What Is Busway, Busway vs Bus Duct vs Busbar and How It Is Rated
Busway is a prefabricated electrical distribution system, busbars inside a protective metal housing, that carries power from a source such as a transformer or switchboard to where it is used. It replaces large cable and conduit runs. Bus duct is the older name for the same thing. The busbar is the conductor bar inside it. NEC Article 368 covers busway and UL 857 is its product standard.
Updated November 16, 2026
Busway, bus duct and busbar
Busway and bus duct are used for the same product in catalogs and specifications. A busbar is the copper or aluminum bar itself, and a busway is the factory assembled run of bars, insulation and housing that arrives in sections. Bus conductors in busway are copper or aluminum, and manufacturers offer either.
Feeder, plug in and data center busway
Feeder busway carries power from point to point where no tap offs are needed. Plug in busway has openings along its length where tap off boxes, each with a breaker or fused switch, are installed. One catalog for 400 to 6000 A busway describes up to 10 plug in openings per 10 foot section. Data center busway is a lighter, open channel product, with one maker rating 250 to 800 A and offering tap off boxes that plug in, are removed and are relocated along the run while the busway is energized. That flexibility to move, add and change racks is the main argument against traditional whip cabling in white space.
Ratings and standards
UL 857 is the UL standard for busway and allows ampacity ratings based on temperature rise. NEC Article 368 covers installation. Published busway ranges depend on the product line. The catalog examples used here are 400 to 6000 A for a feeder and plug in line, and 250 to 800 A for a data center line with up to 6 conductors, meaning three phases, two neutrals and a ground. Housings are rated for ingress protection, and the data center line cited here is IP23D.
Busway from a transformer secondary
A pad mounted or dry type transformer secondary at 480 volts carries a large current, and large secondaries are exactly where busway competes with parallel cable runs. The table computes full load secondary current from kVA for a three phase 480 volt secondary. Check the figure against the busway rating and the feeder protection.
| Transformer kVA | Secondary amps at 480 V three phase |
|---|---|
| 500 | 601 |
| 750 | 902 |
| 1,000 | 1,203 |
| 1,500 | 1,804 |
| 2,000 | 2,406 |
| 2,500 | 3,007 |
Computed as kVA x 1000 / (1.732 x 480).
Busway vs cable and conduit
A plug in run gives many tap points for later changes, and data center busway moves tap offs along the run while energized, which whip cabling cannot. Always get the voltage drop and short circuit ratings from the manufacturer data for the exact product, because they differ by line and conductor material.
Related pages
Common questions
What is busway used for
To distribute power in a building or plant using busbars in a metal housing, from a transformer or switchboard to panels, equipment and racks.
What is the difference between busway and bus duct
None in practice. Both terms describe the same prefabricated busbar system.
What is the difference between busway and busbar
A busbar is a single conductor bar. A busway is the factory assembled system of busbars, insulation and enclosure.
What is plug in busway
Busway with openings along its length for tap off boxes with breakers or fused switches, so loads can be added without cutting the run.
What NEC article covers busway
Article 368 covers busways. UL 857 is the product standard.
What amperage does busway come in
It depends on the line. Examples are 250 to 800 A for data center busway and 400 to 6000 A for a feeder and plug in line.
Sources
- EAE USA, KX-III busway 400 to 6000 A
- EAE USA, KD-III data center busway 250 to 800 A
- EAE USA, busway FAQ
- Consulting Specifying Engineer, how to specify metal clad cable and busways
- Vertiv, PowerBar HPB UL guide specifications
Free to cite with a link to this page. Work out current at any rating with the kVA to amps calculator.