Why Transformers and Power Lines Hum, Buzz and Crackle

A steady low hum is normal. A transformer core expands and contracts twice per AC cycle, so on a 60 Hz system it hums at 120 Hz, and on a 50 Hz system at 100 Hz. Crackling from overhead lines is usually corona and is louder in fog and rain. Sparking, popping, a strong odor or a sudden change are different and should be reported.

Updated November 15, 2026

Why transformers hum

Magnetostriction makes the core change shape slightly as the magnetic field reverses. It happens twice each cycle, giving the 120 Hz tone. Design can reduce it but not remove it. Cooling systems and winding forces add noise, and the hum is slightly higher at no load and falls as load rises.

Sound level by kVA

Sources tied to NEMA ST 20 give maximum average sound levels by size for dry type units. They differ at the boundaries, so treat the table as typical.

kVATypical limit in dB
0 to 940
10 to 5045
51 to 15050
151 to 30055
301 to 50060
501 to 70062
701 to 100064

Sound levels are measured at a set distance from the unit. One table continues to 65 to 68 dB for 1001 to 3000 kVA. Check the standard before specifying.

Crackling and buzzing on power lines

Lines are designed to stay below the corona inception voltage in dry weather. In fog, rain and snow, water droplets cause corona discharge, heard as crackle or hum. Corona can also come from insulators that are damaged, deteriorated or contaminated. It wastes a little power and can wear components over time.

Sound by sound

Steady low hum, normal. Crackle in fog or rain from a high voltage line, usually corona. Loud buzz that changes, sparking, popping, a glowing insulator, burning smell or oil, report it. A sharp noise, strong odor or scorch marks on a green pad mount box are not normal.

When to call

Call the utility for damage, sparking, a sagging or broken line or any unusual change. Stay well away, even at ground level. Never touch the equipment.

Reducing noise

For a transformer you own, the unit sound rating, the mounting and the room all matter. Specify a low sound unit when buying and ask the maker for the guaranteed level.

Related pages

Common questions

Is a humming transformer dangerous

A steady hum is normal. Sparking, popping or a burning smell is not.

What frequency does a transformer hum at

120 Hz on 60 Hz systems and 100 Hz on 50 Hz systems.

Why do power lines crackle in the rain

Corona discharge from water droplets on the conductors and hardware.

Why is the transformer louder than before

A change in load, voltage or mounting can shift the hum. A sudden large change should be reported.