaker, major parts are separated by grounded metal barriers, and shutters cover the primary stabs when the breaker is withdrawn. Rated maximum voltage runs from 4.76 kV to 38 kV and main bus ratings are 1,200, 2,000, 3,000 and 4,000 A. The 2015 edition has been superseded by a newer one, so quote requests should say which edition the project specification cites. The full guide is at metal clad switchgear.

Pad mounted gear

Pad mounted switchgear is outdoor gear on a slab, used to sectionalize loops and protect feeders. S&C offers its PMH and PME gear at 14.4 and 25 kV. Solid dielectric designs such as the Eaton ISG-SD are described for 4 to 27 kV with fault interruption up to 20 kA. G&W describes its gas insulated gear for systems up to 38 kV, 900 A continuous, and its solid dielectric and junction bar products up to 35 kV. PTR research reported by T&D World puts pad mounted gear at 75 percent of the US underground switchgear market. The full guide is at pad mounted switchgear.

Lead times and prices today

Terrapin procurement data from June 2026, reported by IndustrialSage, puts 15 kV switchgear at 52 to 80 weeks and 38 kV equipment at 78 to 104 weeks, against about 24 weeks before the pandemic. An earlier PTR estimate had averages of 26 to 32 weeks after the pandemic, so check the date on any figure you are given. Electrical Trader reports medium voltage switchgear prices up 50 percent and a 15 percent Section 232 tariff on finished grid equipment through December 31, 2027, rising to 25 percent in 2028.

Public budget ranges, including used and reconditioned, are on the price guide. Used and reconditioned gear that already exists can ship much sooner, see used switchgear.

Brands we source

We quote Eaton, Siemens, Schneider Electric and Square D, ABB, Powell, S&C Electric, G&W Electric and others, new, surplus or reconditioned. If you are extending a lineup, match the series and vintage of the existing gear, and send us the nameplate.

Standards buyers specify

IEEE C37.20.2 defines metal clad gear. Pad mounted gear follows the utility or owner standard, so ask your engineer for the exact list. Arc resistant gear is tested to IEEE C37.20.7, and Siemens lists its GM-SG arc resistant variant to Type 2B.

What to send for a quote

  • Nominal system voltage and the maximum voltage class wanted, for example 13.2 kV or 34.5 kV
  • Main bus amps and the short circuit rating in kA
  • Number of breakers, switches or ways, and the feeder schedule
  • Indoor or outdoor, and arc resistant or not
  • New, new surplus or reconditioned, and the date you need it on site
  • A photo of the nameplate if you are matching an existing lineup
  • Delivery ZIP code

Common questions

What is the difference between metal clad and metal enclosed switchgear

Metal clad is a stricter subset. It needs drawout breakers, grounded metal barriers between compartments, shutters and insulated bus. Metal enclosed gear can use fixed devices, usually costs less and takes less floor space.

What voltage is medium voltage switchgear

T&D World describes the range as 1 kV to about 42 kV. Metal clad gear under IEEE C37.20.2 is rated 4.76 to 38 kV maximum voltage.

How long does medium voltage switchgear take to deliver

Terrapin data from June 2026 gives 52 to 80 weeks at 15 kV and 78 to 104 weeks at 38 kV for new gear. Stock, surplus and reconditioned units can be much faster.

Can you supply used medium voltage switchgear

Yes. We source used, surplus and reconditioned gear and quote it delivered. Tests and warranty norms are on the used switchgear page.