Home / Guides / Buying Used Electrical Equipment Safely, A Checklist
Buying Used Electrical Equipment Safely, A Checklist
Used electrical equipment can save money and weeks of lead time, but only if you know its history. Ask who reconditioned it and when, check for water or fire damage, get test reports, and test it again on arrival before it is energized. Your inspector has the final word.
Updated November 18, 2026
Who you are buying from
A dealer who reconditions and tests equipment is a different seller from a broker who passes along a listing. Ask whether the seller did the work, what was done and who stands behind it. Ask for the unit's service history and why it came out of service.
Paperwork to demand
Get a copy of the nameplate photo, the last test reports and a written description of any reconditioning. For liquid filled units ask for the oil test report, including PCBs, which the PCB guide explains. Keep every document with the unit.
Reconditioned equipment under the NEC
NEC 110.21(A)(2) requires reconditioned equipment to be marked with the name or mark of the reconditioner and the date, and the 2023 edition lists wording such as reconditioned or an approved symbol. Approval cannot rest only on the original listing, and the authority having jurisdiction may approve it. An exception covers equipment reconditioned by the owner in a regular maintenance program with qualified staff. Wording changed between editions, so confirm the edition your jurisdiction enforces.
Water and fire damage
NEMA publishes guidance on evaluating water damaged equipment, and it separates what can be reconditioned from what should be replaced.
| Equipment | NEMA guidance on water damage |
|---|---|
| Molded case circuit breakers | Replace |
| Fusible units of fused equipment | Replace |
| Electronic trip units, protective relays and meters | Replace |
| Low voltage power and medium voltage breakers | May be refurbished in close consultation with the maker |
| Larger equipment | May be reconditioned by trained personnel after talking to the maker |
From the NEMA guide Evaluating Water Damaged Electrical Equipment. Editions differ, so read the current one before you decide.
Testing on arrival
Do not energize on the seller's word. ANSI/NETA ATS covers acceptance testing of switchgear, transformers, cables, breakers, relays and more, with separate sections for liquid filled and dry type transformers. Switchgear checks include nameplate data against drawings and phasing. Hire a qualified test firm and ask which parts of the standard they will run.
Inspector and insurer
Talk to the inspector before you buy. Ask whether used or reconditioned gear is accepted for the job, what marking and records they want, and whether your insurer has requirements. A unit you cannot get approved is not a bargain.
Red flags
No nameplate or a painted over one, no test records, a seller unwilling to say where it came from, signs of water lines or soot, and a price far below the market. Walk away or have an independent firm inspect first.
Related pages
Common questions
Is it safe to buy used electrical equipment
It can be, when the seller documents the history and reconditioning, the unit has no flood or fire damage and you test it before energizing.
Does used equipment need a special label
Under NEC 110.21(A)(2), reconditioned equipment must be marked with the reconditioner and the date, with limited exceptions. Check your local edition.
Can flood damaged breakers be reused
NEMA guidance says to replace molded case breakers. Larger breakers may be refurbished with the maker's help.
What testing should I do on arrival
Have a qualified firm run acceptance tests to ANSI/NETA ATS before energizing.
Sources
- NEMA, Evaluating Water Damaged Electrical Equipment
- Eaton, NEC 2023 reconditioned equipment
- Electrical Contractor, reconditioning requirements under the NEC
- ANSI Blog, ANSI/NETA ATS-2025
- Electrical Trader, NETA standards guide
Free to cite with a link to this page. Work out current at any rating with the kVA to amps calculator.